Toshiba G9000 operation manual DC Unbalanced

Page 89

 

Note 3

 

 

 

 

 

Note 1

 

Note 2

 

 

 

 

 

Code

 

Status message

Meaning

Guidance

Buzzer

 

External

 

 

Failure

 

 

indication

 

 

relay contact

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

 

UF109

DC UNBALANCED

Major unbalance of the neutral point voltage.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF110

ZERO PHASE

Detection of converter zero-sequence

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

overcurrent.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF111

UPS CONTROL

Battery current unbalance.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF112

DC CIRCUIT

Sudden change of the DC voltage level.

CALL SERVICE

Continuousso

 

Major

 

Lit on

 

ABNORMAL

ENGINEER

und

 

 

 

 

 

 

 

 

 

 

 

 

 

UF119

DC GROUND

Detection of DC ground fault UF159 exceeds

CALL SERVICE

Continuous

 

Major

 

Lit on

 

FAULT

10 seconds. UPS transfers to bypass.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL POWER

Power supply voltage to IGBT driver PCB is

CALL SERVICE

Continuous

 

 

 

 

 

 

 

UF128

SUPPLY

 

Major

 

Lit on

 

below the specified level.

ENGINEER

sound

 

 

 

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF151

DC VOLTAGE

24 hours after input power restoration,

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

batteries does not reach float voltage level.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF152

DC VOLTAGE

Unable to equalize the voltage of various

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

batteries after 24 hours.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF154

CB2 ABNORMAL

During UVR, status signal from CB2 is ON.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHG.STOPPED

 

 

Intermittent

 

Minor

 

 

 

 

UF156

(BATTERY

UF157 failure persisted for over 2 hours.

CHECK BATTERY

 

Battery

 

Flicker

 

sound

 

 

 

 

 

OVERTEMP.)

 

 

 

abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY

Detection of overtemperature at the

 

Intermittent

 

Minor

 

 

 

 

UF157

OVERTEMPERATU

CHECK BATTERY

 

Battery

 

Flicker

 

batteries.

sound

 

 

 

 

 

RE

 

 

abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY LIQUID

 

 

Intermittent

 

Minor

 

 

 

 

UF158

Low level of battery electrolyte solution.

CHECK BATTERY

 

Battery

 

Flicker

 

LOW

sound

 

 

 

 

 

 

 

 

abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF159

DC GROUND

Detection of DC ground fault. Chopper

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

FAULT

operation is stopped.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF160

UPS CONTROL

Abnormal behavior of DC current sensor.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF161

CHG.STOPPED(DC

UF151 failure is running for over 24 hours.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

VOLT. ABNORMAL)

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF162

BATTERY

Failure detection based on battery

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

self-check.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY

 

CALL SERVICE

Intermittent

 

 

 

 

 

 

 

UF163

VOLTAGE

Battery voltage is abnormal.

 

Minor

 

Flicker

 

ENGINEER

sound

 

 

 

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VDB SENSOR

Detection of a large variation of the

CALL SERVICE

Intermittent

 

 

 

 

 

 

 

UF170

difference between control-only and

 

Minor

 

Flicker

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

protection-only battery voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF171

UPS CONTROL

Poor shared current in parallel chopper

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

CIRCUIT ERROR

circuit; or improper charging current.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF172

CHG. STOPPED

Energy storage device error.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

(DEVICE STATUS)

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G9000 Installation and Operation Manual

