Bay Technical Associates DS72 manual No Outlets displayed for User, Not able to Ping unit

Page 33

DS72 Host Module

6.No Outlets displayed for User:

a.Outlets have to be assigned to the user, refer to ‘DS Configuration User Management Assigned Outlets’ section.

7.Not able to PING unit:

a.Verify unit connected correctly to network.

b.Verify unit network configuration is correct.

c.In the Network Configuration Status Menu, verify the unit has a valid MAC address. The last six digits of the MAC address are the hexadecimal equivalent of the first eight digits of the unit serial number. (i.e. MAC address = 00:C0:48:0A:B6:59 equals to decimal 702041)

8.Verify DS chassis, Host module, and DS74 is functioning:

A rollover cables (pin out 1-8, 2-7, 3-6, 4-5, 5-4, 6-3, 7-2, 8-1) and a 9-pin adapter (9FRJ45PC-

1)and Ethernet or Modem cable.

a.Set up the Host module with modem or Ethernet cables for normal operations.

b.Connect the rollover cable and adapter from the PC to a DS74 port.

c.Create a Modem/Ethernet session, (Hyper-terminal). Type semi-colon 5-times (; ; ; ; ;).

d.The main menu should display the DS74 ports. Select the port connected to the PC from step 2. The cursor will move to next line and wait.

e.From your PC create a terminal session to the serial port. Default setting is 9600, 8, 1, no parity, no flow.

f.Type several random characters to see them echoed in the telnet/modem session.

g.Select the telnet/modem session and type several random characters to see them echoed in the PC serial session.

h.This verifies the Chassis, Host module, and the I/O port is working.

i.Move pc cable to next DS74 port and repeat steps (c-h).

DS72 Factory reset Procedure

1.Remove the module from the chassis (with the unit powered down).

2.Hold the module with the chip side up and the faceplate towards you.

3.Locate jumper JP1.

4.Move the jumper from pins 1 and 2 to pins 2 and 3.

5.Put the module back in the chassis and power up for 15 seconds.

6.Take the module back out and replace the jumper to the original position.

The module will now be reset to factory default.

33

Image 33
Contents DS Series Manual DS72 Host Module EIA-232 Serial Connection DS72 Host Module Connection Description Power InstallationQuick Start DS72 Module Ethernet Controller ConfigurationMain Menu Serial Port SetupAccess Control Login SetupHeader Manage UsersNetwork Port Configuration Adapters Signals CablingRJ-45 Cables and Adapters Adapters Main Screen Detailed Operation and ConfigurationConfiguration Status Configuration MenuDS72 Host Module Serial Port ConfigurationBaud Rate Word SizeStop Bits Parity Xon/XoffRTS/DTR Line Driver Inactivity State Disconnect Timeguard Serial Port Device NameConnection Override Connect Port ID EchoHeader Access ControlChange User’s Password Manage UsersAdd User Delete User Snmp ConfigurationSnmp Enable Snmp Trap Host X IP AddressRead/Write Community String IP Address Subnet Mask Inactivity TimeoutGateway Carriage Return TranslationDHCP/Telnet/BootP Unit IDBreak Length Active Restore Upgrade FirmwareUnder Voltage Alarm Threshold Temperature Alarm ThresholdRPC Management Multiple Strip Current MonitorOver Voltage Alarm Threshold Low Current Alarm ThresholdEnvironmental Sensors Selection 1, the Host Module responds System StatusTroubleshooting Unit ResetNetwork Interface Logged UsersNo Access to Configuration Menu Password not WorkNo Menu Ethernet Port Network session locks upNo Outlets displayed for User Not able to Ping unitVerify DS chassis, Host module, and DS74 is functioning DS72 Host Module Cabling DS72 SetupExceptions BayTech Product WarrantyEmail support@baytech.net Technical SupportReturn Authorization Process