Programming
5.2System Configuration
System configuration parameters are vital for correct system operation and are password- protected.
Incorrect programming may damage battery or cause output voltage to be lost during operation!
System Configuration Parameters (password protected)
Parameter | Setting* | Comments |
|
|
|
Isolation Transformer | YES, NO | YES, if optional input isolation transformer is |
Input |
| available |
|
|
|
Isolation Transformer | YES, NO | YES, if optional output isolation transformer is |
Output |
| available |
|
|
|
Delta Soft Start Time | 1, 10, 20, 40 sec. | Input current switching in ramp function. Use |
|
| higher values for smaller/unstable diesel |
|
| generators |
|
|
|
External SSW available | YES, NO | YES for systems with external static bypass |
|
| switch |
|
|
|
Normal Charge Voltage | Setting of float charge voltage at 20°C/68°F | |
| 438V | (Automatic compensation for temperature |
|
| deviations) |
|
|
|
Boost Charge Voltage | Setting of boost charge voltage at 20°C/68°F | |
| 438V | (Automatic compensation for temperature |
|
| deviations) |
|
|
|
Low Battery warning | Discharged Battery warning | |
| 346V |
|
|
|
|
Low Battery | Switches off system at minimum permissible | |
| 326V | battery voltage |
|
|
|
Synchronization | 0.25, 0.5, 1, 2, 4 | Synchronization speed. Higher values used at |
| Hz/sec. | unstable utility frequencies. |
|
|
|
High Battery Temperature | Alarm - Ambient battery temperature too high | |
| 104°F |
|
| 35°C/95°F |
|
|
|
|
Common fault delay | 0, 10, 20, | Delay before common fault alarm relay is |
| 30 sec. | activated |
|
|
|
Reset operation mode lock | YES, NO | YES resets system locked in bypass or battery |
|
| operation mode caused by system failures (only |
|
| applicable for service personnel) |
|
|
|
Expected | Expected UPS | |
(min.) | 5.0 | running at 100% ohmic load. Time used by |
|
| ABM** |
|
|
|
Battery Capacity in (Ah) | Total Battery capacity in Ah. | |
| 7.0 | Setting used by ABM**. |
|
|
|
Highest Station Address | Highest station address in parallel system | |
|
|
|
Station Address | Station address in parallel system | |
|
|
|
*Bold text refers to standard factory setting **Advanced Battery Monitor
Installation Guide APC Silcon | 49 |