NOTICE!
If the UPS is equipped with an Emergency Power Off (EPO) facility all input sources must be equipped with disconnecting devices.
Terminal rows: X003 and X004 (auxiliary contacts)
When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 from “ON or 1” to “OFF or 0”, the auxiliary contact must open BEFORE the corresponding main contacts are opened. When switching Q001, Q002, Q010, Battery Breaker 1 or Battery Breaker 2 the opposite way from “OFF or 0” to “ON or 1”, the auxiliary contact has to close with a maximum delay of 0.5 seconds from the time the corresponding main contacts are closed.
•This type of auxiliary contact is called a “late make” contact. (This also means that it will “break early” when activated in opposite direction)