American Power Conversion MX28B400 user manual AC Power Connections, Ventilation

Page 10

Ventilation

The rectifier modules for this system have fans that provide front-to-rear airflow for internal cooling. The MX28B housing should mounted such that there is free airflow to the front, top, and bottom of the unit. [Refer to Section 6.5 for environmental characteristics.] Free airflow should be ensured so that the power system can provide full power without de-rating.

3.3. AC Power Connections

WARNING: Ensure that all of the external dc and ac circuit breakers are in the OFF position prior to connecting service to the power plant. Confirm that all voltages have been removed including any battery sources before proceeding.

The MX28B power plant requires the supply of nominal 230 Vac single-phase, 50/60 Hz power through individual external 20-amp circuit breakers to the ac input terminal block connections for each rectifier module in the system. Two rectifier modules are required to accommodate the full ac input voltage range. The 1MRF28H27BV rectifier is designed for the standard 208/220/240 Vac input service, while the 1MRF28H27BV50 is used for the 277 Vac input. The ac wiring, from the input terminal block connections to the hot-pluggable ac input connector for each rectifier, is factory installed.

The ac input enclosure, located at the top right rear of the MX28B housing, is provided with two one-inch conduit entry holes and an access cover. Inside, a terminal strip for ac input power connection and a separate “Earth Ground” bar for connection of the safety ground wire(s) are provided. The terminal block(s) is labeled as Position 1 through Position 4 with each position having inputs designated “L1” and “L2/N” for connection of the 2 ac wires. Positions 1-4 correspond to the rectifier shelf positions from left to right.

The suggested wire size is #10 AWG rated at 90°C or higher; however, the ambient temperature and number of wires in a conduit must also be considered in accordance with NEC requirements. It is suggested that feeds for four rectifiers (8 wires) and one safety ground wire be run in a one-inch conduit; however, be sure to follow any local electrical wiring codes.

If the ac input power is provided from a three-phase distribution panel, the circuit breaker positions should be selected such that the load is balanced as much as possible.

WARNING: The MX28B power plant is supplied from a nominal 230Vac, 60 Hz source. Keep the ac input enclosure in place when the system is operational or energized.

MX28B400 +24 VDC User’s Manual

Page 6

Image 10
Contents Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction General Information2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationPlanning the Battery installation Battery ConnectionsConnecting the Cables Battery Temperature Probe Installation 2 Battery Temperature Probe InstallationDC System Grounding DC Power Output Over-Current Protection DC Circuit BreakersBreaker Part Number Adaptor Size Rating Plug-in Circuit Breaker Installation Load Cable Size ConsiderationsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Option Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Battery Maximum Recharge Rate default = 12AFull System Power Up Technical Description OperationRectifier Management System Output Capacity System Status and Alarm ReportingSystem Management System Voltage ControlBattery Temperature Compensation Battery ManagementBattery Charging and Protection DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer AvBatt Max Rechm+ Minor22.00 50 aComp TC Comp LkneeComp Method m+ 00mVHw Batt T Almm+ Fuse 1 AlmHw Batt C Almm+ Hw LVD AlmLamp Test DisableLVD Reset LVD OptionOut-Rly 1 Dly m+ Out-RlyRelay SecRect 1 Curr Rect CL AlmRect 1 CL 24.9Store Cfg Rect Stdby Almm+Rect 1 Stdby Sys CurrentSys Voltage Sys Temp26.7 Test Maj RlyStatus Alarms Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysDescription Command and Monitoring ProtocolRemote Monitoring Physical Connections1MRF28H27BV Rectifiers SpecificationsAC Input 1MRF28H27BV50 RectifiersDC Output with either Rectifier RectifiersPower Shelf Control Unit PscuEnvironmental MechanicalCompliance APC Worldwide Customer Support Limited Product Warranty