Programming
Parameter | Setting* | Comments |
|
|
|
APM*** Mode Active | Disabled | Use only in parallel systems. |
| Redundant +1 | Disabled: APM*** off. |
| Parallel +1 | Redundant +1: Redundant operation with one unit |
|
| being inactive in parallel system |
|
| Parallel +1: Redundant operation with all units in |
|
| operation. |
|
|
|
APM Test Mode Active | YES, NO | YES, if APM*** test mode is active |
|
|
|
Battery Connection | Common, | Common: if common battery is used in parallel |
| Separate | system. |
|
| Separate: if separate battery is used |
|
|
|
*Bold text refers to standard factory setting **Advanced Battery Monitor
***Advanced Power Management
5.2.1 Programming Example - Change Boost Charge Voltage to 446V
NOTICE!
Change charge voltages, battery warning limit, shut down voltages and high battery temperature limit by entering the actual value. See example above.
50 | Installation Guide APC Silcon |