Displaying Field Control Faults

A Hand-held Monitor can display faults from a Bus Interface Unit or Field Processor while attached anywhere on the Genius bus.

1.From the HHM Main Menu, display the Field Control main menu (instructions are on the previous page).

F 1 : M o n i t o r

F 2 : C o n f i g u r a t i o n

2.From this menu, select F1 (Monitor). The fol- lowing menu appears:

F 1 : M o n i t o r I / O

F 2 : F a u l t s

F 3 : P r e v i o u s M e n u

3.Select F2 (faults) to display fault information for the Field Processor and its modules.

The Faults menu appears:

F 1

F i r s t 1 6 F l t s

F 2

L a s t 1 6 F l t s

F 3

P r e v i o u s M e n u

 

 

4.Press F1 to display the first set of 16 faults (one fault at a time). For example:

S l o t

# 1

F a u l t # 1

E X T R A I / O M O D U L E

<

>

e x i t

 

 

 

A.Use F1 and F2 to display another fault

B.If there are no faults, the HHM displays the message: NoFaults on the top line.

5.To display the last 16 faults (if any):

A.Press F4 (exit) to return to the screen shown at the top if this page.

B.Press F2 (last 16 faults).

Clearing Field Control Faults

If faults are present, pressing the HHM Clear key here has no effect. To clear faults from the Hand-held Monitor you need to do the following:

1.Return to the HHM Main Menu.

2.Press F2 (Analyze).

3.Press F3 (Block./Bus Status).

4.Make the BIU or Field Processor the active de- vice if it is not.

5.Press the Clear key.

Clearing faults from the Hand-held Monitor does not clear faults at the host PLC. To keep the entire system in step and up-to-date, fault clearing should be performed from the host PLC.

5-16

Hand-held Monitor User's Guide ± June 1994

GFK-0121E

Image 52
Contents GE Fanuc Automation GFL±002 Content of this Manual Related PublicationsPreface Contents Chapter Introduction Hand-held Monitor Description HHM KeypadAccessories KeyswitchHHM Display HHM Compatibility HHM Specifications Optional AccessoriesCharging the Battery Pack for AC Operation Selecting 120 VAC or 230 VACUsing the 230VAC Power Adapter InstructionsBattery Operation Low Battery PowerCharging the Battery Pack Replacing the Battery PackChanging the Prom Conductive mat Permanent Installation Configuring a Permanently-installed HHMHHM Installation Instructions CutoutInstalling the D-Shell HHM Connector SERInstalling a Separate Hand-held Monitor Connector Mounting the HHM ConnectorMaking the Bus Connections Chapter Getting Started Setting the HHM Baud Rate Powerup Error MessagesDisplaying the Home Menu Main HHM ScreensConfiguring the Hand-held Monitor Changing the HHM Device NumberSelecting the Host CPU Changing the HHM Display LanguageEnabling/Disabling Automatic Shutoff Enabling/Disabling the Ability to Clear Faults Enabling/Disabling the Ability to Force I/O CircuitsTesting Operation of the Hand-held Monitor Testing the Internal ElectronicsTesting the Keypad Testing the Display ScreenChapter Device Configuration Overview Online or Offline Configuration Starting ConfigurationOnline Configuration Offline ConfigurationDisplaying the Configuration Menus Completing the Program Block ID Screens To Set the I/O Map for a Remote I/O ScannerConfiguration Notes Configuring the Remote DropConfiguringGenius Blocks Copying a ConfigurationConfiguring Block Features Configuration InstructionsChange the Bus Address Configure Additional FeaturesSelect a PLC Reference Address Disable the I/O Scan Configuring Individual Field Control ModulesConfigure Data Addresses and Lengths Add Modules and Assign References Configuring Module FeaturesAssign I/O References for the Module Chapter Monitoring the Bus and its Devices Displaying Information About Bus Devices Selecting Another DeviceSwitching a Dual Bus Monitoring the Bus StatusMonitoring a Genius Block Monitor Block Display for Discrete I/O and Input BlocksMaking the Block Active Block ReferencesMonitor Block Display for Discrete Relay OutputBlocks Monitor Block Display for Analog BlocksPreset Outputs Monitor Block Display for a High-speed Counter BlockMonitor Block Display for a PowerTRACBlock Calculated DataBasic Monitor/Control Display Format Clearing Circuit Faults DiagnosticsForcing an Input or Output Forcing an Analog, RTD, or Thermocouple Value PowerTRAC Data Sequence Monitor/Control Reference Displays for a PowerTRAC BlockSelecting a Memory Type or Address PowerTRAC Status Inputs Screens PowerTRAC Calculated Data ScreensPowerTRAC Extra Calculated Data Lpio Screens PowerTRAC Control Outputs ScreensMonitoring/Controlling Remote Drop Data Displaying Other CircuitsClearing Faults Displaying and Clearing Remote Drop FaultsForcing a Circuit Changing the Display Mode Monitoring/Controlling Field Control DataDisplaying Another Reference Returning to the Previous MenuDisplaying Field Control Faults Clearing Field Control FaultsPulse Testing Outputs on Discrete Genius Blocks Clearing Pulse Test FaultsPulse Test Error Messages Executing a Pulse TestChapter Reading CPU Memory General InstructionsSeries 90 PLC Enter or Change the PLC Type Series Six PLCEnter or Change the Memory Location Series Five PLC DataChanging the Data Format Changing the Selected AddressChapter Error Messages Powerup Error MessagesOperating Error Messages Configuration Error MessagesIndex Index-2 Index-3 Index-4