- INSTALLATION MANUAL -

 

Parameter

Description

 

Default

Default

min

MAX

 

 

(BCF...)

(BC...)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURATION

 

 

 

 

 

 

 

C01

Door input (0 de-activated; 1 activated)

 

1

1

0

1

 

 

C02

Door open polarity

 

0

0

0

1

 

 

C03

Door open alarm delay

 

2 min

2 min

0 min

60 min

 

C04

Activates buzzer (0 de-activated; 1 activated)

 

1

1

0

1

 

 

C05

Buzzer duration at the end of quick cooling cycle

 

10 sec

10 sec

0

600 sec

 

C06

Temperature difference in the first phase of needle insertion

 

13°F

45°F

0

140°F

 

test (0 = test excluded)

 

 

 

 

 

 

 

 

 

 

C07

Duration of the second phase of needle insertion test (0=test

 

56 sec

56 sec

0

600 sec

 

excluded)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activates condenser probe

 

 

 

 

 

 

 

C08

0 = no probe

 

1

1

0

1

 

 

 

1 = probe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C09

Compressor stop delay due to door opening

 

30 sec

30 sec

0 sec

60 sec

 

C10

Control pressure alarm detection time

 

5 sec

5 sec

0 sec

60 sec

 

C11

High pressare digital input polarity

 

0

0

0

1

 

 

C12

Resistances starting SetPoint

 

23°F

23°F

14°F

68°F

 

 

ADJUSTMENT

 

 

 

 

 

 

 

R01

Compressor start/stop hysteresis

 

5°F

38°F

0°F

36°F

 

R02

Min. interval between 2 compressor starting

 

2 min

2 min

0 min

30 min

 

R03

Compressor start delay from card activation

 

0 sec

0 sec

0 sec

300 sec

 

R04

Compressor Duty-Cycle time with faulty room probe in storing

 

10 min

10 min

0 min

90 min

 

R05

Compressor ON time faulty room in pos. storing

 

3 min

3 min

0 min

90 min

 

R06

Compressor ON time with faulty room in neg. storing

 

8 min

8 min

0 min

90 min

 

R07

Needle min. temperature for starting quick cooling

 

158°F

158°F

32°F

194°F

 

R08

Compressor block temperature

 

194°F

194°F

32°F

212°F

 

R09

Compressor Protection function activation time

 

24 hour

24 hour

0 hour

240 hour

 

R10

Pulse duration

 

2 sec

2 sec

1 sec

10 sec

 

R11

Pause between pulses

 

8 sec

4 sec

1 sec

10 sec

 

R12

Number of pulses

 

3

3

1

20

 

 

R13

Temperature at the end of the Cooling cycle

 

-13°F

-13°F

-58°F

50°F

 

 

FANS

 

 

 

 

 

 

 

F01

Evaporator fans activation hysteresis

 

4°F

36°F

0°F

36°F

 

F02

Condenser fans activation hysteresis

 

4°F

36°F

0°F

36°F

 

F03

Evaporator fans activation SetPoint

 

41°F

41°F

-58°F

122°F

 

F04

Condenser fans activation SetPoint

 

59°F

59°F

-58°F

122°F

 

F05

Evaporator fans during defrost

 

0

0

0

1

 

 

0 = fans OFF; 1 = fans ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F06

Condenser fans during defrost

 

0

0

0

1

 

 

0 = fans OFF; 1 = fans ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F07

Fans stop time after defrost

 

1 min

1 min

0 min

30 min

 

F08

Condenser fans stop delay

 

30 sec

30 sec

0 sec

300 sec

 

 

Evaporator fans control during quick cooling:

 

 

 

 

 

 

 

F09

0 = fans always ON

 

0

0

0

1

 

 

 

1 = fans thermostated by evaporator temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator fans control during storing:

 

 

 

 

 

 

 

F10

0 = fans in parallel with the compressor

 

0

0

0

1

 

 

 

1 = fans thermostated by evaporator temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F11

Evaporator fans block temperature

 

158°F

158°F

32°F

194°F

 

 

PRINT

 

 

 

 

 

 

 

PR1

Sampling time

 

10 min

10 min

1 min

60 min

 

 

VENTILATION SPEED (P.W.M.)

