Toshiba G9000 operation manual 52S Abnormal

Page 92

 

Note 3

 

 

 

 

 

Note 1

 

Note 2

 

Code

 

Status message

Meaning

Guidance

Buzzer

 

External

 

 

Failure

 

 

indication

 

 

relay contact

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

 

UF401

52S ABNORMAL

Error to close the contactor 52S.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF402

52S ABNORMAL

Error to open the contactor 52S.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF420

52L OPERATION

Load circuit breaker 52L opened during

CHECK 52L

Continuous

 

Major

 

Lit on

 

ERROR

inverter operation.

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF451

52S ABNORMAL

Contactor 52S failed during load transfer

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

from inverter to bypass.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF452

CB3 ABNORMAL

Contactor CB3 is not working properly.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note 1) 1)

"Major" is defined as major failure. Inverter transferred to the static bypass line;

 

 

 

2)"Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified;

(Note 2) Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent (flicker).

(Note 3) Code indication means:

 

UA+++------------------------

Alarm

UF+++------------------------

Failure

U%0++ -----------------------

Rectifier circuit failure

U%1++ -----------------------

DC circuit failure

U%2++ -----------------------

Inverter circuit failure

U%3++ -----------------------

Control circuit failure

U%4++ -----------------------

Bypass system failure

U%8++ -----------------------

Alarm

U%+00 - U%+49 ---------

Major failure

U%+50 - U%+99 ---------

Minor failure

*)

“+” denotes any numeral from 0 to 9

*)

“%” denotes either “A” or “F”

