Programming
•If APM should not be tested, “APM test mode active” must be “NO”.
•If a system is isolated due to service the station numbers must be reprogrammed for the remaining active systems starting with number 1 and ending with maximum number of active systems. No numbers must be left in this sequence. Furthermore, “Highest station address” must be changed to number of active UPS’s in parallel.
5.4Battery Monitor
Installation of new batteries:
To avoid false alarms, the above procedure MUST be followed.
NOTICE!
Contact your local dealer if you have any questions regarding changing parameters.
Installation Guide APC Silcon | 53 |