American Power Conversion MX28B400 Rectifier Module Installation, Initial Power-Up and Checkout

Page 21

3.9. Rectifier Module Installation

WARNING: Rectifier output circuits would be damaged if battery were installed incorrectly. Before rectifier installation, ensure proper battery polarity and that the battery is isolated from the rest of the system

The rectifier modules are shipped in separate containers. Follow the procedure below to install a rectifier module.

1)Remove the rectifier from its shipping container.

2)Remove any rectifier retaining screws from the shelf position where the rectifier is to be installed.

3)Slide the rectifier module into the shelf between the guides until it is fully seated.

4)Fasten the rectifier in place with the rectifier retaining screw (included in literature kit with product manual).

Since all adjustments are made from the system control unit, no rectifier adjustments are necessary.

NOTE: All “FLOAT” – “BOOST/EQUALISE” switches (one is located on the front of each rectifier in the system) must be set to “FLOAT” to allow the MX28B to control the output voltage properly.

CAUTION: Rectifier fan inlet filters are available for dusty or hostile environments. Failure to periodically check and clean filters can lead to rectifier shutdown due to over temperature and produce power plant failure.

3.10.Initial Power-Up and Checkout

Before initiating power-up and checkout, ensure that the following conditions exist:

1)Make sure that the external circuit breaker protecting the cables from the battery to the power plant is turned OFF (the battery cables should be connected to the power plant, but the battery should not be connected).

2)Make sure that all load circuit breakers are turned OFF (including the one feeding the GMT fuses if the unit has the GMT fuse option).

3)Verify that all rectifiers have been installed.

MX28B400 +24 VDC User’s Manual

Page 17

Image 21
Contents Page Table of Contents Remote Monitoring Revision Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information Introduction2 MX28B-400 +24 Vdc System Wiring Diagram with Battery LVD How to Use This Manual Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsBattery Connections Planning the Battery installationConnecting the Cables 2 Battery Temperature Probe Installation Battery Temperature Probe InstallationDC System Grounding DC Circuit Breakers DC Power Output Over-Current ProtectionBreaker Part Number Adaptor Size Rating Load Cable Size Considerations Plug-in Circuit Breaker InstallationCircuit Breaker Connections 60-100 Amps Circuit Breaker Connections 1 to 50 AmpsGMT Fuse Option Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Smart Cable DB9 ConnectionRelay Output Connections RJ45 Ethernet ConnectorNO-NC-C External Alarm Input ConnectionsInitial Power-Up and Checkout Rectifier Module InstallationBattery Maximum Recharge Rate default = 12A System Parameters Verification/AdjustmentFull System Power Up Operation Technical DescriptionRectifier Management System Management System Status and Alarm ReportingSystem Output Capacity System Voltage ControlBattery Charging and Protection Battery ManagementBattery Temperature Compensation DC DistributionControls and Indicators Battery/Load Low Voltage DisconnectFront Panel User Interface Parameter Locations, Descriptions, and Default Values Status Alarms System Modules Batt PIN OEMNo Alarms Alarm ItemAddress Switzer Av22.00 MinorBatt Max Rechm+ 50 aComp Method m+ Comp LkneeComp TC 00mVHw Batt C Almm+ Fuse 1 AlmHw Batt T Almm+ Hw LVD AlmLVD Reset DisableLamp Test LVD OptionRelay Out-RlyOut-Rly 1 Dly m+ SecRect 1 CL Rect CL AlmRect 1 Curr 24.9Rect 1 Stdby Rect Stdby Almm+Store Cfg Sys Current26.7 Sys TempSys Voltage Test Maj RlyControl Unit Menu Structure Status AlarmsV e l C o n d L e v e l I r d L e v e l U r t h L e v e l Sysout AP Alias MOD Modrec EM Modules Batt Rect Conv CIR SET-ALM Param MOD Modcir MOD Modlvd MT LVD SET-ALM Param Front Panel LED Indicators External Alarm Inputs Input Relays Alarm Outputs Output RelaysRemote Monitoring Command and Monitoring ProtocolDescription Physical ConnectionsAC Input Specifications1MRF28H27BV Rectifiers 1MRF28H27BV50 RectifiersRectifiers DC Output with either RectifierPscu Power Shelf Control UnitMechanical EnvironmentalCompliance APC Worldwide Customer Support Limited Product Warranty