Toshiba 1000 user manual Important Safety Instructions

Page 14

Important Safety Instructions

This manual contains important instructions that should be followed during the installation, maintenance, and operation of the UPS and its batteries to assure safe and proper operation.

SAVE THESE INSTRUCTIONS

Disconnect device in the building installation wiring.

Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.

CAUTION - To reduce the risk of fire, the input of the unit is connected only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70

CAUTION - Disconnect switch for each ungrounded conductor of ac output shall be provided by others. To reduce the risk of fire, the output of the unit is connected in series with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.

• CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY

AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.

1.Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment or when performing maintenance.

2.Hardwire type UPS units are not equipped with an over-current protection device, nor do they have an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input.

3.The maximum ambient operating temperature is 40° C (104° F).

4.Battery servicing should be performed by a qualified Toshiba Representative only.

5.Unauthorized personnel should not service batteries.

XIII

Image 14
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII ICES-003 EMC StatementsFCC Part Declaration of Conformity Request General Safety Instructions Safety Alert Symbol / Signal WordsPage Special Symbols Important Safety Instructions Qualified Personnel only Qualified Personnel shallPage XVI Instructions Importantes Concernant LA Sécurité Conserver CES InstructionsInspection/Storage/Disposal Storage Maintenance DisposalInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv Introduction System DescriptionGeneral Description Efficiency Optimizer Function Auto-Restart Free Run ModeDiagnostic Tests System Configuration Storage ShippingPage UPS Frequency Converter Option InstallationEnvironment Rear Panel Views 1000VA 1500VA Tower Rear Panel 2000VA 3000VA Tower Rear Panel2400VA Tower Rear Panel 2400VA Power Wiring Options X1-N or N-X3 120V Half Load1000 1500 VA Rack mount 2U Rear Panel 2000 3000 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel Example of Installation of Plug & Play products 2400 VA6000 VA Front Panel Settings HE Mode SET ON/OFFOutlet GROUP1/GROUP2 Computer and Alarm Connections RS-232 Standard Interface PortDB9 Male Connector Outline Facing connector Dry Contact Interface optional cardNetwork Transient Protector EPO Port emergency power offUSB Port Load SegmentsShutting Down the UPS User’s Guide to OperationsUPS Startup and Shutdown Starting the UPS Button OperationControl Panel Functions Control panels 1000/1500/2000/3000VA Normal DisplayLCD Message Description UPS ConfigurationsUPS Meters Display Page UPS Manual Test Audible AlarmsSilencing an Alarm Interpreting UPS MessagesTroubleshooting Alarm Description What You Should DoMaintenance Battery ServicingTechnical Specifications Power Range 1000-3000 VA 120Power Range 2400 VA 208/240 Power Range 6000 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 GeneralEnvironment Power Range 1000-3000 VA 230 RKB2Backup Time at Partial Loads Warranty Information Uninterruptible Power SystemLimitations and Exclusions Modifications