Socket Mobile GFK0121E manual Monitor Block Display for a PowerTRACBlock, Calculated Data

Page 43

5

Monitor Block Display for a PowerTRACBlock

If the active device is a PowerTRAC block, the HHM's Monitor Block function displays the following screens:

HOne screen showing the states of all of the block's Status Inputs.

HIndividual screens showing the block's current calculated data values. In the Monitor Block function, these values are NOT labelled. It is easier to display this information using the Monitor/Control Reference function (F2), be- cause those displays are labelled.

HOne screen showing the states of all of the block's Control Outputs.

On each of these screens, you can press F1 ( > ) to display next screen, or press F2 (ref) and enter a reference location to display a specific screen. For a sequential list of the PowerTRAC block data, see page 5-11.

Bit 15 = 1 means the overcurrent event indicated by bit 4 occurred on the auxiliary current line.

Bit 16 = 1 indicates an internal calculation has re- sulted in an out-of-range value. The block should be reconfigured to prevent this.

Calculated Data

After the Status Inputs, the HHM displays the block's calculated data. If the PowerTRAC Block is version 2.3 or later, this includes the additional ªlow-priorityI/Oº data listed on page 5-11.

R E F (input reference) I

1 1 7

>r e f

Status Inputs

The Monitor Block function first displays the PowerTRAC block's Status Inputs:

R E F (inputreferences) I

1 2 3 4 5 6 7 8 9 O 1 2 3 4 5 6

O O O 1 1 O O O O O O 1 O O O O

>r e f

Line 2 indicates each of the 16 possible bit locations for status data. Lin e3 shows the current states of all inputs.

Bits 1 ± 3 indicate the status of table data transfer, for datagram communications.

Bit 4 = 1 indicates the block has captured an over- current event.

Bit 5 should always be 1, indicating that the block's phase-lock loop is synchronized with the incoming AC voltage.

Bit 12 = 1 means the overcurrent event indicated by bit 4 occurred on phase A.

Bit 13 = 1 means the overcurrent event indicated by bit 4 occurred on phase B.

Bit 14 = 1 means the overcurrent event indicated by bit 4 occurred on phase C.

Control Outputs

After the calculated data screens, the HHM's Monitor Block function displays the PowerTRAC block's Control Outputs. You can also display this data by using the F2 (ref) key to select output 1. You may need to toggle (F2) the memory type.

R E F (outputreferences) O

1 2 3 4 5 6 7 8 9 O 1 2 3 4 5 6

O O O O O O O O O O O O O O O O

>r e f

Line 2 indicates each of the 16 possible bit locations for Control Outputs. Line 3 shows the current state of each Control Outputs. These outputs are communications handshaking bits, sent from the CPU to the block for certain datagram communications. Information about these outputs is in the PowerTRAC Block User's Manual.

GFK-0121E

Chapter 5 Monitoring the Bus and its Devices

5-7

Image 43
Contents GE Fanuc Automation GFL±002 Related Publications Content of this ManualPreface Contents Chapter Introduction HHM Keypad Hand-held Monitor DescriptionAccessories KeyswitchHHM Display HHM Compatibility Optional Accessories HHM SpecificationsSelecting 120 VAC or 230 VAC Charging the Battery Pack for AC OperationInstructions Using the 230VAC Power AdapterReplacing the Battery Pack Battery OperationLow Battery Power Charging the Battery PackChanging the Prom Conductive mat Configuring a Permanently-installed HHM Permanent InstallationCutout HHM Installation InstructionsSER Installing the D-Shell HHM ConnectorMounting the HHM Connector Installing a Separate Hand-held Monitor ConnectorMaking the Bus Connections Chapter Getting Started Powerup Error Messages Setting the HHM Baud RateMain HHM Screens Displaying the Home MenuChanging the HHM Device Number Configuring the Hand-held MonitorSelecting the Host CPU Changing the HHM Display LanguageEnabling/Disabling Automatic Shutoff Enabling/Disabling the Ability to Force I/O Circuits Enabling/Disabling the Ability to Clear FaultsTesting the Display Screen Testing Operation of the Hand-held MonitorTesting the Internal Electronics Testing the KeypadChapter Device Configuration Overview Offline Configuration Online or Offline ConfigurationStarting Configuration Online ConfigurationDisplaying the Configuration Menus To Set the I/O Map for a Remote I/O Scanner Completing the Program Block ID ScreensConfiguring the Remote Drop Configuration NotesConfiguration Instructions ConfiguringGenius BlocksCopying a Configuration Configuring Block FeaturesChange the Bus Address Configure Additional FeaturesSelect a PLC Reference Address Disable the I/O Scan Configuring Individual Field Control ModulesConfigure Data Addresses and Lengths Add Modules and Assign References Configuring Module FeaturesAssign I/O References for the Module Chapter Monitoring the Bus and its Devices Selecting Another Device Displaying Information About Bus DevicesMonitoring the Bus Status Switching a Dual BusBlock References Monitoring a Genius BlockMonitor Block Display for Discrete I/O and Input Blocks Making the Block ActiveMonitor Block Display for Analog Blocks Monitor Block Display for Discrete Relay OutputBlocksMonitor Block Display for a High-speed Counter Block Preset OutputsCalculated Data Monitor Block Display for a PowerTRACBlockBasic Monitor/Control Display Format Clearing Circuit Faults DiagnosticsForcing an Input or Output Forcing an Analog, RTD, or Thermocouple Value PowerTRAC Data Sequence Monitor/Control Reference Displays for a PowerTRAC BlockSelecting a Memory Type or Address PowerTRAC Control Outputs Screens PowerTRAC Status Inputs ScreensPowerTRAC Calculated Data Screens PowerTRAC Extra Calculated Data Lpio ScreensDisplaying Other Circuits Monitoring/Controlling Remote Drop DataClearing Faults Displaying and Clearing Remote Drop FaultsForcing a Circuit Returning to the Previous Menu Changing the Display ModeMonitoring/Controlling Field Control Data Displaying Another ReferenceClearing Field Control Faults Displaying Field Control FaultsExecuting a Pulse Test Pulse Testing Outputs on Discrete Genius BlocksClearing Pulse Test Faults Pulse Test Error MessagesGeneral Instructions Chapter Reading CPU MemorySeries 90 PLC Enter or Change the PLC Type Series Six PLCEnter or Change the Memory Location Data Series Five PLCChanging the Selected Address Changing the Data FormatPowerup Error Messages Chapter Error MessagesConfiguration Error Messages Operating Error MessagesIndex Index-2 Index-3 Index-4