GE FVR-C9S-7UX instruction manual Setting with UP/DOWN keys

Page 9

FVR-C9S-7UX

Type (FVR _ _ _ C9S-7UX)

 

F12

 

F25

F50

001

 

002

 

Applicable motor output1

[Hp]

1/8

 

1/4

1/2

1

 

2

 

 

Frequency setting

 

Key operation:

 

Setting with UP/DOWN keys

 

 

 

Potentiometer:

 

Terminal for 1-5K ohm VR is provided

 

 

 

Analog signal:

 

0-5 VDC 0-10 VDC (resistance = 12k ohm)

 

 

 

 

 

 

4-20 mA (resistance = 250 ohm)

 

Display

Run mode

Output frequency is displayed. (3 digit LED)

 

 

 

 

Fault mode

Cause of fault is displayed.

 

 

 

 

 

 

Other

LED comes on with charging voltage applied.

 

 

 

Acceleration/Deceleration time

0-60s (Variable setting) Acceleration time and deceleration

 

Control

 

 

time can be set independently.

 

 

 

 

 

Voltage frequency characteristics

Setting of maximum frequency/base frequency is variable.

 

 

Restart after momentary power failure

"Automatic restart" setting makes it possible to keep motor

 

 

 

 

running and restart drive in case of a momentary power failure.

 

High Limiter & Low Limiter

 

Upper limit and lower limit of frequency can be set.

 

 

 

Bias setting

 

Bias setting is possible with respect to analog frequency setting.

 

 

Jump frequency

 

Three jump points and one jump width can be set.

 

 

 

Torque boost

 

Setting variable in 32 steps.

 

 

 

 

 

Starting torque

[%]

150% for 60 seconds.

 

 

 

 

 

 

Braking torque5

[%]

150% 1 min.

100% 1 min.

 

50% 1 min.

Braking

DC brake

 

Brake starting frequency: 3 Hz (fixed)

 

 

 

 

 

Setting of braking current / braking time is variable.

 

 

 

Overload

 

Detects overload current and stops drive.

 

 

 

Momentary overcurrent

 

Protects drive In case of ground fault (detects at start) and

 

 

 

 

short circuit of output circuit.

 

 

 

 

 

Overvoltage

 

Detects overvoltage of DC bus and stops drive.

 

 

Protection

Overheating of cooling element

Detects abnormal temp. rise of cooling element and stops drive.

 

 

Motor protection

 

Protects standard 4-pole motor and forced-air cooled motor by

 

 

 

 

means of electronic thermal overload relay.

 

 

 

Alarm protection

 

Outputs contact signal in case of a trip for protection

 

 

 

 

(1c contact capacity: AC250V 0.3A

cos = 0.3)

 

 

 

Installation location

 

Indoor at an altitude of 3283 feet (1000m) or less and free of

 

 

 

dust, corrosive gas and oil mist.

 

 

 

 

 

Ambient temperature

 

-10 to 50°C

 

 

 

 

 

 

 

Ambient humidity

 

20 -90% RH (There shall be no dew condensation)

 

 

Environment

Vibration

 

19 feet/s2 (5.9m/s2) or less

 

 

 

 

 

 

 

Vibration frequency: 5 - 55 Hz

 

 

 

 

 

Storage temperature

 

-25 to 65°C

 

 

 

 

 

 

 

Atmospheric pressure

 

Operation/storage: min 900 mb (equivalent to 3283 feet (1000m)

 

 

 

 

Transport: min 660 mb (equivalent to 10720 feet (3265m)

 

Enclosure

 

IP20

 

 

 

 

 

 

Cooling method

 

Self-cooling (up to 1 Hp), forced-air cooling (2 Hp)

 

 

5) This indicates average braking torque of a single motor. (Value varies according to motor efficiency.

C92-7-14

 

9

Image 9
Contents FVR-C9S-7UX Drive Series Product specifications are subject to change without notice Contents Fire and Personal Injury Hazard Safety PrecautionsOperation Electric Shock Hazard Nameplate Inspection Upon ReceiptPart Names Supply voltage 3% SpecificationsSetting with UP/DOWN keys External Dimensions DWG 2 FVR002C9S-7UX Wiring Installation InstructionsInstallation Conditions Mounting Direction and SpaceRequired for CE Certification Keypad Panel Operation Basic Wiring Diagram50/60Hz Phase External Signal OperationMccb Elcb Application of Wiring and EquipmentTerminal Function Explanation Terminal Function ExplanationClassi Terminal Code Terminal Name Explanation of Function Operation Frequency Setting MethodPre-Operation Inspection Test Run Check PointsRUN/STOP Selecting Operation MethodKeypad Panel Part Names and FunctionsControlling Method for Keypad Panel Method Operation Procedure Display Function Code Tables Motor Running Code Detailed Explanation of Each Function Code Torque Boost 8 Electronic Thermal Overload RelayElectronic Thermal Overload Relay Level Current 1 Gain for Frequency Setting Signal 2 DC Brake3 DC Brake Braking Time 6 Fault Memory 4 Starting Frequency5 Motor Running Sound 7 Data Initialization 9 Motor Characteristics8 Retry Jump Frequency Range6 Bias Frequency 4 High Limiter F 2 5 Low Limiter7 THR Terminal Function 8 BX Terminal FunctionMultistep Speed Setting 1 Speed Multistep Speed Setting 2 SpeedMultistep Speed Setting 3 Speed 3 FM Terminal Function Selection 2 FM Terminal Output Level CalibrationOC3 Protective FunctionsTechnical Services GE Fuji Drives USA, Inc Warranty Parts and ServiceOut-of-Warranty Procedures MotorsLatest Fault Previous Faults No Message In-Warranty Failure ChecklistElectromagnetic Compatibility EMC Recommended Installation InstructionsGeneral RFI FiltersLine Noise filter EnclosureRFI FVR-C9S-7UX Product identification EC Declaration of ConformityEC Declaration of Conformity FVR-C9S-7UX