79

Image 89
Contents Document 4GBA0012 Rev. E January Page Document No GBA0012 Rev. E January Page Important Notice Uninterruptible Power SystemPurpose and Scope of Manual Table of Contents List of Tables List of Figures Power wire connections parallel system configuration How to use this Manual Important Safety Instructions Safety Precautions Environment standard UPS Installation EnvironmentCapacity kVA Bypass Voltage Vac Bypass Rating Aac Breaker a General Definitions Operation Overview CB3 Mccb Single Line Diagram Battery Operation Page 1 UPS Parts Location 80,100kVA UPS cabinet Front Inside View UPS cabinet Front ViewUPS Parts Location 300kVA Door Backside Main Cabinet Backside of Left Door 4 UPS Parts Location 500kVA UPS cabinet Front ViewItem 10 Grounding bar is not shown in .4.5. Refer to Figure 12. SW5 13. SW6 Reset switch Button Test switchCN96 CN95 CN94 1 Parallel I/F PCB IFAU-08 80-225kVALCD Touch Panel Monitor Display External I/F PCB IOAU-09 Figure Signal I/F on IOAU-09 boardDescription of Figures 1.4.1-5 to External contact signal terminal block 15 L S/W switch for Service Personnel onlyRefer to Figures 3.7.1 to 3.7.4 for details AC input, AC output, DC input terminal80kVA / 72kW 480V SpecificationsWidth Depth Height Gross Weight Lbs KVA Width Depth Height Net Weight TypicalUPS Lbs Heating KVA Knockout KBTU/hAC Input A Detail of SpecificationsCooling Operating TemperaturePhase I 80-225kVA Phase II 300-750kVA Output Capacity of Equipment Number Application Rating of Contactors, Breakers and FusesOperator Controls and Indicators EPO Button Emergency Power Off button Battery operation Battery OP. orangeLED Display Load on inverter Load on Inverter greenStartup/Shutdown Guidance Figures 2.3.1 to Liquid Crystal DisplayMenu 2 Startup guidance 2 Output values 1 Log menu Fault Indication Input Power FailureMessage Summary Alarm Triggers on fault alarm only External Signal Terminal BlockOUT8 Total Alarm Triggers on any alarm including faults TN2TN1 Battery Breaker PanelTerminals 7 to 8 Battery Operation contact OUT3 Output Contacts for external alarm annunciationTerminals 11 to 12 Battery Low Voltage contact OUT5 Terminals 3 to 4 Load on Bypass contact OUT112 Remote Start Contact Connections Input Contacts for remote access of UPSTerminals 13 to 14 Power Demand Command contact input IN4 Terminals 11 to 12 Battery Temp. High contact input IN3Used to perform a remote UPS Emergency Power Off EPO Terminals 9 to 10 Remote Inverter Stop input terminal IN2RemotEyeII Introduction 13.1 Configuration of the RemotEyeII Overview 80-225kVADPAU-81 Back of the front door Main cabinet RemotEyeIISW1 Cable2 Cable3 Provided PSAU-60SW1 Back of the front left door Main cabinetProvided PSAU-60 PS1 Cable1 Cable1 3BBA0083P001 Male Cable3 12V Power Cable Cable2 Sub 9-pin Cable15 PSAU-60 PCB PS1 Connector Definition Figure Transportation Installation Transportation and InstallationInstallation Procedure Space requirement for routine maintenanceProcedure for Cable Connections External Battery SupplyUPS Capacity DC Voltage KVA Rating Current Permitted aRequired Page Recommended Cable Sizes UPS Terminal Designation Crimp Type Compression LugInput A40,B40,C40 Location of bus bars and terminal blocks Bottom EntryUPS module UPS module 300kVA Detailed Power TerminalsUPS module 500kVA A50, B50, C50 Grounding Bar not shown 18.5UPS module 750kVA AC Output 78.7 A50, B50, C50 Grounding Bar Not shown 19.7BUS BAR Detail TOP View BUS BAR Detail TOP View BUS BAR Connection TOP View Alternate Landing Main Cabinet BUS BAR Connection DC Breaker for Battery Breaker 52Ln *1 AC output CB2 BatteryBypass52S Converter CB1 /Charger Inverter 52C UPS-1 UPS-1 ~~~~~ UPS-1 No.N UPS Use Ethernet STP Shielded Twisted Pair Cable Cat 5 or ~~~~~ Circuit protectors location Operating ProceduresOperation Menu Shut-down ProcedureUPS Bypass Operation ProcedureLCD Screen MMS Operation MMS Start-up ProcedureResponse to UPS Failure UPS Component Parts BatteryReplace battery if its capacity is within this percentage Fault Codes Failure Code List Fault Code CB2 Open DC Unbalanced Overvoltage Engineer Inverter Call Service 52S Abnormal Daily Inspection How to perform daily inspectionPage Variations Consult latest edition of applicableNational and local codes for possible 114 150 AT 3/0 27.6 x 32.8 x 855 136 13,463100 120 150 AT 3/0 94 @ 0.9 PF 235 250 AT Kcmil 300 kcmil151 181 250 AT Kcmil 300 kcmil 35.4 x 32.8 x 1160 144 17,821160 192 250 AT Kcmil 300 kcmil 149 @ 0.9 PF 372 400 AT Kcmil212 255 350 AT Kcmil 2 x 250 kcmil 35.4 x 32.8 x 1230 152 25,060225 271 350 AT Kcmil 2 x 250 kcmil 210 @ 0.9 PF 524 600 AT 300 kcmil 2 x 400 kcmil312 376 500 AT 250 kcmil 2 x 300 kcmil 51.2 x 32.7 x 1230 189 31,659300 361 500 AT 4/0 2 x 250 kcmil 309 @ 1.0 PF 772 800 AT 400 kcmil521 626 800 AT 300 kcmil 3 x 350 kcmil 70.9 x 32.7 x 3300 205 52.8 23.6 42.3500 601 800 AT 300 kcmil 3 x 350 kcmil 512 @ 1.0 PF 1292 1400 AT 400 kcmil 4 x 500 kcmil781 939 1400 a 500 kcmil 90.6 x 32.7 x 4255 207 79,147750 902 1200 a X350 kcmil 4 x 400 kcmil 776 @ 1.0 PF 1935 2000 AT 400 kcmil 6 x 500 kcmilPage Page Industrial Division