Toshiba G9000 operation manual Phase I 80-225kVA Phase II 300-750kVA

Page 34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

no sidecars used.

 

 

Rated Output kVA

 

 

80

 

100

 

 

160

 

 

225

 

 

300

 

500

 

750

 

Enclosure

 

 

 

 

 

 

 

 

 

 

NEMA 1

 

 

 

 

 

 

 

 

Audible Noise

 

 

 

 

 

70 dB @ 1 m

 

 

 

 

 

 

72 dB @ 1 m

 

 

73 dB @ 1 m

 

Listings/Standards

 

 

 

UL 1778; cUL; FCC Class A-Article 47 – Part 15 B;

 

 

 

UL 1778; cUL; IEC 62040-2

Cat. C3;

 

 

 

 

 

 

ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)

 

 

 

ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)

 

Warranty

 

 

 

 

 

 

 

 

3 Years Parts and Labor

 

 

 

 

 

 

Emergency Power Off

 

 

 

 

 

 

 

 

 

 

Included

 

 

 

 

 

 

MONITORING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry Contacts Included

 

 

 

 

 

 

 

 

Yes, for Input and Output Signals

 

 

 

 

RS232 Port

 

 

 

 

 

 

 

 

 

 

Included

 

 

 

 

 

 

Intelligent Monitoring

 

 

 

 

 

SNMP; MODBus RTU; MODBus TCP; BACNET; METASYS

 

 

 

 

(Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

LCD Touch Panel for Local Monitoring, Operation, and Control

 

 

 

 

TABLE 1.5.b Typical UPS Efficiencies at Various Loads

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

% Full Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20%

 

40%

60%

 

 

80%

 

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 kVA

 

92.5%

 

94.3%

95.0%

 

95.2%

 

 

95.8%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 kVA

 

92.5%

 

94.3%

95.0%

 

95.2%

 

 

95.8%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160 kVA

 

94.7%

 

95.7%

96.2%

 

96.5%

 

 

96.5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225 kVA

 

94.9%

 

96.2%

96.5%

 

96.5%

 

 

96.5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300 kVA

 

94.4%

 

96.3%

96.9%

 

97.0%

 

 

97.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500 kVA

 

94.8%

 

96.7%

97.0%

 

97.0%

 

 

97.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750 kVA

 

95.5%

 

96.6%

97.0%

 

97.0%

 

 

97.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 1.5.c MTBF and MTTR

Parameter

Phase I – 80-225kVA

Phase II – 300-750kVA

 

 

 

MTBF (Mean Time Between Failures): System (With Bypass)

3,081,946 hr.

2,633,910 hr.

Inverter (Without Bypass)

140,406 hr.

101,687 hr.

MTTR (Mean Time to Repair) – Excluding Travel and Shipping Time)

4 hr.

1.5 hr.

 

 

 

