DS72 Host Module
Active restore is.................Enabled
Enable ? (Y/N, CR for no change) :
RPC Management
These options are independent of the power strip’s Alarm Thresholds. It is through these settings that the DS72 SNMP agent will send a (trap) to the designated SNMP Manager.
This allows you to set the temperature, voltage and current threshold alarms for the unit remotely without ever entering the firmware of the RPC itself as shown.
| |||
Temperature Alarm Threshold | 1 | Enter value in tenths of unit measurement | |
Multiple Strip Current Monitor..2 | Sets | alarm values for RPC strips | |
Under Voltage Alarm Threshold... | 3 | Enter value in tenths of a voltage | |
Over Voltage Alarm Threshold.... | 4 | Enter value in tenths of a voltage | |
Low Current Alarm Threshold | 5 | Enter value in tenths of an amperage | |
Environmental Sensors | 6 | sets | threshold and enable/disable probes |
If you receive the following message, the SNMP query is not being received from the RPC units.
None of the installed devices support this option.
Strike ENTER to continue
Temperature Alarm Threshold
Select 1), Temperature Alarm Threshold and the Host Module responds:
Sel M/P | Identifier | Tmp Lvl | Sel M/P Identifier Tmp Lvl | |
1 2/1 | rpc14 | 500 2 | 5/1 | 500 |
Enter Request :1 |
|
|
|
NOTE: M/P = Module number and Port number; Identifier should be this unit model number; Tmp Lvl = temperature level. The unit’s firmware determines whether the degrees are Celsius or Fahrenheit. Currently there is no option to change the degrees.
Type #1 for the selection, press <cr> and the Host Module responds:
Enter threshold value in tenths of unit measurement (degrees,%,etc.):
Multiple Strip Current Monitor
Sets Current Levels
Under Voltage Alarm Threshold
Select 3), Under Voltage Alarm Threshold and the Host Module responds:
27