Parameter Locations, Descriptions, and Default Values

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

Rectifier Standby Alarm

The output relay that is energized or

Rect Stdby Almm+

Security Level {1}

special rectifier alarm group n of N that

n of N

 

[MODULES/RECT/SET-ALM]

occurs when the control unit is holding a

 

 

 

rectifier in the standby mode.

 

 

Rectifier Standby Alarm Status

The status will be “ON” if the control unit

Rect 1 Stdby

#

{Status Only}

is holding the rectifier in the standby

OFF

 

[MODULES/RECT/INFO]

mode. NOTE: This information can be

 

 

 

viewed for each rectifier installed by

 

 

 

using the horizontal arrow keys.

 

 

Store Configuration

Setting this parameter to “Enable” will

Store Cfg

m+

Security Level {1}

cause the current rectifier configuration

Disable

 

[SYSTEM/DIAG]

to be stored (the display toggles back to

 

 

 

“Disable” after entry).

 

 

System Current

The total system output current

Sys Current

+

{Status Only}

(calculated as the sum of the individual

145.8

A

[STATUS]

rectifier output currents).

 

 

System High Temperature

The output relay energized if the System

Sys HT Alm

m+

Alarm

Temperature exceeds the system high

Minor

 

Security Level {1}

temperature threshold.

 

 

[SYSTEM/SET-ALM]

 

 

 

System High Temperature

System Temperature is ambient

Sys HT Thr

m+

Threshold

temperature measured inside the

70.0

C

Security Level {1}

controller. An alarm will be reported if

 

 

[SYSTEM/SET-ALM]

temperature is higher than the

 

 

 

temperature entered.

 

 

System High Voltage alarm

The output relay energized if the System

Sys HV Alm

m+

Security Level {1}

Voltage is above the System High

Minor

 

[SYSTEM/SET-ALM]

Voltage threshold.

 

 

System High Voltage

System Voltage is bus voltage measured

Sys HV Thr

m+

Threshold

by the controller. An alarm will be

29.00

V

Security Level {1}

reported if voltage is higher than the

 

 

[SYSTEM/SET-ALM]

voltage entered.

 

 

System Low Temperature

The output relay energized if the System

Sys LT Alm

m+

Alarm

Temperature is below the System Low

Minor

 

Security Level {1}

Temperature threshold.

 

 

[SYSTEM/SET-ALM]

 

 

 

System Low Temperature

System Temperature is ambient

Sys LT Thr

m+

Threshold

temperature measured inside the

0.0

C

Security Level {1}

controller. An alarm will be reported if

 

 

[SYSTEM/SET-ALM]

temperature is lower than the

 

 

 

temperature entered.

 

 

System Low Voltage Alarm

The output relay energized if the System

Sys LV Alm

m+

Security Level {1}

Voltage is below the System Low Voltage

Minor

 

[SYSTEM/SET-ALM]

threshold.

 

 

System Low Voltage Threshold

System Voltage is bus voltage measured

Sys LV Thr

m+

Security Level {1}

by the controller. An alarm will be

25.00

V

[SYSTEM/SET-ALM]

reported if voltage is lower than the

 

 

 

voltage entered.

 

 

MX28B400 +24 VDC User’s Manual

Page 32

Image 36
Contents Page Table of Contents Remote Monitoring Revision History Revision Date DescriptionSafety First General PrecautionsIntroduction General Information2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Power Connections VentilationBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation 2 Battery Temperature Probe InstallationDC System Grounding DC Power Output Over-Current Protection DC Circuit BreakersBreaker Part Number Adaptor Size Rating Plug-in Circuit Breaker Installation Load Cable Size ConsiderationsCircuit Breaker Connections 1 to 50 Amps Circuit Breaker Connections 60-100 AmpsMonitoring and Relay Output Connections GMT Fuse OptionFront Panel DB9 Connection Smart Cable DB9 ConnectionRJ45 Ethernet Connector Relay Output ConnectionsExternal Alarm Input Connections NO-NC-CRectifier Module Installation Initial Power-Up and CheckoutSystem Parameters Verification/Adjustment Battery Maximum Recharge Rate default = 12AFull System Power Up Operation Technical DescriptionRectifier Management System Status and Alarm Reporting System ManagementSystem Output Capacity System Voltage ControlBattery Management Battery Charging and ProtectionBattery Temperature Compensation DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Status Alarms System Modules Batt PIN OEM Parameter Locations, Descriptions, and Default ValuesAlarm Item No AlarmsAddress Switzer AvMinor 22.00Batt Max Rechm+ 50 aComp Lknee Comp Method m+Comp TC 00mVFuse 1 Alm Hw Batt C Almm+Hw Batt T Almm+ Hw LVD AlmDisable LVD ResetLamp Test LVD OptionOut-Rly RelayOut-Rly 1 Dly m+ SecRect CL Alm Rect 1 CLRect 1 Curr 24.9Rect Stdby Almm+ Rect 1 StdbyStore Cfg Sys CurrentSys Temp 26.7Sys Voltage Test Maj RlyStatus Alarms Control Unit Menu StructureV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators Alarm Outputs Output Relays External Alarm Inputs Input RelaysCommand and Monitoring Protocol Remote MonitoringDescription Physical ConnectionsSpecifications AC Input1MRF28H27BV Rectifiers 1MRF28H27BV50 RectifiersDC Output with either Rectifier RectifiersPower Shelf Control Unit PscuMechanical EnvironmentalCompliance APC Worldwide Customer Support Limited Product Warranty