82

G9000 Installation and Operation Manual

Image 92
Contents Document 4GBA0012 Rev. E January Page Document No GBA0012 Rev. E January Page Uninterruptible Power System Important NoticePurpose and Scope of Manual Table of Contents List of Tables List of Figures Power wire connections parallel system configuration How to use this Manual Important Safety Instructions Safety Precautions UPS Installation Environment Environment standardCapacity kVA Bypass Voltage Vac Bypass Rating Aac Breaker a General Definitions Operation Overview CB3 Mccb Single Line Diagram Battery Operation Page 1 UPS Parts Location 80,100kVA UPS cabinet Front Inside View UPS cabinet Front ViewUPS Parts Location 300kVA Door Backside Main Cabinet 4 UPS Parts Location 500kVA UPS cabinet Front View Backside of Left DoorItem 10 Grounding bar is not shown in .4.5. Refer to Figure Reset switch Button Test switch 12. SW5 13. SW61 Parallel I/F PCB IFAU-08 80-225kVA CN96 CN95 CN94LCD Touch Panel Monitor Display External I/F PCB IOAU-09 Figure Signal I/F on IOAU-09 boardDescription of Figures 1.4.1-5 to 15 L S/W switch for Service Personnel only External contact signal terminal blockRefer to Figures 3.7.1 to 3.7.4 for details AC input, AC output, DC input terminalSpecifications 80kVA / 72kW 480VWidth Depth Height Net Weight Typical Width Depth Height Gross Weight Lbs KVAUPS Lbs Heating KVA Knockout KBTU/hA Detail of Specifications AC InputOperating Temperature CoolingPhase I 80-225kVA Phase II 300-750kVA Rating of Contactors, Breakers and Fuses Output Capacity of Equipment Number ApplicationOperator Controls and Indicators Battery operation Battery OP. orange EPO Button Emergency Power Off buttonLED Display Load on inverter Load on Inverter greenStartup/Shutdown Guidance Figures 2.3.1 to Liquid Crystal DisplayMenu 2 Startup guidance 2 Output values 1 Log menu Input Power Failure Fault IndicationMessage External Signal Terminal Block Summary Alarm Triggers on fault alarm onlyOUT8 Total Alarm Triggers on any alarm including faults TN2Battery Breaker Panel TN1Output Contacts for external alarm annunciation Terminals 7 to 8 Battery Operation contact OUT3Terminals 11 to 12 Battery Low Voltage contact OUT5 Terminals 3 to 4 Load on Bypass contact OUT1Input Contacts for remote access of UPS 12 Remote Start Contact ConnectionsTerminals 11 to 12 Battery Temp. High contact input IN3 Terminals 13 to 14 Power Demand Command contact input IN4Used to perform a remote UPS Emergency Power Off EPO Terminals 9 to 10 Remote Inverter Stop input terminal IN213.1 Configuration of the RemotEyeII Overview 80-225kVA RemotEyeII IntroductionBack of the front door Main cabinet RemotEyeII DPAU-81SW1 Cable2 Cable3 Provided PSAU-60SW1 Back of the front left door Main cabinetProvided PSAU-60 PS1 Cable1 Male Cable3 12V Power Cable Cable2 Sub 9-pin Cable Cable1 3BBA0083P00115 PSAU-60 PCB PS1 Connector Definition Figure Transportation and Installation Transportation InstallationInstallation Procedure Space requirement for routine maintenanceExternal Battery Supply Procedure for Cable ConnectionsUPS Capacity DC Voltage KVA Rating Current Permitted aRequired Page Recommended Cable Sizes Crimp Type Compression Lug UPS Terminal DesignationInput A40,B40,C40 Location of bus bars and terminal blocks Bottom EntryUPS module Detailed Power Terminals UPS module 300kVAA50, B50, C50 Grounding Bar not shown 18.5 UPS module 500kVAAC Output 78.7 A50, B50, C50 Grounding Bar Not shown 19.7 UPS module 750kVABUS BAR Detail TOP View BUS BAR Detail TOP View BUS BAR Connection TOP View Alternate Landing Main Cabinet BUS BAR Connection DC Breaker for Battery Breaker 52Ln *1 AC output CB2 BatteryBypass52S Converter CB1 /Charger Inverter 52C UPS-1 UPS-1 ~~~~~ UPS-1 No.N UPS Use Ethernet STP Shielded Twisted Pair Cable Cat 5 or ~~~~~ Operating Procedures Circuit protectors locationShut-down Procedure Operation MenuBypass Operation Procedure UPSMMS Start-up Procedure LCD Screen MMS OperationResponse to UPS Failure UPS Component Parts BatteryReplace battery if its capacity is within this percentage Fault Codes Failure Code List Fault Code CB2 Open DC Unbalanced Overvoltage Engineer Inverter Call Service 52S Abnormal How to perform daily inspection Daily InspectionPage Variations Consult latest edition of applicableNational and local codes for possible 27.6 x 32.8 x 855 136 13,463 114 150 AT 3/0100 120 150 AT 3/0 94 @ 0.9 PF 235 250 AT Kcmil 300 kcmil35.4 x 32.8 x 1160 144 17,821 151 181 250 AT Kcmil 300 kcmil160 192 250 AT Kcmil 300 kcmil 149 @ 0.9 PF 372 400 AT Kcmil35.4 x 32.8 x 1230 152 25,060 212 255 350 AT Kcmil 2 x 250 kcmil225 271 350 AT Kcmil 2 x 250 kcmil 210 @ 0.9 PF 524 600 AT 300 kcmil 2 x 400 kcmil51.2 x 32.7 x 1230 189 31,659 312 376 500 AT 250 kcmil 2 x 300 kcmil300 361 500 AT 4/0 2 x 250 kcmil 309 @ 1.0 PF 772 800 AT 400 kcmil70.9 x 32.7 x 3300 205 52.8 23.6 42.3 521 626 800 AT 300 kcmil 3 x 350 kcmil500 601 800 AT 300 kcmil 3 x 350 kcmil 512 @ 1.0 PF 1292 1400 AT 400 kcmil 4 x 500 kcmil90.6 x 32.7 x 4255 207 79,147 781 939 1400 a 500 kcmil750 902 1200 a X350 kcmil 4 x 400 kcmil 776 @ 1.0 PF 1935 2000 AT 400 kcmil 6 x 500 kcmilPage Page Industrial Division