Toshiba G9000 operation manual Overvoltage Engineer

Page 90

 

Note 3

 

 

 

 

 

Note 1

 

Note 2

 

 

 

 

 

Code

 

Status message

Meaning

Guidance

Buzzer

 

External

 

 

Failure

 

 

indication

 

 

relay contact

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

 

UF201

INVERTER

Detection of output overvoltage.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERVOLTAGE

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF202

INVERTER

Output voltage dropped.below specs.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

UNDERVOLTAGE

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF203

INVERTER

Detection of inverter overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT CIRCUIT

Detection of a large variation of the reference

CALL SERVICE

Continuous

 

 

 

 

 

 

 

UF204

error signal (current reference and actual

 

Major

 

Lit on

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

current).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF206

UPS CONTROL

Discrepancy between output voltage and

CALL SERVICE

Continuous

 

Major

 

Lit on

 

CIRCUIT ERROR

external voltage (bypass, common ac bus)

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF207

ZERO PHASE

Inverter zero-sequence overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF208

UPS CONTROL

Cross current is abnormal.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF209

52C ABNORMAL

Error to close the contactor 52C.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF210

52C ABNORMAL

Error to open the contactor 52C.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF211

52C ABNORMAL

No answer from contactor 52C during

CALL SERVICE

Continuous

 

Major

 

Lit on

 

inverter operation.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF213

OVERTEMP

Heatsinks temperature exceeds thermal

CALL SERVICE

Continuous

 

Major

 

Lit on

 

settings.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF214

COOLING FAN

Thermal relay activated protection.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF217

INVERTER

Detection of inverter output phase

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERVOLTAGE

overvoltage.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF230

ZERO PHASE

Detection of zero-sequence overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS CONTROL

Discrepancy between output voltage and

CALL SERVICE

Intermittent

 

 

 

 

 

 

 

UF253

inverter voltage, or between output voltage

 

Minor

 

Flicker

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

and bypass voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF256

OUTPUT VOLTAGE

Output voltage is outside of the specified

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

range.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF257

52C ABNORMAL

Contactor 52C failed to open during load

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

transfer from inverter to bypass.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF258

LOAD ABNORMAL

Load transfer due to overload for over 4

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

times within 5 minutes.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF259

ANOTHER UPS

No detection of another UPS voltage signal.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

