American Power Conversion 240-320kW manual External Connection

Page 32

External Connection

Relay Number

Message

Alarm Trigging Events

 

 

 

2 ##

Bypass Outside

Bypass voltage RMS value outside tolerance

(X003)

Tolerance

Bypass wave form (fast detector) outside tolerance

 

 

Bypass frequency outside tolerance

 

 

 

3 ##

Output Outside

Output voltage RMS value outside tolerance

(X004)

Tolerance

Output wave form (fast detector) outside tolerance

 

 

Output frequency outside tolerance

 

 

 

4

System Overload

Output load over 100%

(X005)

 

Delta inverter current limiter active

 

 

Main inverter current limiter active

 

 

 

5 (X006)

Fan Fault

Blocked or faulty fan

 

 

 

6

High Equipment

Static switch temperature too high

(X007)

Temperature or

Main inverter failure (temperature too high or fuse blown)

 

Inverter Fuse Blown

Delta inverter temperature too high

 

 

Magnetics temperature too high

 

 

Isolation transformer optional temperature too high

 

 

Battery temperature too high

 

 

 

7 (X008)

Battery Breaker Box

Battery Breaker Box battery OFF

 

Battery OFF

 

 

 

 

8 (X009)

Normal Operation

UPS running in normal operation (Status)

 

 

 

9 ##

Battery Operation

UPS running in battery operation (Status)

(X010)

 

 

 

 

 

10 ##

Bypass Operation

UPS running in bypass operation (Status)

(X011)

 

 

 

 

 

11 ##

Stand-by Operation

UPS in stand-by mode

(X012)

 

(Hot stand-by, parallel systems only)

 

 

 

12

Service Bypass

Service bypass switch active

(X013)

Operation

 

 

 

 

13 ##

Boost Charge

UPS boost charging on battery

(X014)

Operation

 

 

 

 

14

Battery Voltage Outside

DC voltage too high (shut down)

(X015)

Tolerance

DC voltage under warning level

 

 

DC voltage too low (shut down)

 

 

 

15

Battery Condition Fault

ABM detected battery weak

(X016)

 

ABM detected defective battery

 

 

(ABM = Advanced Battery Monitor)

 

 

 

16 ##

Common Fault

All alarms as mentioned above (except relays

(X017)

 

8+9+10+11)

 

 

Internal power supply fault

 

 

System locked in operation mode

 

 

Internal memory fault

 

 

Internal communication fault

 

 

 

##Delay programmable in XXXXXX stack “Common fault delay”. Settings 0,10,20,30 seconds. See section 5.2: System configuration in this guide.

990-4049

32

Installation Guide APC Silcon 240-320kW 480V UPS

Image 32
Contents APC Silcon 240-320kW 480V UPS Installation Guide Copyright 2001 APC Denmark ApSThank You Installation Guide APC Silcon 240-320kW 480V UPSSafety Symbols used in this manual Contents Installation Guide APC Silcon 240-320kW 480V UPS Introduction IntroductionTools and Equipment ToolsUnpacking/Identification of Equipment Unpacking/Identification of EquipmentService Bypass Panel Battery Breaker BoxBattery Cabinet Main UPS systemIsolation Transformer Seismic AnchoringNema 12 Cover Remote DisplayInstallation InstallationDimensions and Weight Requirements on SiteFootprints UPS Cabinet FootprintsConduit Entrance Plate in bottom of the system COM COM FrontTop Cable Entry External Connection Connecting the UPSExternal Connection Connecting AC and DC Power Cables Dual Utility Connection Dual Utility Connection Seperation of AC from DC1 and DC2 Top or Bottom Cable Entry Dual and Single Utility Supply Working Principle of Dual Utility 2 utility supplies Working Principle of Single Utility 1 utility supplySwitching from Dual to Single Utility Input Wiring Stud size M10 M12 Terminals Input Battery Output System earth TypeStud size Terminal Ground terminals System Integration Interface Single Utility Dual UtilityConnecting the System Integration Interface Board SII-board SII BoardExternal Connection External Connection External Connection Parallel Board Parallel BoardPower Cables External Control CablesRelay Number Message Alarm Trigging Events Relay BoardRelays Relay Board FunctionsExternal Connection Cable Sizes Connections Communication Interface / Smart SlotSmartSlot for APC Silcon 240-320kW UPS SmartSlot Accessories Multiple SmartSlot Installation introductionPriority of APC accessories Installing accessories procedureInstallation in APC Silcon 240kW and 320kW APC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries APC SilconBattery Breaker Box Mounting and Connection of Battery Breaker Box InterconnectionRear of enclosure See measurementsUPS Installations in Computer Rooms UPS with External Battery via Battery Breaker BoxEPO Principle S002 Choose either Emergency shutdown connection betweenPrinciple diagram UPSSupply Emergency Power Off EPO for UPSUtility Possible UPS operation Tripping Single configuration for Single Utility Utility Possible UPS operation modes Tripping SupplyParameter Setting Comments ProgrammingProgramming ParametersProgramming Example Switch to Bypass Operation Programming KeysProgramming System Configuration 438V346V 326VSeparate Programming Example Change Boost Charge Voltage toProgramming Programming Example Description of SettingsProgramming Parameters for Advanced Parallel Operation Battery Monitor Principle diagram Service Bypass Panel for single operation Options/AccessoriesOptions/Accessories Battery Breaker Box APC Silcon UPS System Integration Interface Mounting and Connecting Service Bypass Panel Options/Accessories Options/Accessories Mounting and Connecting Seismic Anchoring Mounting Seismic Anchoring Nema 12 Cover IP31 Mounting Nema 12 CoverStandard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Screws DP9-FCommunication Fault Remote Display SettingRemote Display Cables Remote Display UseIsolation Transformer Module Cabinets and Dimensions Connecting Isolation TransformerExternal Temperature Alarm Cable FootprintsIsolation Transformer Diagram Delta WYE configuration Dyn11 Isolation Transformer Grounding 6.5.7.1 System GroundingSingle Utility and Redundant System Dual Utility and Single System Dual Utility and Redundant SystemIntersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System System Specifications System SpecificationsTechnical Data Voltage 3x480VAppendix Installation Planning DataAppendix Fepw TBS,SA RH,RHW Correction Factors APC Silcon Series Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC Denmark