American Power Conversion MX28B400 Comp Lknee, Comp Method m+, Comp TC, 00mV, Cntrl Rev, 000002

Page 31

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Compensation Low Knee

The temperature compensation low knee

Comp Lknee

m+

Security Level {1}

is the point below which there is no

0.0 C

[BATT/COMP]

additional battery voltage compensation

 

 

 

for further decreases in temperature.

 

 

Compensation Method

One of three parameters that control the

Comp Method m+

Security Level {1}

dc output voltage. Activate “ON” or de-

OFF

[BATT/COMP]

activate “OFF” battery temperature

 

 

 

compensation.

 

 

Compensation Temperature

Temperature compensation coefficient

Comp TC

m+

Coefficient

between low knee and high knee in

- 3.00mV

Security Level {1}

mV/cell/°C. (Compensation equals zero

 

 

[BATT/COMP]

at 25°C.)

 

 

Control Unit Revision

Hardware revision level of the control

Cntrl Rev

+

{Status Only}

unit. This parameter cannot be changed.

000002

[SYSTEM/SETUP]

 

 

 

Conv HV Alm

The output relay energized if the

Conv HV Alm

m+

 

Converter Voltage (nominal -48 Vdc) is

Minor

 

above the Converter High Voltage

 

 

 

threshold.

 

 

Conv HV Thr

Converters are an optional device used

Conv HV Thr

m+

 

to convert +24 Vdc to –48 Vdc.

-58.00 V

 

Converter Voltage is converter bus

 

 

 

voltage measured by the controller. An

 

 

 

alarm will be reported if voltage is higher

 

 

 

than the voltage entered.

 

 

Conv LV Alm

The output relay energized if the

Conv LV Alm

m+

 

Converter Voltage (nominal -48 Vdc) is

Minor

 

below the Converter Low Voltage

 

 

 

threshold.

 

 

Conv LV Thr

Converters are an optional device used

Conv LV Thr

m+

 

to convert +24 Vdc to –48 Vdc.

-50.00 V

 

Converter Voltage is converter bus

 

 

 

voltage measured by the controller. An

 

 

 

alarm will be reported if voltage is lower

 

 

 

than the voltage entered.

 

 

Date

Internal system calendar date. Used as

Date

m+

Security Level {1}

a date stamp in the event log.

DEC 16 1999

[SYSTEM/DATE]

 

 

 

Display Type

Type number for the control unit display.

Display Type

+

{Status Only}

This parameter cannot be changed.

000255

[SYSTEM/SETUP]

 

 

 

Fahrenheit Scale

Enables selection of Fahrenheit or

Fahrenheit

m+

Security Level {1}

Celsius temperature scale (Fahrenheit

OFF

[SYSTEM/SETUP]

“OFF” displays readings in °C).

 

 

Firmware Version

Version number of the control unit

FW Version

+

{Status Only}

firmware.

000192

[SYSTEM/SETUP]

NOTE: Actual firmware version

 

 

 

number displayed is the current

 

 

 

version as of the date of manufacture.

 

 

 

This parameter cannot be changed.

 

 

MX28B400 +24 VDC User’s Manual

Page 27

 

Image 31
Contents Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information Introduction2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsPlanning the Battery installation Battery ConnectionsConnecting the Cables 2 Battery Temperature Probe Installation Battery Temperature Probe InstallationDC System Grounding DC Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Adaptor Size Rating Load Cable Size Considerations Plug-in Circuit Breaker InstallationCircuit Breaker Connections 60-100 Amps Circuit Breaker Connections 1 to 50 AmpsSmart Cable DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Option Front Panel DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationBattery Maximum Recharge Rate default = 12A System Parameters Verification/AdjustmentFull System Power Up Technical Description OperationRectifier Management System Voltage Control System Status and Alarm ReportingSystem Management System Output CapacityDC Distribution Battery ManagementBattery Charging and Protection Battery Temperature CompensationBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMSwitzer Av Alarm ItemNo Alarms Address50 a Minor22.00 Batt Max Rechm+00mV Comp LkneeComp Method m+ Comp TCHw LVD Alm Fuse 1 AlmHw Batt C Almm+ Hw Batt T Almm+LVD Option DisableLVD Reset Lamp TestSec Out-RlyRelay Out-Rly 1 Dly m+24.9 Rect CL AlmRect 1 CL Rect 1 CurrSys Current Rect Stdby Almm+Rect 1 Stdby Store CfgTest Maj Rly Sys Temp26.7 Sys VoltageControl Unit Menu Structure Status AlarmsV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysPhysical Connections Command and Monitoring ProtocolRemote Monitoring Description1MRF28H27BV50 Rectifiers SpecificationsAC Input 1MRF28H27BV RectifiersRectifiers DC Output with either RectifierPscu Power Shelf Control UnitEnvironmental MechanicalCompliance APC Worldwide Customer Support Limited Product Warranty