Toshiba G9000 operation manual

Page 21

When power is restored after a low battery shutdown, the UPS converter(s) automatically restarts operation, the charger(s) recharges the batteries and the Inverter(s) is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention.

* (s) : In the case of the Parallel Operation

The power drawn by the load is equally shared between all UPS regardless of the presence or absence of the UPS that is (are) in battery operation or not whenever the system is in the Parallel Operation.

G9000 Installation and Operation Manual

11

Image 21
Contents Document 4GBA0012 Rev. E January Page Document No GBA0012 Rev. E January Page Important Notice Uninterruptible Power SystemPurpose and Scope of Manual Table of Contents List of Tables List of Figures Power wire connections parallel system configuration How to use this Manual Important Safety Instructions Safety Precautions Environment standard UPS Installation EnvironmentCapacity kVA Bypass Voltage Vac Bypass Rating Aac Breaker a General Definitions Operation Overview CB3 Mccb Single Line Diagram Battery Operation Page 1 UPS Parts Location 80,100kVA UPS cabinet Front View UPS Parts Location 300kVA Door Backside Main CabinetUPS cabinet Front Inside View Backside of Left Door 4 UPS Parts Location 500kVA UPS cabinet Front ViewItem 10 Grounding bar is not shown in .4.5. Refer to Figure 12. SW5 13. SW6 Reset switch Button Test switchCN96 CN95 CN94 1 Parallel I/F PCB IFAU-08 80-225kVAExternal I/F PCB IOAU-09 Figure Signal I/F on IOAU-09 board Description of Figures 1.4.1-5 toLCD Touch Panel Monitor Display External contact signal terminal block 15 L S/W switch for Service Personnel onlyRefer to Figures 3.7.1 to 3.7.4 for details AC input, AC output, DC input terminal80kVA / 72kW 480V SpecificationsWidth Depth Height Gross Weight Lbs KVA Width Depth Height Net Weight TypicalUPS Lbs Heating KVA Knockout KBTU/hAC Input A Detail of SpecificationsCooling Operating TemperaturePhase I 80-225kVA Phase II 300-750kVA Output Capacity of Equipment Number Application Rating of Contactors, Breakers and FusesOperator Controls and Indicators EPO Button Emergency Power Off button Battery operation Battery OP. orangeLED Display Load on inverter Load on Inverter greenLiquid Crystal Display MenuStartup/Shutdown Guidance Figures 2.3.1 to 2 Startup guidance 2 Output values 1 Log menu Fault Indication Input Power FailureMessage Summary Alarm Triggers on fault alarm only External Signal Terminal BlockOUT8 Total Alarm Triggers on any alarm including faults TN2TN1 Battery Breaker PanelTerminals 7 to 8 Battery Operation contact OUT3 Output Contacts for external alarm annunciationTerminals 11 to 12 Battery Low Voltage contact OUT5 Terminals 3 to 4 Load on Bypass contact OUT112 Remote Start Contact Connections Input Contacts for remote access of UPSTerminals 13 to 14 Power Demand Command contact input IN4 Terminals 11 to 12 Battery Temp. High contact input IN3Used to perform a remote UPS Emergency Power Off EPO Terminals 9 to 10 Remote Inverter Stop input terminal IN2RemotEyeII Introduction 13.1 Configuration of the RemotEyeII Overview 80-225kVADPAU-81 Back of the front door Main cabinet RemotEyeIISW1 Cable2 Cable3 Provided PSAU-60Back of the front left door Main cabinet Provided PSAU-60 PS1 Cable1SW1 Cable1 3BBA0083P001 Male Cable3 12V Power Cable Cable2 Sub 9-pin Cable15 PSAU-60 PCB PS1 Connector Definition Figure Transportation Installation Transportation and InstallationInstallation Procedure Space requirement for routine maintenanceProcedure for Cable Connections External Battery SupplyUPS Capacity DC Voltage KVA Rating Current Permitted aRequired Page Recommended Cable Sizes UPS Terminal Designation Crimp Type Compression LugLocation of bus bars and terminal blocks Bottom Entry UPS moduleInput A40,B40,C40 UPS module 300kVA Detailed Power TerminalsUPS module 500kVA A50, B50, C50 Grounding Bar not shown 18.5UPS module 750kVA AC Output 78.7 A50, B50, C50 Grounding Bar Not shown 19.7BUS BAR Detail TOP View BUS BAR Detail TOP View BUS BAR Connection TOP View Alternate Landing Main Cabinet BUS BAR Connection DC Breaker for Battery CB2 Battery Bypass52S Converter CB1 /Charger Inverter 52CBreaker 52Ln *1 AC output UPS-1 UPS-1 ~~~~~ UPS-1 No.N UPS Use Ethernet STP Shielded Twisted Pair Cable Cat 5 or ~~~~~ Circuit protectors location Operating ProceduresOperation Menu Shut-down ProcedureUPS Bypass Operation ProcedureLCD Screen MMS Operation MMS Start-up ProcedureResponse to UPS Failure Battery Replace battery if its capacity is within this percentageUPS Component Parts Fault Codes Failure Code List Fault Code CB2 Open DC Unbalanced Overvoltage Engineer Inverter Call Service 52S Abnormal Daily Inspection How to perform daily inspectionPage Consult latest edition of applicable National and local codes for possibleVariations 114 150 AT 3/0 27.6 x 32.8 x 855 136 13,463100 120 150 AT 3/0 94 @ 0.9 PF 235 250 AT Kcmil 300 kcmil151 181 250 AT Kcmil 300 kcmil 35.4 x 32.8 x 1160 144 17,821160 192 250 AT Kcmil 300 kcmil 149 @ 0.9 PF 372 400 AT Kcmil212 255 350 AT Kcmil 2 x 250 kcmil 35.4 x 32.8 x 1230 152 25,060225 271 350 AT Kcmil 2 x 250 kcmil 210 @ 0.9 PF 524 600 AT 300 kcmil 2 x 400 kcmil312 376 500 AT 250 kcmil 2 x 300 kcmil 51.2 x 32.7 x 1230 189 31,659300 361 500 AT 4/0 2 x 250 kcmil 309 @ 1.0 PF 772 800 AT 400 kcmil521 626 800 AT 300 kcmil 3 x 350 kcmil 70.9 x 32.7 x 3300 205 52.8 23.6 42.3500 601 800 AT 300 kcmil 3 x 350 kcmil 512 @ 1.0 PF 1292 1400 AT 400 kcmil 4 x 500 kcmil781 939 1400 a 500 kcmil 90.6 x 32.7 x 4255 207 79,147750 902 1200 a X350 kcmil 4 x 400 kcmil 776 @ 1.0 PF 1935 2000 AT 400 kcmil 6 x 500 kcmilPage Page Industrial Division
Related manuals
Manual 17 pages 22.24 Kb