American Power Conversion MX28B400 Sys Temp, 26.7, Sys Voltage, Test Maj Rly, Test Min Rly, Time

Page 37

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

System Temperature

System temperature measured within the

Sys Temp

+

{Status Only}

control unit.

26.7

C

[STATUS]

 

 

 

System Voltage

System output voltage measured

Sys Voltage

+

{Status Only}

between the power plant +24V and

27.00 V

[STATUS]

return buses.

 

 

Test Major Relay

Setting this parameter to “ON” de-

Test Maj Rly

m+

Security Level {1}

energizes the Major Relay and turns on

OFF

 

[SYSTEM/DIAG]

the “MAJ” LED on the control unit front

 

 

 

panel. In normal operation Major Relay

 

 

 

is energized so that when a loss of +24

 

 

 

Vdc power occurs, the relay will change

 

 

 

state.

 

 

Test Minor Relay

Setting this parameter to “ON” energizes

Test Min Rly

m+

Security Level {1}

the Minor Relay and turns on the “MIN”

OFF

 

[SYSTEM/DIAG]

LED on the control unit front panel.

 

 

Test Relay 1

Setting this parameter to “ON” energizes

Test Relay 1

m+

Security Level {1}

Relay 1 and turns on the “ALM1” LED on

OFF

 

[SYSTEM/DIAG]

the control unit front panel.

 

 

 

 

 

 

Test Relay 6

Setting this parameter to “ON” energizes

 

Security Level {1}

Relay 6 and turns on the “ALM6” LED on

Test Relay 6

m+

[SYSTEM/DIAG]

the control unit front panel.

OFF

 

 

 

 

 

 

 

Test Relay Enable

This parameter must be set to “Enable”

Test Relay En m+

Security Level {1}

to permit the eight output relays to be

Disable

 

[SYSTEM/DIAG]

manually tested; otherwise, the state of

 

 

 

the relays will be per system conditions.

 

 

Time

Internal system clock time (24-hour

Time

m+

Security Level {1}

format). Used as a date stamp in the

9:00:25

 

[SYSTEM/DATE]

event log.

 

 

MX28B400 +24 VDC User’s Manual

Page 33

Image 37
Contents Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information Introduction2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsPlanning the Battery installation Battery ConnectionsConnecting the Cables 2 Battery Temperature Probe Installation Battery Temperature Probe InstallationDC System Grounding DC Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Adaptor Size Rating Load Cable Size Considerations Plug-in Circuit Breaker InstallationCircuit Breaker Connections 60-100 Amps Circuit Breaker Connections 1 to 50 AmpsGMT Fuse Option Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationBattery Maximum Recharge Rate default = 12A System Parameters Verification/AdjustmentFull System Power Up Technical Description OperationRectifier Management System Management System Status and Alarm ReportingSystem Output Capacity System Voltage ControlBattery Charging and Protection Battery ManagementBattery Temperature Compensation DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress Switzer Av22.00 MinorBatt Max Rechm+ 50 aComp Method m+ Comp LkneeComp TC 00mVHw Batt C Almm+ Fuse 1 AlmHw Batt T Almm+ Hw LVD AlmLVD Reset DisableLamp Test LVD OptionRelay Out-RlyOut-Rly 1 Dly m+ SecRect 1 CL Rect CL AlmRect 1 Curr 24.9Rect 1 Stdby Rect Stdby Almm+Store Cfg Sys Current26.7 Sys TempSys Voltage Test Maj RlyControl Unit Menu Structure Status AlarmsV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysRemote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsAC Input Specifications1MRF28H27BV Rectifiers 1MRF28H27BV50 RectifiersRectifiers DC Output with either RectifierPscu Power Shelf Control UnitEnvironmental MechanicalCompliance APC Worldwide Customer Support Limited Product Warranty