Socket Mobile GFK0121E manual Series Six PLC, Enter or Change the PLC Type

Page 56

6

Series Six PLC

For a Series Six PLC, the Hand-held Monitor can read data from register memory. That includes I/O data mapped into register memory, (it is easier to display I/O data with the HHM's Monitor Block or Monitor Control Reference function).

For a Series Six PLC, the Device Memory screen looks like this example:

Enter or Change the PLC Type

To enter or change the PLC type:

1.Press F3 (chng). A cursor appears at the left of the colon. For a Series Six PLC, enter the num- ber 32768.

2.Press the F3 (entr) key.

D E V I C E M E M O R Y 7

M E M : (location)

t g l c h n g e n t r S B A

The top line shows the currently-selected Device Number (7 in the example above). If there is a currently-selected memory location, it appears on the second line of the display as two numbers separated by a colon.

The number on the left will be:

32768 for a Series Six PLC

The number on the right is the actual memory location that will be read.

From this screen, use the Hand-held Monitor function keys to:

A.Select a different device on the bus (press F4 (SBA)).

B.Select another memory type (press F2 (chng)). See right for instructions.

C.Select another reference location in the dis- played memory type (press F2(chng)). See right for instructions.

D.Display the current memory contents of the specified location (press F3 (entr)).

Enter or Change the Memory Location

To enter or change the memory location:

1.On the same screen, press F1 ( > ) to move the cursor to the right of the colon.

2.Press F2 (chng).

3.Enter a number equal to the actual register number plus 16383. For example, for regis- ter#100, you would enter (16383 + 100), which is 16483:

M E M : 3 2 7 6 8 : 1 6 4 8 3

Expanded I/O Data

Expanded I/O data is mapped into registers and can be accessed as described above. I/O data from channel 0, or the main I/O chain in an expanded I/O system can be displayed using the integer result of the following formula:

((point number ± 1) / 8) + table offset

The table offset is either 8192 for the output table or 8320 for the input table. Example: to display input 672, you would enter: ((672 ± 1) / 8) +8320, which is 8403.

GFK-0121E

Chapter 6 Reading CPU Memory

6-3

Image 56
Contents GE Fanuc Automation GFL±002 Content of this Manual Related PublicationsPreface Contents Chapter Introduction Hand-held Monitor Description HHM KeypadHHM Display KeyswitchAccessories HHM Compatibility HHM Specifications Optional AccessoriesCharging the Battery Pack for AC Operation Selecting 120 VAC or 230 VACUsing the 230VAC Power Adapter InstructionsBattery Operation Low Battery PowerCharging the Battery Pack Replacing the Battery PackChanging the Prom Conductive mat Permanent Installation Configuring a Permanently-installed HHMHHM Installation Instructions CutoutInstalling the D-Shell HHM Connector SERInstalling a Separate Hand-held Monitor Connector Mounting the HHM ConnectorMaking the Bus Connections Chapter Getting Started Setting the HHM Baud Rate Powerup Error MessagesDisplaying the Home Menu Main HHM ScreensConfiguring the Hand-held Monitor Changing the HHM Device NumberEnabling/Disabling Automatic Shutoff Changing the HHM Display LanguageSelecting the Host CPU Enabling/Disabling the Ability to Clear Faults Enabling/Disabling the Ability to Force I/O CircuitsTesting Operation of the Hand-held Monitor Testing the Internal ElectronicsTesting the Keypad Testing the Display ScreenChapter Device Configuration Overview Online or Offline Configuration Starting ConfigurationOnline Configuration Offline ConfigurationDisplaying the Configuration Menus Completing the Program Block ID Screens To Set the I/O Map for a Remote I/O ScannerConfiguration Notes Configuring the Remote DropConfiguringGenius Blocks Copying a ConfigurationConfiguring Block Features Configuration InstructionsSelect a PLC Reference Address Configure Additional FeaturesChange the Bus Address Configure Data Addresses and Lengths Configuring Individual Field Control ModulesDisable the I/O Scan Assign I/O References for the Module Configuring Module FeaturesAdd Modules and Assign References Chapter Monitoring the Bus and its Devices Displaying Information About Bus Devices Selecting Another DeviceSwitching a Dual Bus Monitoring the Bus StatusMonitoring a Genius Block Monitor Block Display for Discrete I/O and Input BlocksMaking the Block Active Block ReferencesMonitor Block Display for Discrete Relay OutputBlocks Monitor Block Display for Analog BlocksPreset Outputs Monitor Block Display for a High-speed Counter BlockMonitor Block Display for a PowerTRACBlock Calculated DataBasic Monitor/Control Display Format Forcing an Input or Output DiagnosticsClearing Circuit Faults Forcing an Analog, RTD, or Thermocouple Value Selecting a Memory Type or Address Monitor/Control Reference Displays for a PowerTRAC BlockPowerTRAC Data Sequence PowerTRAC Status Inputs Screens PowerTRAC Calculated Data ScreensPowerTRAC Extra Calculated Data Lpio Screens PowerTRAC Control Outputs ScreensMonitoring/Controlling Remote Drop Data Displaying Other CircuitsForcing a Circuit Displaying and Clearing Remote Drop FaultsClearing Faults Changing the Display Mode Monitoring/Controlling Field Control DataDisplaying Another Reference Returning to the Previous MenuDisplaying Field Control Faults Clearing Field Control FaultsPulse Testing Outputs on Discrete Genius Blocks Clearing Pulse Test FaultsPulse Test Error Messages Executing a Pulse TestChapter Reading CPU Memory General InstructionsSeries 90 PLC Enter or Change the Memory Location Series Six PLCEnter or Change the PLC Type Series Five PLC DataChanging the Data Format Changing the Selected AddressChapter Error Messages Powerup Error MessagesOperating Error Messages Configuration Error MessagesIndex Index-2 Index-3 Index-4