American Power Conversion MX28B400 user manual System Parameters Verification/Adjustment

Page 22

4)Apply ac Power. Turn on the circuit breakers that supply ac power to the rectifiers in the MX28B power plant. The main screen should appear on the control unit display (see Figure 4.6-1). The display on the control unit is a 2-lines by 16-characters display. The cursor cycles below the characters of the active selection on the display. Information shown in the second line of Figure 4.6-1 that extends beyond 16 characters (to the right of the “S” in “ALARMS”) can viewed on the control unit display by using the scrolling controls (refer to Section 4.6 for operation of the control unit).

NOTE: When ac power is initially applied, there is a 60-second period during which no alarms are reported.

WARNING: The power plant is supplied from a nominal 220Vac, 50/60 Hz source. Keep the ac input enclosure cover in place when the system is operational or energized

.

3.11.System Parameters Verification/Adjustment

The MX28B system control unit is delivered with pre-programmed parameter default settings. A complete listing and description of all system configuration parameters as well as displayable system status and information is provided in Section 4.6. Users should read Section 4.1 to gain an understanding of and how to use the operational features provided by the MX28B power plant. As a minimum, the following parameters should be verified and adjusted, if required, before connecting batteries or loads to the power plant:

1)Battery Float Voltage - default = +27.00Vdc (Check the manufacturer’s recommendation for the batteries being used in the system.)

2)Battery Maximum Recharge Rate - default = 12A.

3)System Voltage - measurement +27.00Vdc (This is a measurement by the system of the output bus voltage.)

4)LVD Option - default = “Enable” (If the MX28B does not have an LVD installed, this should be changed to “Disable”.)

5)Rectifier Information - Check the rectifier information displays to verify that all rectifiers installed can be viewed on the control unit display and that no rectifier alarms are active.

Section 4.6 provides location information for these parameters and how to make changes if required.

MX28B400 +24 VDC User’s Manual

Page 18

Image 22
Contents Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction General Information2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Unpacking Equipment InstallationMechanical Installation Room / LocationAC Power Connections VentilationPlanning the Battery installation Battery ConnectionsConnecting the Cables Battery Temperature Probe Installation 2 Battery Temperature Probe InstallationDC System Grounding DC Power Output Over-Current Protection DC Circuit BreakersBreaker Part Number Adaptor Size Rating Plug-in Circuit Breaker Installation Load Cable Size ConsiderationsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsFront Panel DB9 Connection Monitoring and Relay Output ConnectionsGMT Fuse Option Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Battery Maximum Recharge Rate default = 12AFull System Power Up Technical Description OperationRectifier Management System Output Capacity System Status and Alarm ReportingSystem Management System Voltage ControlBattery Temperature Compensation Battery ManagementBattery Charging and Protection DC DistributionBattery/Load Low Voltage Disconnect Controls and IndicatorsFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAddress Alarm ItemNo Alarms Switzer AvBatt Max Rechm+ Minor22.00 50 aComp TC Comp LkneeComp Method m+ 00mVHw Batt T Almm+ Fuse 1 AlmHw Batt C Almm+ Hw LVD AlmLamp Test DisableLVD Reset LVD OptionOut-Rly 1 Dly m+ Out-RlyRelay SecRect 1 Curr Rect CL AlmRect 1 CL 24.9Store Cfg Rect Stdby Almm+Rect 1 Stdby Sys CurrentSys Voltage Sys Temp26.7 Test Maj RlyStatus Alarms Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysDescription Command and Monitoring ProtocolRemote Monitoring Physical Connections1MRF28H27BV Rectifiers SpecificationsAC Input 1MRF28H27BV50 RectifiersDC Output with either Rectifier RectifiersPower Shelf Control Unit PscuEnvironmental MechanicalCompliance APC Worldwide Customer Support Limited Product Warranty