 

 

 

 

 

 

 

CF1

Evaporator fan min. speed

 

30

20

0

100

 

 

CF2

Evaporator fan min. speed selectable in a quick cooling cycle

 

50

50

0

100

 

 

 

 

 

 

 

 

33

 

Image 35
Contents 3185550/146127 Page Manual Cycles .…………….………………………………………………………………15 Maintenance and Cleaning ……………………………………………………………23Description of Controls ………………………………………………………………7 Programs .…………………….………………………………………………………………10Dimensions …………………………………………………………………………………42 Installation …………………………………………………………………………………26Refrigerant Material Safety Data SHEET………………………………………40 General Instructions Technical DataInformation for the Reader Chapter General Instructions on Delivery ChapterTab.2 Model Max. output/cycle Capacity Setting UPPosition of Trays Storage Temperatures and TimesMachine Loading Core Probe Tab.3Description of Controls Control Panel Chapter… Core … Time Manual settingPrograms Manual Store Ok or No IFR Chilling Cycle Operation ChapterPrograms USER’S Programs Recommended Working CyclesDisplay shows the program number and name USER’S CycleStoring USER’S Programs Rename a USER’S Program Delete a USER’S ProgramKeep menu/esc pressed for 5 seconds. The display ShowsPRE-COOLING Cycle ƒ Hard Positive Chilling Cycle Manual Cyclesƒ Negative Freezing Cycle ƒ Soft Positive Chilling CyclePress enter to confirm your choice. The display shows Negative Freezing Cycle with TimerNegative Freezing Cycle with Core Probe Soft Positive Chilling Cycle with Core Probe Hard Positive Chilling Cycle with Core Probe Soft Positive Chilling Cycle with TimerHard Positive Chilling Cycle with Timer Negative Store Storing CyclesPositive Store Printing DefrostingPress enter to start printing the saved cycles Pict.12 Maintenance ChapterMaintenance and Cleaning Cleaning the CabinetSTAINLESS-STEEL Maintenance Cleaning the AIR CondenserDIS USE OFFDetail of above data plate InstallationMAX Room Temperature TAB.4 IntroductionPict.27 WiringConnection to Condensate Drain TestingLanguage Clock SettingProgressive number ranging from A01 to A30 Alarms and Fault Analysis TAB.5TAB.5 Fault Cause RemedyDescription of Parameters ServiceParameters Print Display shows Changing ParametersUse the keys up and down to display Reset MemoryThis function restores the original parameters Restoring Default ParametersINPUTS/OUTPUTS Printer InstallationMod. BCF44244 / BCB44244 / BC40-4 Electrical Compartment AccessDisposal Wiring Diagram PlateControl and Safety Systems Procedure for Rough Dismantling the ApplianceMount the upper bracket Refrigerant Material Safety Data SheetDoor Reversal Installation Manual BCF11514 BC113-14 DimensionsBCF22020 TAB.1a Model AppendixTAB.4 Description Pict.47Comment SE Préparer AU Démarrage ……………………………………………4 Liste DES Références Normatives …………………………………………………3Entretien DU Tableau Électrique …………………………………………………37 Données Techniques Informations Pour LE Lecteur ChapitreDonnees Generales a LA Remise Chapitre Données GénéralesTab.2 Modéle Rendu max/cycle Capacité Comment SE Préparer AU DémarrageDurée DE Conservation Placement DES RécipientsChargement DE LA Cellule Sonde a Coeur Description DES Commandes Panneau DE Commande ChapitreRéglages manuels Programmes Manuel Conservation… Coeur … Temps Ok ou No Imprimer Regler Horlose Langue Alarme ServiceDegivrage Cycle DE Refroidissement Rapide IFR Fonctionnement ChapitreProgrammes Utilisation DE Programmes Utilisateur Cycles ConseillésCycle Utilisateur Programme Le premier emplacement libre s’afficheEnregistrement Programmes Utilisateur Renommer UN Programme Utilisateur Effacer UN Programme UtilisateurOn affiche Cycle DE PRÉ-REFROIDISSEMENT Temps de refroidissement rapide Cycles ManuelsCycle DE Refroidissement Rapide Negatif À Temps Cycle DE Refroidissement Rapide Negatif Avec Sonde À CoeurNeg Temps Ok Esc Cycle DE Refroidissement Rapide Positif Soft À Temps Cycle DE Refroidissement Rapide Positif Hard À Temps Conservation Negative Cycle DE ConservationConservation Positive Appuyer sur la touche Up pour afficherImpression DégivrageManuel D’INSTRUCTION Nettoyage Enceinte Entretien ChapitreNettoyage ET Entretien Entretien Acier Inox Nettoyage DU Condenseur a AIRInterruption D’UTILISATION Mise EN Place Temperature MAX DU Local D’UTILISATIN TAB.4Branchement Electrique Essais Regler HorloseEvacuation DES Eaux DE Condensation Langue Alarmes ET Analyse EN Panne TAB.5Advenue avec le numéro progressif d’alarme de A01 à A30 Panne Cause Solution Description DES Parametres ParametresRegulation Impression Modification DES Parametres Enregistrées en mémoire. On affiche Restore Default ParametresEntrees ET DES Sorties Installation DE L’IMPRIMANTEEntretien DU Tableau Électrique Stockage DES Déchets Plaquette Schéma ÉlectriqueSystémes DE Contrôle ET Témoins EcoulementFiche Technique DU Refrigerant Inversion PorteManuel D’INSTALLATION Dimensions D’ENCOMBREMENT BCF22020 TAB.1a AnnexesCirculation air min Modèle Quantité air Cfm 79A