4)Apply ac Power. Turn on the circuit breakers that supply ac power to the rectifiers in the MX28B power plant. The main screen should appear on the control unit display (see Figure
NOTE: When ac power is initially applied, there is a
WARNING: The power plant is supplied from a nominal 220Vac, 50/60 Hz source. Keep the ac input enclosure cover in place when the system is operational or energized
.
3.11.System Parameters Verification/Adjustment
The MX28B system control unit is delivered with
1)Battery Float Voltage - default = +27.00Vdc (Check the manufacturer’s recommendation for the batteries being used in the system.)
2)Battery Maximum Recharge Rate - default = 12A.
3)System Voltage - measurement ≅ +27.00Vdc (This is a measurement by the system of the output bus voltage.)
4)LVD Option - default = “Enable” (If the MX28B does not have an LVD installed, this should be changed to “Disable”.)
5)Rectifier Information - Check the rectifier information displays to verify that all rectifiers installed can be viewed on the control unit display and that no rectifier alarms are active.
Section 4.6 provides location information for these parameters and how to make changes if required.
MX28B400 +24 VDC User’s Manual | Page 18 |