American Power Conversion 240-320kW manual Remote Display, Standard Short-haul RS232 Modem Async

Page 65

Options/Accessories

6.4Remote Display

With the remote display unit data may be displayed at distances of up to 25m from UPS. For extended communication distance, see below.

Remote display may easily be connected to UPS via one of the two serial communication ports on the communication interface board.

To obtain a transmission distance of up to 3.2km normal RS232C signal levels must be converted to a long distance communication standard. The converter must be placed outside the UPS cabinet.

6.4.1 Extension of Remote Display Communication Distance

The remote display communicates with the UPS through a 3-wire RS232 interface. The remote display is a DTE (Data Terminal Equipment) employing a SUB-D 9-pin female connector. Communication speed: 9600 bps.

For communication distances, see table below. Insert converters if longer distances are necessary, or if communication cables are led through magnetically noisy areas. Converters must comply with local regulations

Remote Display Communication Extensions

 

Standard

Short-haul

 

(RS232)

Modem Async

 

 

 

Max. distance

80/25 ft/m

10000/3200 ft/m

 

 

 

Converter Manufacture

No converter

BLACK BOX

Art. Code

 

ME800A-R2

 

 

 

RS232 BLACK BOX connector

 

Sub-D 25-pin female

 

 

 

BLACK BOX interconnector

 

4-screw terminal

 

 

 

Two converter boxes are required for a communication distance extension: One

box near the UPS for the conversion from RS232C to a long distance communication standard, and another box at the other end to convert back to RS232C, which is to be connected to the

990-4049

Installation Guide APC Silcon 240-320kW 480V UPS

65

Image 65
Contents Copyright 2001 APC Denmark ApS APC Silcon 240-320kW 480V UPS Installation GuideThank You Installation Guide APC Silcon 240-320kW 480V UPSSafety Symbols used in this manual Contents Installation Guide APC Silcon 240-320kW 480V UPS Introduction IntroductionTools and Equipment ToolsUnpacking/Identification of Equipment Unpacking/Identification of EquipmentBattery Breaker Box Service Bypass PanelBattery Cabinet Main UPS systemSeismic Anchoring Isolation TransformerNema 12 Cover Remote DisplayInstallation InstallationDimensions and Weight Requirements on SiteUPS Cabinet Footprints FootprintsCOM COM Front Conduit Entrance Plate in bottom of the systemTop Cable Entry External Connection Connecting the UPSExternal Connection Connecting AC and DC Power Cables Dual Utility Connection Dual Utility Connection Seperation of AC from DC1 and DC2 Top or Bottom Cable Entry Dual and Single Utility Supply Working Principle of Single Utility 1 utility supply Working Principle of Dual Utility 2 utility suppliesSwitching from Dual to Single Utility Input Wiring Stud size M10 M12 Terminals Input Battery Output System earth TypeStud size Terminal Ground terminals Single Utility Dual Utility System Integration InterfaceSII Board Connecting the System Integration Interface Board SII-boardExternal Connection External Connection External Connection Parallel Board Parallel BoardExternal Control Cables Power CablesRelay Board Relay Number Message Alarm Trigging EventsRelays Relay Board FunctionsExternal Connection Cable Sizes Connections Communication Interface / Smart SlotSmartSlot for APC Silcon 240-320kW UPS Multiple SmartSlot Installation introduction SmartSlot AccessoriesPriority of APC accessories Installing accessories procedureInstallation in APC Silcon 240kW and 320kW Important Safety Instructions APC Silcon Battery CabinetsAPC Silcon Installation of BatteriesBattery Breaker Box Interconnection Mounting and Connection of Battery Breaker BoxRear of enclosure See measurementsUPS with External Battery via Battery Breaker Box UPS Installations in Computer RoomsS002 Choose either Emergency shutdown connection between EPO PrincipleUPS Principle diagramSupply Emergency Power Off EPO for UPSUtility Possible UPS operation Tripping Utility Possible UPS operation modes Tripping Supply Single configuration for Single UtilityProgramming Parameter Setting CommentsProgramming ParametersProgramming Keys Programming Example Switch to Bypass OperationProgramming 438V System Configuration346V 326VProgramming Example Change Boost Charge Voltage to SeparateProgramming Programming Example Description of SettingsProgramming Parameters for Advanced Parallel Operation Battery Monitor Principle diagram Service Bypass Panel for single operation Options/AccessoriesOptions/Accessories Battery Breaker Box APC Silcon UPS System Integration Interface Mounting and Connecting Service Bypass Panel Options/Accessories Options/Accessories Mounting and Connecting Seismic Anchoring Mounting Seismic Anchoring Mounting Nema 12 Cover Nema 12 Cover IP31Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Host DTE Remote Display DTE Connections Without ConverterConnections With Converter Pin Connections for cable from host to ME800A-R2 HostScrews DP9-F Remote Display Power SupplyRemote Display Setting Communication FaultRemote Display Cables Remote Display UseIsolation Transformer Module Connecting Isolation Transformer Cabinets and DimensionsExternal Temperature Alarm Cable FootprintsIsolation Transformer Grounding 6.5.7.1 System Grounding Isolation Transformer Diagram Delta WYE configuration Dyn11Single Utility and Redundant System Dual Utility and Redundant System Dual Utility and Single SystemIntersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System System Specifications System SpecificationsTechnical Data Voltage 3x480VAppendix Installation Planning DataAppendix Fepw TBS,SA RH,RHW Correction Factors APC Silcon Series Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC Denmark