Details of input contacts for remote access : TN1
Terminals 7 to 8 Remote "Inverter Start" input terminal (IN1)
Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.
Terminals 9 to 10 Remote "Inverter Stop" input terminal (IN2)
Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.
Terminals 11 to 12 "Battery Temp. High" contact input (IN3)
Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery
Terminals 13 to 14 "Power Demand” Command contact input (IN4)
This contact is used to control the input power. Power demand is turned ON when the contact is closed, and power demand is turned OFF when the contact is open. (The Power demand function is custom designed by the factory to match the users specific system specifications. Contact the factory for additional information.)
Terminals 15 to 16 "Remote EPO" contact input
Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.
!The above items are the default settings.
Contact Toshiba International Corporation for setup information.The UPS is equipped with a selectable input contact item.
NOTE
In all cases, a switch having a protective cover is recommended in order to reduce the possibility of accidental operation.
CAUTION
38 | G9000 Installation and Operation Manual |