4. Specifications
Type (FVR _ _ _ |
|
| F12 |
| F25 | F50 |
| 001 |
| 002 | |
Applicable motor output1 |
| [Hp] | 1/8 |
| 1/4 | 1/2 |
| 1 |
| 2 | |
| Rated capacity2 |
| [kVA] | 0.27 |
| 0.5 | 0.87 |
| 1.5 |
| 2.7 |
| Voltage |
| [V] | ||||||||
|
|
|
| to input voltage) |
|
|
|
|
|
| |
Output Rating | Rated current |
| [A] | 0.66 |
| 1.2 | 2.1 |
| 3.7 |
| 6.4 |
| Overload current rating |
| 150% 1 min. |
|
|
|
|
|
| ||
| Rated frequency |
| [Hz] | 50/60 Hz |
|
|
|
|
|
| |
| Phase, voltage, frequency |
|
|
|
| ||||||
| Allowable variation in |
| Voltage: =10 - 15% Frequency: 15% (Imbalance in power |
| |||||||
Input power | voltage/frequency |
|
| supply voltage: 3%) |
|
|
|
|
| ||
supply | Instantaneous voltage drop |
| Drive is kept running if voltage is 165V or more. If voltage drops | ||||||||
| withstanding capacity |
| more than 165V from rated voltage, drive is run for 15ms.3 |
| |||||||
| Required power supply | [kVA] | 0.3 |
| 0.6 | 1.0 |
| 1.7 |
| 3.1 | |
| capacity |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |
| Adjustment | Max. freq.4 | [Hz] |
| |||||||
|
| Base freq. | [Hz] |
| |||||||
| Starting freq. | [Hz] |
| ||||||||
Output | Accuracy |
|
| Analog setting: ±1.0% of max. frequency (25±10°C) |
| ||||||
frequency |
|
|
| Digital setting: ±0.01% of max. frequency |
| ||||||
| Setting resolution |
|
| Analog setting:1/255 of max. frequency |
|
|
| ||||
|
|
|
|
| (ex. 0.25 Hz / 60 Hz, 0.5 Hz / 120 Hz) |
| |||||
|
|
|
| Digital Setting: 0.1 Hz (99.9 Hz max) 1 Hz |
| ||||||
| Control method |
|
| Sine wave PWM control |
|
|
|
|
| ||
|
|
|
| (Extremely low noise by high frequency carrier) |
| ||||||
Control | Operation |
|
| Keypad operation: | Operation control by RUN/STOP keys | ||||||
|
|
|
| Terminal strip: |
| Forward command. Reverse command. | |||||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| External alarm. |
|
|
| |
1) "Applicable motor" indicates a standard |
|
|
|
|
| ||||||
|
|
|
|
|
|
2)"Rated capacity" indicates a capacity at 240V rating.
3)This applies to the case where momentary power failure occurs under such conditions that rated voltage is inputted and load factor is 85%.
4)Shows the case where an applicable motor equipped with an AC reactor (option) on the input side is used.
8