American Power Conversion MX28B400 Minor, 22.00, Batt Max Rechm+, 50 a, Batt Temp, 25.2 C, Major

Page 30

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Battery Low Temperature

The output relay energized if the Battery

Batt LT Alm

m+

Alarm

Temperature drops below the battery

Minor

Security Level {1}

Low Temperature threshold.

 

 

[BATT/SET-ALM]

 

 

 

Battery Low Temperature

Battery Temperature is temperature

Batt LT Thr

m+

Threshold Security Level {1}

measured at the battery probe. An alarm

 

0.0 C

[BATT/SET-ALM]

is generated if the battery temperature

 

 

 

drops below this value.

 

 

Battery Low Voltage Alarm

The output relay energized if the dc

Batt LV Alm

m+

Security Level {1}

output voltage drops below the battery

Minor

[BATT/SET-ALM]

low voltage threshold.

 

 

Battery Low Voltage Threshold

An alarm is generated if the dc output

Batt LV Thr

m+

Security Level {1}

voltage drops below this value.

22.00 V

[BATT/SET-ALM]

 

 

 

Battery Maximum Recharge

One of three parameters that control the

Batt Max Rechm+

Current

dc output voltage. If Battery Current

 

50 A

Security Level {1}

surpasses the Maximum Battery

 

 

[BATT/PARAM]

Recharge Current, the dc output voltage

 

 

 

will be reduced (the system limits the

 

 

 

charging current to this programmable

 

 

 

value).

 

 

Battery Temperature

Battery temperature measured by the

Batt Temp

+

{Status Only}

system controller at the optional battery

25.2 C

[STATUS]

temperature sensor probe.

 

 

Circuit Breaker 1 Alias

An alternate name (alias) that can be

Cir Bkr 1

m+

Security Level {1}

assigned to a circuit breaker if desired.

 

+24V

[MODULES/CIRBKR/ALIAS]

 

 

 

 

 

 

 

Circuit Breaker 24 Alias

An alternate name (alias) that can be

 

Security Level {1}

assigned to a circuit breaker if desired.

Cir Bkr 24

m+

[MODULES/CIRBKR/ALIAS]

 

 

+24V

 

 

 

Circuit Breaker 1 Tripped

An alarm that indicates Circuit Breaker 1

Cir Bkr 1 Alm m+

Security Level {1}

is tripped.

Major

[MODULES/CIRBKR/SET-

 

 

 

ALM]

 

 

 

 

 

 

Circuit Breaker 24 Tripped

An alarm that indicates Circuit Breaker

 

Security Level {1}

24 is tripped.

Cir Bkr 24 Almm+

[MODULES/CIRBKR/SET-

 

 

Major

ALM]

 

 

 

 

Compensation High Knee

The temperature compensation high

Comp Hknee

m+

Security Level {1}

knee is the point above which there is no

40.0 C

[BATT/COMP]

additional battery voltage compensation

 

 

 

for further increases in temperature.

 

 

MX28B400 +24 VDC User’s Manual

Page 26

Image 30
Contents Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction General Information2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation 2 Battery Temperature Probe InstallationDC System Grounding DC Power Output Over-Current Protection DC Circuit BreakersBreaker Part Number Adaptor Size Rating Plug-in Circuit Breaker Installation Load Cable Size ConsiderationsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Option Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Battery Maximum Recharge Rate default = 12AFull System Power Up Operation Technical DescriptionRectifier Management System Output Capacity System Status and Alarm ReportingSystem Management System Voltage ControlBattery Temperature Compensation Battery ManagementBattery Charging and Protection DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer AvBatt Max Rechm+ Minor22.00 50 aComp TC Comp LkneeComp Method m+ 00mVHw Batt T Almm+ Fuse 1 AlmHw Batt C Almm+ Hw LVD AlmLamp Test DisableLVD Reset LVD OptionOut-Rly 1 Dly m+ Out-RlyRelay SecRect 1 Curr Rect CL AlmRect 1 CL 24.9Store Cfg Rect Stdby Almm+Rect 1 Stdby Sys CurrentSys Voltage Sys Temp26.7 Test Maj RlyStatus Alarms Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysDescription Command and Monitoring ProtocolRemote Monitoring Physical Connections1MRF28H27BV Rectifiers SpecificationsAC Input 1MRF28H27BV50 RectifiersDC Output with either Rectifier RectifiersPower Shelf Control Unit PscuMechanical EnvironmentalCompliance APC Worldwide Customer Support Limited Product Warranty