- INSTALLATION MANUAL -
SERVICE
PARAMETERS
DESCRIPTION OF PARAMETERS
| Parameter | Description | Default | Default | min | MAX | |
| (BCF...) | (BC...) | |||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| POSITIVE QUICK COOLING |
|
|
|
|
|
| P01 | Room SetPoint in pos. quick cooling, Soft phase | 23°F | 23°F | 86°F | ||
| P02 | SetPoint in pos. quick cooling, Hard | 86°F | ||||
| P03 | Needle SetPoint in pos. quick cooling , Soft phase | 37°F | 37°F | 86°F | ||
| P04 | Needle SetPoint in Hard quick cooling | 68°F | 68°F | 86°F | ||
| P05 | Positive quick cooling duration | 90min | 90min | 0min | 900min | |
| P06 | Hard phase duration expressed as % in relation to P05 | 60% | 60% | 0% | 100% |
|
| P07 | Room SetPoint in pos. storing | 36°F | 36°F | 86°F | ||
|
| NEGATIVE QUICK COOLING |
|
|
|
|
|
| N01 | Room SetPoint in neg, quick cooling | 86°F | ||||
| N02 | Needle SetPoint in neg. quick cooling | 0°F | 86°F | |||
| N03 | Negative quick cooling duration | 240min | 240min | 0min | 900min | |
| N04 | Room SetPoint in neg. storing | 86°F | ||||
|
| ALARMS |
|
|
|
|
|
| A01 | Temperature alarm hysteresis | 4°F | 4°F | 0°F | 18°F | |
| A02 | High temperature limit alarm in pos. storing in relation to P07 | 18°F | 18°F | 0°F | 90°F | |
| A03 | Low temperature limit alarm in pos. storing in relation to P07 | 0°F | ||||
| A04 | High temperature limit alarm in neg. storing in relation to N04 | 18°F | 18°F | 0°F | 90°F | |
| A05 | Low temperature limit alarm in neg. storing in relation to N04 | 0°F | ||||
| A06 | Temperature alarm delay fron storing or defrost start | 60min | 60min | 0min | 300min | |
| A07 | Temperature alarm delay | 30min | 30min | 0min | 300min | |
| A08 | Duration of the buzzer in the alarm mode | 1min | 1min | 0min | 240min | |
|
| DISPLAY |
|
|
|
|
|
| D01 | Temperature unit of measurement (0 Celsius; 1 Fahrenheit) | 1 | 1 | 0 | 1 |
|
| D02 | Room probe Offset | 0°F | 0°F | 18°F | ||
| D03 | BackLight (0 on when pressing a key; 1 always on) | 0 | 0 | 0 | 1 |
|
| D04 | Core probe offset | 0°F | 0°F | 18°F | ||
| D05 | Under surface probe offset | 0°F | 0°F | 18°F | ||
| D06 | Over surface probe offset | 0°F | 0°F | 18°F | ||
|
| DEFROST |
|
|
|
|
|
| S01 | Performs defrost on quick cooling start | 0 | 0 | 0 | 1 |
|
| 0 = No; 1 = Yes |
| |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
| S02 | 46°F | 46°F | 14°F | 86°F | ||
| S03 | Defrost max. duration | 15 min | 15 min | 1 min | 90 min | |
| S04 | Interval between defrosts in storing (0=excluded) | 0 hour | 0 hour | 0 | 18 hour | |
|
| Type of defrost: |
|
|
|
|
|
| S05 | 0= electrical or due to compressor stop | 2 | 2 | 0 | 2 |
|
| 1= hot gas |
| |||||
|
|
|
|
|
|
| |
|
| 2= air |
|
|
|
|
|
|
|
|
|
|
|
| |
| S06 | Dripping time | 1 min | 1 min | 0 min | 90 min | |
| S07 | Compressor activation delay with hot gas defrost | 0 sec | 0 sec | 0 sec | 600 sec | |
| S08 | First defrost activation time from storing start (0=excluded) | 0 | 0 | 0 | 90 min | |
| S09 | Ignores compressor protection delays in defrost | 0 | 0 | 0 | 1 |
|
|
| Defrost type started through keyboard: |
|
|
|
|
|
| S10 | 0= electrical or due to compressor stop | 2 | 0 | 0 | 2 |
|
| 1= hot gas |
| |||||
|
|
|
|
|
|
| |
|
| 2= air |
|
|
|
|
|
|
|
|
|
|
|
|
|
32