4
Configuring Field Control Station
1.From the HHM Main Menu, display the special set of menus for Field Control.
A.If the Bus Interface Unit or Field Processor is the
B.If it is NOT the
H Select F2 (analyze) then F3 (Block/Bus Status).
H Press the F1 (nxt) or F2 (prev) key repeat- edly to reach the serial bus address of the
BIU or Field Processor. Press F3 to make it the active device. Then, press ΔMenu, fol- lowed by F2 (Monitor/Control Ref).
F 1 : M o n i t o r
F 2 : C o n f i g u r a t i o n
From this menu, press F2 (Configuration). This menu appears:
F 1 : G E N I U S | C O N F I G |
F 2 : M o d u l e | C o n f i g |
F 3 : P r e v i o u s M e n u
HPress F1 to configure the BIU/Field Processor.
HPress F2 to configure individual modules.
Change the Bus Address
When you press F1 (Genius Configuration) from the Configuration menu, the HHM shows the serial bus address previously configured for the BIU or Field Processor:
D e v i c e | S B A |
1 4 |
|
P r v > | e n t r |
|
|
If the bus address is correct, press F2 to go on.
Note: If a BIU or Field Processor has a Serial Bus Address conflict on an operating bus, it will not scan the modules in the station until the fault is cleared.
1.If you want to change the address, enter the new address using the keypad.
2.Press F4 (entr). An error message appears if the number has been used for another device.
Select a PLC Reference Address
If the host is not a Series Six PLC or Series Five PLC, no entry is necessary here.
If the host is a Series Six PLC or Series Five PLC, assign an I/O or register reference address.
S t a t T b l A d d r | ||
O O O O O |
| |
< | > | I O 6 e n t r |
shows reference type
1.Use the F3 key to toggle the selection of Series SixI/Omemory, Series Five I/O memory, or register memory. (See the BIU/Field Processor User's Manual for information about memory usage in the Series Five and Series Six PLC).
If I/O memory is used, the amount required is equal to the number of bits of discrete data PLUS analog data. Each analog reference used consumes 16 points.
If register memory is used, an amount is re- quired that is equal to the total number of bytes of input data PLUS all of the output data
2.Key in the number of the block's beginning I/O or register reference. This may be:
SeriesSixI/O | 1 to 993 |
Series FiveI/O | 1 to 2041 |
Registers | 1 to 16383 |
3. Press the F4 (Entr) key.
Configure Additional Features
On the screens that follow, select these features:
HFault Reporting
HGenius bus redundancy
HBSM Controller
HOutput default time (for redundancy)
HCPU redundancy
HDuplex redundancy: default mode for outputs
HConfiguration protection
Chapter 4 Device Configuration: Overview |