Socket Mobile GFK0121E manual Forcing an Analog, RTD, or Thermocouple Value

Page 46

5

Monitor/Control Reference Display for an Analog, RTD, or Thermocouple Block

For an analog, RTD, or Thermocouple block, the Monitor/Control Reference screen shows the current value for each circuit. For example:

M N T R (ckt. reference)

A

I 2 :

± 1 9 3 7 O

 

 

N O F A U L T S

 

 

> f o r c e r e l e s

 

 

 

 

 

 

For an analog block, the values may represent either engineering units or unscaled analog data.

For an RTD or Thermocouple block, the values represent tenths of degrees (Celsius or Fahrenheit), tenths of ohms, or unconverted counts.

Press F1 ( > ) to display other circuits.

Forcing an Analog, RTD, or Thermocouple Value

The HHM's circuit forcing capability must be enabled to perform this function.

1.Press F2 (Force) to force the displayed circuit.

2.If you make a mistake entering a value, use the Clear key to delete one digit at a time, starting with the last. To exit without forcing a circuit, press F2 (Change).

3.Press F3 (Enter) to save this value as the value for the circuit. The forced value will remain until you press F4 (reles), or enter a new value.

Diagnostics

Line 3 shows whether the circuit has any faults. If it does, one of these messages appears on line 3:

Feedback error: There is a wiring error or other hardware fault on a Current-source Ana- log block. The output's actual current dif- fers from the commanded current by more than 250mA.

High alarm/low alarm: An analog input value ex- ceeds its high or low alarm limit.

Input shorted: An RTD input circuit measurement is less than expected for the RTD type.

Internal fault: Internal calibration readings for a pair of RTD circuits are out of tolerance.

Open wire: On an RTD block, the RTD is missing or faulty, or there is an open wire. On an analog block, an input configured for 4 to 20mA has less than 2mA present.

Overrange/underrange: An analog or RTD circuit exceeds its maximum value.

Overtemperature: The block's internal tempera- ture exceeds 100_C.

Wiring error: There is a faulty connection be- tween an RTD and the block.

Clearing Circuit Faults

After correcting a fault condition, press the CLEAR key to remove the message and restore the reference to normal operation (the Clear Block Faults function must be enabled to use this feature). If the fault condition still exists, the fault message will reappear.

5-10

Hand-held Monitor User's Guide ± June 1994

GFK-0121E

Image 46
Contents GE Fanuc Automation GFL±002 Content of this Manual Related PublicationsPreface Contents Chapter Introduction Hand-held Monitor Description HHM KeypadAccessories KeyswitchHHM Display HHM Compatibility HHM Specifications Optional AccessoriesCharging the Battery Pack for AC Operation Selecting 120 VAC or 230 VACUsing the 230VAC Power Adapter InstructionsCharging the Battery Pack Battery OperationLow Battery Power Replacing the Battery PackChanging the Prom Conductive mat Permanent Installation Configuring a Permanently-installed HHMHHM Installation Instructions CutoutInstalling the D-Shell HHM Connector SERInstalling a Separate Hand-held Monitor Connector Mounting the HHM ConnectorMaking the Bus Connections Chapter Getting Started Setting the HHM Baud Rate Powerup Error MessagesDisplaying the Home Menu Main HHM ScreensConfiguring the Hand-held Monitor Changing the HHM Device NumberSelecting the Host CPU Changing the HHM Display LanguageEnabling/Disabling Automatic Shutoff Enabling/Disabling the Ability to Clear Faults Enabling/Disabling the Ability to Force I/O CircuitsTesting the Keypad Testing Operation of the Hand-held MonitorTesting the Internal Electronics Testing the Display ScreenChapter Device Configuration Overview Online Configuration Online or Offline ConfigurationStarting Configuration Offline ConfigurationDisplaying the Configuration Menus Completing the Program Block ID Screens To Set the I/O Map for a Remote I/O ScannerConfiguration Notes Configuring the Remote DropConfiguring Block Features ConfiguringGenius BlocksCopying a Configuration Configuration InstructionsChange the Bus Address Configure Additional FeaturesSelect a PLC Reference Address Disable the I/O Scan Configuring Individual Field Control ModulesConfigure Data Addresses and Lengths Add Modules and Assign References Configuring Module FeaturesAssign I/O References for the Module Chapter Monitoring the Bus and its Devices Displaying Information About Bus Devices Selecting Another DeviceSwitching a Dual Bus Monitoring the Bus StatusMaking the Block Active Monitoring a Genius BlockMonitor Block Display for Discrete I/O and Input Blocks Block ReferencesMonitor Block Display for Discrete Relay OutputBlocks Monitor Block Display for Analog BlocksPreset Outputs Monitor Block Display for a High-speed Counter BlockMonitor Block Display for a PowerTRACBlock Calculated DataBasic Monitor/Control Display Format Clearing Circuit Faults DiagnosticsForcing an Input or Output Forcing an Analog, RTD, or Thermocouple Value PowerTRAC Data Sequence Monitor/Control Reference Displays for a PowerTRAC BlockSelecting a Memory Type or Address PowerTRAC Extra Calculated Data Lpio Screens PowerTRAC Status Inputs ScreensPowerTRAC Calculated Data Screens PowerTRAC Control Outputs ScreensMonitoring/Controlling Remote Drop Data Displaying Other CircuitsClearing Faults Displaying and Clearing Remote Drop FaultsForcing a Circuit Displaying Another Reference Changing the Display ModeMonitoring/Controlling Field Control Data Returning to the Previous MenuDisplaying Field Control Faults Clearing Field Control FaultsPulse Test Error Messages Pulse Testing Outputs on Discrete Genius BlocksClearing Pulse Test Faults Executing a Pulse TestChapter Reading CPU Memory General InstructionsSeries 90 PLC Enter or Change the PLC Type Series Six PLCEnter or Change the Memory Location Series Five PLC DataChanging the Data Format Changing the Selected AddressChapter Error Messages Powerup Error MessagesOperating Error Messages Configuration Error MessagesIndex Index-2 Index-3 Index-4