American Power Conversion MX28B400 Lamp Test, LVD Option, Disable, LVD Reset, +24.00, LVD Trip

Page 33

Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Lamp Test

Setting Lamp Test to “ON” will turn on

Lamp Test

m+

Security Level {1}

the “MAJOR”, “MINOR”, “NORMAL”,

OFF

 

[SYSTEM/DIAG]

“MAJ”, and “MIN” LEDs on the control

 

 

 

unit front panel.

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an

LVD Option

m+

Security Level {1}

LVD. If the unit has an LVD, but it is

Disable

[MODULES/LVD/SET-ALM]

disabled, the controller will not

 

 

 

disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

+24.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

+21.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when

LVD Open Alm m+

Security Level {1}

the controller opens the LVD. If unit has

Minor

 

[MODULES/LVD/SET-ALM]

a battery LVD, no power will be available

 

 

 

to turn on any Output Relays.

 

 

Model Programming

Model type number for the power plant

Model

m+

Security Level {2}

NOTE: Changing the model number

MX28B-400 +24V

[SYSTEM/SETUP]

causes the system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory

OEM R Gain

m+

Security Level {2}

calibration of system voltage

1.000 V

[OEM]

readings/settings.

 

 

OEM R Offset

Voltage offset adjustment for factory

OEM R Offset

m+

Security Level {2}

calibration of system voltage

0.000 V

[OEM]

readings/settings.

 

 

OEM S Gain

Current gain adjustment for factory

OEM S Gain

m+

Security Level {2}

calibration of battery current

1.000 A

[OEM]

readings/settings.

 

 

OEM S Offset

Current offset adjustment for factory

OEM S Offset

m+

Security Level {2}

calibration of battery current

0.0 A

[OEM]

readings/settings.

 

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped”

Out-Rly 1 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

 

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

MAP]

 

 

 

 

 

 

Output Relay 6 Alarm

Output Relay 6 Alarm can be “mapped”

Out-Rly 6 Alm m+

Security Level {1}

to activate other output relays (“Ignore”

Ignore

 

[SYSTEM/OUT-RLY/RLY-

activates no additional relays).

 

 

 

MAP]

 

 

 

MX28B400 +24 VDC User’s Manual

Page 29

Image 33
Contents Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information Introduction2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsBattery Connections Planning the Battery installationConnecting the Cables 2 Battery Temperature Probe Installation Battery Temperature Probe InstallationDC System Grounding DC Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Adaptor Size Rating Load Cable Size Considerations Plug-in Circuit Breaker InstallationCircuit Breaker Connections 60-100 Amps Circuit Breaker Connections 1 to 50 AmpsGMT Fuse Option Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationBattery Maximum Recharge Rate default = 12A System Parameters Verification/AdjustmentFull System Power Up Operation Technical DescriptionRectifier Management System Management System Status and Alarm ReportingSystem Output Capacity System Voltage ControlBattery Charging and Protection Battery ManagementBattery Temperature Compensation DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress Switzer Av22.00 MinorBatt Max Rechm+ 50 aComp Method m+ Comp LkneeComp TC 00mVHw Batt C Almm+ Fuse 1 AlmHw Batt T Almm+ Hw LVD AlmLVD Reset DisableLamp Test LVD OptionRelay Out-RlyOut-Rly 1 Dly m+ SecRect 1 CL Rect CL AlmRect 1 Curr 24.9Rect 1 Stdby Rect Stdby Almm+Store Cfg Sys Current26.7 Sys TempSys Voltage Test Maj RlyControl Unit Menu Structure Status AlarmsV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysRemote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsAC Input Specifications1MRF28H27BV Rectifiers 1MRF28H27BV50 RectifiersRectifiers DC Output with either RectifierPscu Power Shelf Control UnitMechanical EnvironmentalCompliance APC Worldwide Customer Support Limited Product Warranty