Parameter Locations, Descriptions, and Default Values
PARAMETER NAME/ | DESCRIPTION | DISPLAY SCREENS / | |
[MENU LOCATION] |
| DEFAULT SETTINGS | |
|
|
| |
Lamp Test | Setting Lamp Test to “ON” will turn on | Lamp Test | m+ |
Security Level {1} | the “MAJOR”, “MINOR”, “NORMAL”, | OFF |
|
[SYSTEM/DIAG] | “MAJ”, and “MIN” LEDs on the control |
|
|
| unit front panel. |
|
|
LVD 1 or 2 Option | Must be set to “Enable” if the unit has an | LVD Option | m+ |
Security Level {1} | LVD. If the unit has an LVD, but it is | Disable | |
| disabled, the controller will not |
|
|
| disconnect the LVD. |
|
|
LVD 1 or 2 Reset | LVD Reset (reconnect) threshold voltage. | LVD Reset | m+ |
Security Level {1} |
| +24.00 V | |
[MODULES/LVD/PARAM] |
|
|
|
LVD 1 or 2 Trip | LVD Trip (disconnect) threshold voltage. | LVD Trip | m+ |
Security Level {1} |
| +21.00 V | |
[MODULES/LVD/PARAM] |
|
|
|
LVD Alarm | The output relay that is energized when | LVD Open Alm m+ | |
Security Level {1} | the controller opens the LVD. If unit has | Minor |
|
a battery LVD, no power will be available |
|
| |
| to turn on any Output Relays. |
|
|
Model Programming | Model type number for the power plant | Model | m+ |
Security Level {2} | NOTE: Changing the model number |
| |
[SYSTEM/SETUP] | causes the system to reinitialize. |
|
|
OEM R Gain | Voltage gain adjustment for factory | OEM R Gain | m+ |
Security Level {2} | calibration of system voltage | 1.000 V | |
[OEM] | readings/settings. |
|
|
OEM R Offset | Voltage offset adjustment for factory | OEM R Offset | m+ |
Security Level {2} | calibration of system voltage | 0.000 V | |
[OEM] | readings/settings. |
|
|
OEM S Gain | Current gain adjustment for factory | OEM S Gain | m+ |
Security Level {2} | calibration of battery current | 1.000 A | |
[OEM] | readings/settings. |
|
|
OEM S Offset | Current offset adjustment for factory | OEM S Offset | m+ |
Security Level {2} | calibration of battery current | 0.0 A | |
[OEM] | readings/settings. |
|
|
Output Relay 1 Alarm | Output Relay 1 Alarm can be “mapped” |
| |
Security Level {1} | to activate other output relays (“Ignore” | Ignore |
|
activates no additional relays). |
|
| |
MAP] |
| • |
|
• | • |
| |
• |
| ||
• | • |
| |
• | • | • |
|
Output Relay 6 Alarm | Output Relay 6 Alarm can be “mapped” |
| |
Security Level {1} | to activate other output relays (“Ignore” | Ignore |
|
activates no additional relays). |
| ||
|
| ||
MAP] |
|
|
|
MX28B400 +24 VDC User’s Manual | Page 29 |