80

G9000 Installation and Operation Manual

Image 90
Contents Document 4GBA0012 Rev. E January Page Document No GBA0012 Rev. E January Page Uninterruptible Power System Important NoticePurpose and Scope of Manual Table of Contents List of Tables List of Figures Power wire connections parallel system configuration How to use this Manual Important Safety Instructions Safety Precautions UPS Installation Environment Environment standardCapacity kVA Bypass Voltage Vac Bypass Rating Aac Breaker a General Definitions Operation Overview CB3 Mccb Single Line Diagram Battery Operation Page 1 UPS Parts Location 80,100kVA UPS cabinet Front View UPS Parts Location 300kVA Door Backside Main CabinetUPS cabinet Front Inside View 4 UPS Parts Location 500kVA UPS cabinet Front View Backside of Left DoorItem 10 Grounding bar is not shown in .4.5. Refer to Figure Reset switch Button Test switch 12. SW5 13. SW61 Parallel I/F PCB IFAU-08 80-225kVA CN96 CN95 CN94External I/F PCB IOAU-09 Figure Signal I/F on IOAU-09 board Description of Figures 1.4.1-5 toLCD Touch Panel Monitor Display Refer to Figures 3.7.1 to 3.7.4 for details 15 L S/W switch for Service Personnel onlyExternal contact signal terminal block AC input, AC output, DC input terminalSpecifications 80kVA / 72kW 480VUPS Width Depth Height Net Weight TypicalWidth Depth Height Gross Weight Lbs KVA Lbs Heating KVA Knockout KBTU/hA Detail of Specifications AC InputOperating Temperature CoolingPhase I 80-225kVA Phase II 300-750kVA Rating of Contactors, Breakers and Fuses Output Capacity of Equipment Number ApplicationOperator Controls and Indicators LED Display Battery operation Battery OP. orangeEPO Button Emergency Power Off button Load on inverter Load on Inverter greenLiquid Crystal Display MenuStartup/Shutdown Guidance Figures 2.3.1 to 2 Startup guidance 2 Output values 1 Log menu Input Power Failure Fault IndicationMessage OUT8 Total Alarm Triggers on any alarm including faults External Signal Terminal BlockSummary Alarm Triggers on fault alarm only TN2Battery Breaker Panel TN1Terminals 11 to 12 Battery Low Voltage contact OUT5 Output Contacts for external alarm annunciationTerminals 7 to 8 Battery Operation contact OUT3 Terminals 3 to 4 Load on Bypass contact OUT1Input Contacts for remote access of UPS 12 Remote Start Contact ConnectionsUsed to perform a remote UPS Emergency Power Off EPO Terminals 11 to 12 Battery Temp. High contact input IN3Terminals 13 to 14 Power Demand Command contact input IN4 Terminals 9 to 10 Remote Inverter Stop input terminal IN213.1 Configuration of the RemotEyeII Overview 80-225kVA RemotEyeII IntroductionSW1 Cable2 Cable3 Provided Back of the front door Main cabinet RemotEyeIIDPAU-81 PSAU-60Back of the front left door Main cabinet Provided PSAU-60 PS1 Cable1SW1 Male Cable3 12V Power Cable Cable2 Sub 9-pin Cable Cable1 3BBA0083P00115 PSAU-60 PCB PS1 Connector Definition Figure Installation Procedure Transportation and InstallationTransportation Installation Space requirement for routine maintenanceUPS Capacity DC Voltage External Battery SupplyProcedure for Cable Connections KVA Rating Current Permitted aRequired Page Recommended Cable Sizes Crimp Type Compression Lug UPS Terminal DesignationLocation of bus bars and terminal blocks Bottom Entry UPS moduleInput A40,B40,C40 Detailed Power Terminals UPS module 300kVAA50, B50, C50 Grounding Bar not shown 18.5 UPS module 500kVAAC Output 78.7 A50, B50, C50 Grounding Bar Not shown 19.7 UPS module 750kVABUS BAR Detail TOP View BUS BAR Detail TOP View BUS BAR Connection TOP View Alternate Landing Main Cabinet BUS BAR Connection DC Breaker for Battery CB2 Battery Bypass52S Converter CB1 /Charger Inverter 52CBreaker 52Ln *1 AC output UPS-1 UPS-1 ~~~~~ UPS-1 No.N UPS Use Ethernet STP Shielded Twisted Pair Cable Cat 5 or ~~~~~ Operating Procedures Circuit protectors locationShut-down Procedure Operation MenuBypass Operation Procedure UPSMMS Start-up Procedure LCD Screen MMS OperationResponse to UPS Failure Battery Replace battery if its capacity is within this percentageUPS Component Parts Fault Codes Failure Code List Fault Code CB2 Open DC Unbalanced Overvoltage Engineer Inverter Call Service 52S Abnormal How to perform daily inspection Daily InspectionPage Consult latest edition of applicable National and local codes for possibleVariations 100 120 150 AT 3/0 27.6 x 32.8 x 855 136 13,463114 150 AT 3/0 94 @ 0.9 PF 235 250 AT Kcmil 300 kcmil160 192 250 AT Kcmil 300 kcmil 35.4 x 32.8 x 1160 144 17,821151 181 250 AT Kcmil 300 kcmil 149 @ 0.9 PF 372 400 AT Kcmil225 271 350 AT Kcmil 2 x 250 kcmil 35.4 x 32.8 x 1230 152 25,060212 255 350 AT Kcmil 2 x 250 kcmil 210 @ 0.9 PF 524 600 AT 300 kcmil 2 x 400 kcmil300 361 500 AT 4/0 2 x 250 kcmil 51.2 x 32.7 x 1230 189 31,659312 376 500 AT 250 kcmil 2 x 300 kcmil 309 @ 1.0 PF 772 800 AT 400 kcmil500 601 800 AT 300 kcmil 3 x 350 kcmil 70.9 x 32.7 x 3300 205 52.8 23.6 42.3521 626 800 AT 300 kcmil 3 x 350 kcmil 512 @ 1.0 PF 1292 1400 AT 400 kcmil 4 x 500 kcmil750 902 1200 a X350 kcmil 4 x 400 kcmil 90.6 x 32.7 x 4255 207 79,147781 939 1400 a 500 kcmil 776 @ 1.0 PF 1935 2000 AT 400 kcmil 6 x 500 kcmilPage Page Industrial Division