Circuit Breaker Connections (1 to 50 Amps)

Connections for 1 to 50 amp dc loads require standard two-hole lugs with holes for #10 screws on 5/8” centers and are located directly above the corresponding circuit breaker. The load returns connect to the return bus located just above and rearward of the breaker connection points as seen in Figure 3.6-4 The return bus provides 24 sets of threaded #10-32 holes on 5/8” centers and four sets of threaded ¼-20 holes on ¾” centers for connection of two-hole lugs on load return wires. Load Connections should be made as shown in Figure 3.6-4

Figure 3.6-4 Standard lug for 1 to 50A breakers.

NOTE: Load return lugs are connected to the front of the return bus to prevent interfering with the top cover of the unit.

Circuit Breaker Connections (60-100 Amps)

Connections for 60 to 100 amp dc loads are twice as wide as the smaller breakers and therefore require two positions and a circuit breaker adapter kit. The adaptor connects the two output lug positions to one lug. Adaptors are available with studs for #10-32 nuts on 5/8” centers, #10-32 nuts on ¾” centers, or ¼-20 nuts on 1” centers. The adaptor is installed directly above the two positions the circuit breaker is mounted on using #10 screws provided in the kit. The lugs (not included with the kit) fasten on to the adaptor’s studs using nuts and washers provided in the kit.

MX28B400 +24 VDC User’s Manual

Page 13

Image 17
Contents Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information Introduction2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsConnecting the Cables Battery ConnectionsPlanning the Battery installation 2 Battery Temperature Probe Installation Battery Temperature Probe InstallationDC System Grounding DC Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Adaptor Size Rating Load Cable Size Considerations Plug-in Circuit Breaker InstallationCircuit Breaker Connections 60-100 Amps Circuit Breaker Connections 1 to 50 AmpsGMT Fuse Option Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationBattery Maximum Recharge Rate default = 12A System Parameters Verification/AdjustmentFull System Power Up Rectifier Management OperationTechnical Description System Management System Status and Alarm ReportingSystem Output Capacity System Voltage ControlBattery Charging and Protection Battery ManagementBattery Temperature Compensation DC DistributionFront Panel User Interface Controls and IndicatorsBattery/Load Low Voltage Disconnect Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress Switzer Av22.00 MinorBatt Max Rechm+ 50 aComp Method m+ Comp LkneeComp TC 00mVHw Batt C Almm+ Fuse 1 AlmHw Batt T Almm+ Hw LVD AlmLVD Reset DisableLamp Test LVD OptionRelay Out-RlyOut-Rly 1 Dly m+ SecRect 1 CL Rect CL AlmRect 1 Curr 24.9Rect 1 Stdby Rect Stdby Almm+Store Cfg Sys Current26.7 Sys TempSys Voltage Test Maj RlyControl Unit Menu Structure Status AlarmsV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysRemote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsAC Input Specifications1MRF28H27BV Rectifiers 1MRF28H27BV50 RectifiersRectifiers DC Output with either RectifierPscu Power Shelf Control UnitCompliance MechanicalEnvironmental APC Worldwide Customer Support Limited Product Warranty