Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/ | DESCRIPTION | DISPLAY SCREENS / | |
[MENU LOCATION] |
| DEFAULT SETTINGS | |
|
|
| |
Compensation Low Knee | The temperature compensation low knee | Comp Lknee | m+ |
Security Level {1} | is the point below which there is no | 0.0 C | |
[BATT/COMP] | additional battery voltage compensation |
|
|
| for further decreases in temperature. |
|
|
Compensation Method | One of three parameters that control the | Comp Method m+ | |
Security Level {1} | dc output voltage. Activate “ON” or de- | OFF | |
[BATT/COMP] | activate “OFF” battery temperature |
|
|
| compensation. |
|
|
Compensation Temperature | Temperature compensation coefficient | Comp TC | m+ |
Coefficient | between low knee and high knee in | - 3.00mV | |
Security Level {1} | mV/cell/°C. (Compensation equals zero |
|
|
[BATT/COMP] | at 25°C.) |
|
|
Control Unit Revision | Hardware revision level of the control | Cntrl Rev | + |
{Status Only} | unit. This parameter cannot be changed. | 000002 | |
[SYSTEM/SETUP] |
|
|
|
Conv HV Alm | The output relay energized if the | Conv HV Alm | m+ |
| Converter Voltage (nominal | Minor | |
| above the Converter High Voltage |
|
|
| threshold. |
|
|
Conv HV Thr | Converters are an optional device used | Conv HV Thr | m+ |
| to convert +24 Vdc to |
| |
| Converter Voltage is converter bus |
|
|
| voltage measured by the controller. An |
|
|
| alarm will be reported if voltage is higher |
|
|
| than the voltage entered. |
|
|
Conv LV Alm | The output relay energized if the | Conv LV Alm | m+ |
| Converter Voltage (nominal | Minor | |
| below the Converter Low Voltage |
|
|
| threshold. |
|
|
Conv LV Thr | Converters are an optional device used | Conv LV Thr | m+ |
| to convert +24 Vdc to |
| |
| Converter Voltage is converter bus |
|
|
| voltage measured by the controller. An |
|
|
| alarm will be reported if voltage is lower |
|
|
| than the voltage entered. |
|
|
Date | Internal system calendar date. Used as | Date | m+ |
Security Level {1} | a date stamp in the event log. | DEC 16 1999 | |
[SYSTEM/DATE] |
|
|
|
Display Type | Type number for the control unit display. | Display Type | + |
{Status Only} | This parameter cannot be changed. | 000255 | |
[SYSTEM/SETUP] |
|
|
|
Fahrenheit Scale | Enables selection of Fahrenheit or | Fahrenheit | m+ |
Security Level {1} | Celsius temperature scale (Fahrenheit | OFF | |
[SYSTEM/SETUP] | “OFF” displays readings in °C). |
|
|
Firmware Version | Version number of the control unit | FW Version | + |
{Status Only} | firmware. | 000192 | |
[SYSTEM/SETUP] | NOTE: Actual firmware version |
|
|
| number displayed is the current |
|
|
| version as of the date of manufacture. |
|
|
| This parameter cannot be changed. |
|
|
MX28B400 +24 VDC User’s Manual | Page 27 |
|