24

G9000 Installation and Operation Manual

Image 34
Contents Document 4GBA0012 Rev. E January Page Document No GBA0012 Rev. E January Page Uninterruptible Power System Important NoticePurpose and Scope of Manual Table of Contents List of Tables List of Figures Power wire connections parallel system configuration How to use this Manual Important Safety Instructions Safety Precautions UPS Installation Environment Environment standardCapacity kVA Bypass Voltage Vac Bypass Rating Aac Breaker a General Definitions Operation Overview CB3 Mccb Single Line Diagram Battery Operation Page 1 UPS Parts Location 80,100kVA UPS Parts Location 300kVA Door Backside Main Cabinet UPS cabinet Front ViewUPS cabinet Front Inside View 4 UPS Parts Location 500kVA UPS cabinet Front View Backside of Left DoorItem 10 Grounding bar is not shown in .4.5. Refer to Figure Reset switch Button Test switch 12. SW5 13. SW61 Parallel I/F PCB IFAU-08 80-225kVA CN96 CN95 CN94Description of Figures 1.4.1-5 to External I/F PCB IOAU-09 Figure Signal I/F on IOAU-09 boardLCD Touch Panel Monitor Display Refer to Figures 3.7.1 to 3.7.4 for details 15 L S/W switch for Service Personnel onlyExternal contact signal terminal block AC input, AC output, DC input terminalSpecifications 80kVA / 72kW 480VUPS Width Depth Height Net Weight TypicalWidth Depth Height Gross Weight Lbs KVA Lbs Heating KVA Knockout KBTU/hA Detail of Specifications AC InputOperating Temperature CoolingPhase I 80-225kVA Phase II 300-750kVA Rating of Contactors, Breakers and Fuses Output Capacity of Equipment Number ApplicationOperator Controls and Indicators LED Display Battery operation Battery OP. orangeEPO Button Emergency Power Off button Load on inverter Load on Inverter greenMenu Liquid Crystal DisplayStartup/Shutdown Guidance Figures 2.3.1 to 2 Startup guidance 2 Output values 1 Log menu Input Power Failure Fault IndicationMessage OUT8 Total Alarm Triggers on any alarm including faults External Signal Terminal BlockSummary Alarm Triggers on fault alarm only TN2Battery Breaker Panel TN1Terminals 11 to 12 Battery Low Voltage contact OUT5 Output Contacts for external alarm annunciationTerminals 7 to 8 Battery Operation contact OUT3 Terminals 3 to 4 Load on Bypass contact OUT1Input Contacts for remote access of UPS 12 Remote Start Contact ConnectionsUsed to perform a remote UPS Emergency Power Off EPO Terminals 11 to 12 Battery Temp. High contact input IN3Terminals 13 to 14 Power Demand Command contact input IN4 Terminals 9 to 10 Remote Inverter Stop input terminal IN213.1 Configuration of the RemotEyeII Overview 80-225kVA RemotEyeII IntroductionSW1 Cable2 Cable3 Provided Back of the front door Main cabinet RemotEyeIIDPAU-81 PSAU-60Provided PSAU-60 PS1 Cable1 Back of the front left door Main cabinetSW1 Male Cable3 12V Power Cable Cable2 Sub 9-pin Cable Cable1 3BBA0083P00115 PSAU-60 PCB PS1 Connector Definition Figure Installation Procedure Transportation and InstallationTransportation Installation Space requirement for routine maintenanceUPS Capacity DC Voltage External Battery SupplyProcedure for Cable Connections KVA Rating Current Permitted aRequired Page Recommended Cable Sizes Crimp Type Compression Lug UPS Terminal DesignationUPS module Location of bus bars and terminal blocks Bottom EntryInput A40,B40,C40 Detailed Power Terminals UPS module 300kVAA50, B50, C50 Grounding Bar not shown 18.5 UPS module 500kVAAC Output 78.7 A50, B50, C50 Grounding Bar Not shown 19.7 UPS module 750kVABUS BAR Detail TOP View BUS BAR Detail TOP View BUS BAR Connection TOP View Alternate Landing Main Cabinet BUS BAR Connection DC Breaker for Battery Bypass52S Converter CB1 /Charger Inverter 52C CB2 BatteryBreaker 52Ln *1 AC output UPS-1 UPS-1 ~~~~~ UPS-1 No.N UPS Use Ethernet STP Shielded Twisted Pair Cable Cat 5 or ~~~~~ Operating Procedures Circuit protectors locationShut-down Procedure Operation MenuBypass Operation Procedure UPSMMS Start-up Procedure LCD Screen MMS OperationResponse to UPS Failure Replace battery if its capacity is within this percentage BatteryUPS Component Parts Fault Codes Failure Code List Fault Code CB2 Open DC Unbalanced Overvoltage Engineer Inverter Call Service 52S Abnormal How to perform daily inspection Daily InspectionPage National and local codes for possible Consult latest edition of applicableVariations 100 120 150 AT 3/0 27.6 x 32.8 x 855 136 13,463114 150 AT 3/0 94 @ 0.9 PF 235 250 AT Kcmil 300 kcmil160 192 250 AT Kcmil 300 kcmil 35.4 x 32.8 x 1160 144 17,821151 181 250 AT Kcmil 300 kcmil 149 @ 0.9 PF 372 400 AT Kcmil225 271 350 AT Kcmil 2 x 250 kcmil 35.4 x 32.8 x 1230 152 25,060212 255 350 AT Kcmil 2 x 250 kcmil 210 @ 0.9 PF 524 600 AT 300 kcmil 2 x 400 kcmil300 361 500 AT 4/0 2 x 250 kcmil 51.2 x 32.7 x 1230 189 31,659312 376 500 AT 250 kcmil 2 x 300 kcmil 309 @ 1.0 PF 772 800 AT 400 kcmil500 601 800 AT 300 kcmil 3 x 350 kcmil 70.9 x 32.7 x 3300 205 52.8 23.6 42.3521 626 800 AT 300 kcmil 3 x 350 kcmil 512 @ 1.0 PF 1292 1400 AT 400 kcmil 4 x 500 kcmil750 902 1200 a X350 kcmil 4 x 400 kcmil 90.6 x 32.7 x 4255 207 79,147781 939 1400 a 500 kcmil 776 @ 1.0 PF 1935 2000 AT 400 kcmil 6 x 500 kcmilPage Page Industrial Division