American Power Conversion 240-320kW manual Appendix, Installation Planning Data

Page 76

Appendix

8.0Appendix

8.1Table 1. Installation Planning Data

Service (480V

 

 

3 Phase, 3 or 4 wire

Q3

Service Bypass Panel

grounded Wye)

Bypass

input breaker *

Q1

Field

Wiring*

Main Input

Breaker*

UPS Module

Field

Wiring*

Battery Bank

*Supplied by others

Input must be limited to less than 50 kAIC

Installation Planning Data

APC Silcon Series

Load

Q2(480V

3 Phase,

3 or 4

Wire)

 

 

 

 

 

 

 

AC Input (480V)

 

 

Battery System DC

 

AC Output (480V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power rating

 

 

 

 

 

 

 

 

Service

 

 

 

 

 

 

Load side

Heat

 

 

 

Source

P (kW)

I (A)

 

Min. Input

Over-

 

Full

INom

 

IMax

 

Over-

Rejec-

kW

kVA

Pf

V

Hz

Nom.

Max.

Nom.

Max.

 

Cable

current

Vn

load

Disch

 

Disch

In

current

tion

 

(per phase)

Protection*

(Vdc)

P(kW)

(A)

 

(A)

(A)

Protection*

kBTU/hr

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

120

1

480

60

126.8

140.0

152.5

168.0

 

1 x 4/0

225AT

2x384

127.0

166

 

194.8

144.0

200AT

23.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

160

1

480

60

167.5

186.0

201.5

224.0

 

1 x 350mcm

300AT

2x384

168.8

220

 

258.9

192.0

250AT

25.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

240

1

480

60

252.9

280.0

304.2

336.0

 

1 x 700mcm /

450AT

2x384

252.1

328

 

386.7

289.0

400AT

44.0

 

 

 

 

 

 

 

 

 

 

2 x 4/0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

320

320

1

480

60

334.4

373.0

402.2

448.0

 

2 x 350mcm

600AT

2x384

335.4

437

 

514.4

385.0

500AT

49.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

400

1

480

60

415.8

460.0

500.1

560.0

 

2 x 350mcm

700AT

2x384

421.9

549

 

647.1

482.0

600AT

35.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

500

1

480

60

519.2

574.0

624.5

700.0

 

2 x 700 /

900AT

2x384

525.8

685

 

806.4

602.0

800AT

65.5

 

 

 

 

 

 

 

 

 

 

3 x 350mcm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes

 

 

 

 

 

1

2

 

3,6,8,A,B,C,D

4,7,9,D

5

 

6,10

 

6,11

 

4,6,8,D

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Not provided by APC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Nominal (Nom) Input current based on rated load.

2.Maximum (Max:) Input current based on full battery recharge + nominal load.

3.Recommendation: Input and Output cables run in separate conduits.

4.Suggested Input overcurrent protection based on continuous full load

Maximum Input current. Suggested Load Side Overcurrent Protection based on Nominal current. Breakers sized per NEC 220-3 and NEC 240-3(b). 80% rated breakers assumed. Trip rating based on

NEC 240-6(a) standard breaker sizes.

5.Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).

6.Recommendation: All cables should be sized in accordance with NEC 210-19 FPN No. 4 branch feeder voltage drop of 3%. Voltage drop not considered in above chart. Application

990-4049

76

Installation Guide APC Silcon 240-320kW 480V UPS

Image 76
Contents APC Silcon 240-320kW 480V UPS Installation Guide Copyright 2001 APC Denmark ApSSafety Symbols used in this manual Installation Guide APC Silcon 240-320kW 480V UPSThank You Contents Installation Guide APC Silcon 240-320kW 480V UPS Introduction IntroductionTools and Equipment ToolsUnpacking/Identification of Equipment Unpacking/Identification of EquipmentService Bypass Panel Battery Breaker BoxBattery Cabinet Main UPS systemIsolation Transformer Seismic AnchoringNema 12 Cover Remote DisplayInstallation InstallationDimensions and Weight Requirements on SiteFootprints UPS Cabinet FootprintsConduit Entrance Plate in bottom of the system COM COM FrontTop Cable Entry External Connection Connecting the UPSExternal Connection Connecting AC and DC Power Cables Dual Utility Connection Dual Utility Connection Seperation of AC from DC1 and DC2 Top or Bottom Cable Entry Dual and Single Utility Supply Working Principle of Dual Utility 2 utility supplies Working Principle of Single Utility 1 utility supplySwitching from Dual to Single Utility Input Wiring Stud size Terminals Input Battery Output System earth TypeStud size M10 M12 Terminal Ground terminals System Integration Interface Single Utility Dual UtilityConnecting the System Integration Interface Board SII-board SII BoardExternal Connection External Connection External Connection Parallel Board Parallel BoardPower Cables External Control CablesRelay Number Message Alarm Trigging Events Relay BoardRelays Relay Board FunctionsExternal Connection Cable Sizes SmartSlot for APC Silcon 240-320kW UPS Communication Interface / Smart SlotConnections SmartSlot Accessories Multiple SmartSlot Installation introductionPriority of APC accessories Installing accessories procedureInstallation in APC Silcon 240kW and 320kW APC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries APC SilconBattery Breaker Box Mounting and Connection of Battery Breaker Box InterconnectionRear of enclosure See measurementsUPS Installations in Computer Rooms UPS with External Battery via Battery Breaker BoxEPO Principle S002 Choose either Emergency shutdown connection betweenPrinciple diagram UPSUtility Possible UPS operation Tripping Emergency Power Off EPO for UPSSupply Single configuration for Single Utility Utility Possible UPS operation modes Tripping SupplyParameter Setting Comments ProgrammingProgramming ParametersProgramming Example Switch to Bypass Operation Programming KeysProgramming System Configuration 438V346V 326VSeparate Programming Example Change Boost Charge Voltage toProgramming Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming Example Battery Monitor Options/Accessories Options/AccessoriesPrinciple diagram Service Bypass Panel for single operation Battery Breaker Box APC Silcon UPS System Integration Interface Mounting and Connecting Service Bypass Panel Options/Accessories Options/Accessories Mounting and Connecting Seismic Anchoring Mounting Seismic Anchoring Nema 12 Cover IP31 Mounting Nema 12 CoverExtension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Screws DP9-FCommunication Fault Remote Display SettingRemote Display Cables Remote Display UseIsolation Transformer Module Cabinets and Dimensions Connecting Isolation TransformerExternal Temperature Alarm Cable FootprintsIsolation Transformer Diagram Delta WYE configuration Dyn11 Isolation Transformer Grounding 6.5.7.1 System GroundingSingle Utility and Redundant System Dual Utility and Single System Dual Utility and Redundant SystemIntersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU System Specifications System SpecificationsTechnical Data Voltage 3x480VAppendix Installation Planning DataAppendix Fepw TBS,SA RH,RHW Correction Factors Warranty WarrantyAPC Silcon Series Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark