American Power Conversion 240-320kW manual Programming, Parameters, Parameter Setting Comments

Page 46

Programming

5.0 Programming

Below table shows operating parameters programmable from keyboard. Only qualified users should amend programming parameters.

5.1Parameters

Parameter

Setting*

 

 

 

Comments

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into bypass

 

 

mode***

 

 

 

 

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF,

Languages of text in display

 

NL, PL, CZ, E, P, SK,

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by utility return (1 min. delay).

 

 

Ensures quick battery recharge.

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote signal when in

 

 

battery operation. Saves battery energy.

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown signal level

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, Time delay on remote shutdown of UPS

 

9, 10 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check. Time measured

 

 

from start until it reaches low DC warning level

 

 

(See User Guide, section 6.0).

 

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery condition by 25%

 

 

discharging.

 

 

 

 

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test in cyclic

 

 

intervals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

.

and

 

 

key to reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light)

 

 

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10 hours)

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after battery

 

 

operation (10 hours).

 

Enter new date

YYMMDD

Set to local date

Enter new time

HHMMSS

Set to local time (24 hour clock)

*Factory settings in bold

**For stystems with avctive Battery Monitor only

***Do not leave system running in bypass mode (static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4049

46

Installation Guide APC Silcon 240-320kW 480V UPS

Image 46
Contents APC Silcon 240-320kW 480V UPS Installation Guide Copyright 2001 APC Denmark ApSSafety Symbols used in this manual Installation Guide APC Silcon 240-320kW 480V UPSThank You Contents Installation Guide APC Silcon 240-320kW 480V UPS Tools and Equipment IntroductionIntroduction ToolsUnpacking/Identification of Equipment Unpacking/Identification of EquipmentBattery Cabinet Service Bypass PanelBattery Breaker Box Main UPS systemNema 12 Cover Isolation TransformerSeismic Anchoring Remote DisplayDimensions and Weight InstallationInstallation Requirements on SiteFootprints UPS Cabinet FootprintsConduit Entrance Plate in bottom of the system COM COM FrontTop Cable Entry External Connection Connecting the UPSExternal Connection Connecting AC and DC Power Cables Dual Utility Connection Dual Utility Connection Seperation of AC from DC1 and DC2 Top or Bottom Cable Entry Dual and Single Utility Supply Working Principle of Dual Utility 2 utility supplies Working Principle of Single Utility 1 utility supplySwitching from Dual to Single Utility Input Wiring Stud size Terminals Input Battery Output System earth TypeStud size M10 M12 Terminal Ground terminals System Integration Interface Single Utility Dual UtilityConnecting the System Integration Interface Board SII-board SII BoardExternal Connection External Connection External Connection Parallel Board Parallel BoardPower Cables External Control CablesRelays Relay Number Message Alarm Trigging EventsRelay Board Relay Board FunctionsExternal Connection Cable Sizes SmartSlot for APC Silcon 240-320kW UPS Communication Interface / Smart SlotConnections Priority of APC accessories SmartSlot AccessoriesMultiple SmartSlot Installation introduction Installing accessories procedureInstallation in APC Silcon 240kW and 320kW APC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries APC SilconBattery Breaker Box Rear of enclosure Mounting and Connection of Battery Breaker BoxInterconnection See measurementsUPS Installations in Computer Rooms UPS with External Battery via Battery Breaker BoxEPO Principle S002 Choose either Emergency shutdown connection between Principle diagram UPSUtility Possible UPS operation Tripping Emergency Power Off EPO for UPSSupply Single configuration for Single Utility Utility Possible UPS operation modes Tripping SupplyProgramming Parameter Setting CommentsProgramming ParametersProgramming Example Switch to Bypass Operation Programming KeysProgramming 346V System Configuration438V 326VSeparate Programming Example Change Boost Charge Voltage toProgramming Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming Example Battery Monitor Options/Accessories Options/AccessoriesPrinciple diagram Service Bypass Panel for single operation Battery Breaker Box APC Silcon UPS System Integration Interface Mounting and Connecting Service Bypass Panel Options/Accessories Options/Accessories Mounting and Connecting Seismic Anchoring Mounting Seismic Anchoring Nema 12 Cover IP31 Mounting Nema 12 CoverExtension of Remote Display Communication Distance Remote DisplayStandard Short-haul RS232 Modem Async Connections With Converter Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Screws DP9-FRemote Display Cables Communication FaultRemote Display Setting Remote Display UseIsolation Transformer Module External Temperature Alarm Cable Cabinets and DimensionsConnecting Isolation Transformer FootprintsIsolation Transformer Diagram Delta WYE configuration Dyn11 Isolation Transformer Grounding 6.5.7.1 System GroundingSingle Utility and Redundant System Dual Utility and Single System Dual Utility and Redundant SystemIntersystem Synchronization Unit System ISU System Intersystem Synchronization UnitIntersystem Synchronization Unit ISU Technical Data System SpecificationsSystem Specifications Voltage 3x480VAppendix Installation Planning DataAppendix Fepw TBS,SA RH,RHW Correction Factors Warranty WarrantyAPC Silcon Series Limited Factory Warranty APC Corporate How to Contact APCHow to Contact APC APC Denmark