Toshiba 1000 user manual Environment

Page 57

Battery

Acceptable manufacturer

Yuasa Taiwan only

 

Type / Rating

9AH/12V Valve Regulated Lead Acid, Flame Retardant

 

Back-up Time at Full Load (at 25

7 minutes

 

degree C) (min)

 

 

 

Battery Bus Voltage (VDC)

240

 

Number of Batteries

20

 

Recharge

4 hours to 90% for all ratings

 

Battery Mode Voltage Regulation

±3% RMS for entire battery voltage range and 0 to 100% load

 

Battery Leakage

100 mA maximum

 

Battery Test

Automatic and Manual

 

Replaceable Batteries

Not Hot-Swappable

 

Battery Protection

Fuse

 

Pre-alarm Level

2 minutes

 

Battery Level @ Shutdown

1.67 VPC, ± 3% of battery voltage at FL with level automatically

 

raised for lighter loading

 

 

 

Overcharge Protection

2.50 VPC, ± 3% of battery voltage

 

 

Maintains proper float voltage per battery specification over a

 

Temperature Compensated Charger

temperature range of 10 to 40 degree C (2.3V/cell at 25 degree C

 

with a temperature coefficient of minus 5 millivolts per degree

 

 

 

 

C)

 

Voltage Level

2.25 minimum, 2.275 nominal, 2.30V maximum voltage of

 

battery voltage

 

 

 

Protection against Batteries Deep

 

 

Discharge

 

Environment

Operating Temperature

0 - 40oC (32 - 104oF)

 

Storage Temperature

-20 - 40oC (-4 - 104oF)

 

Operating Humidity

30-90% (No Condensation)

 

Altitude

11500 ft (3500 m) above sea level

 

Acoustical Noise

50dB(A) maximum at 1 meter from Front Panel

 

Heat Generation (BTU/Hour)

2234BTU/Hour

Mechanical

Dimensions (Rackmount) LxWxH

16.8 in. x23.5 in. x10.5 in. (427 mm x 597mm x 267mm)

 

Weight (Rackmount)

148lbs (67.1 kg)

 

Line Cord

Terminal Block with L6-30P (option to remove the L6-30P)

 

Receptacles

(2) L6-30R

 

Enclosure

Enclosure of unit made from sheet metal meets NEMA 1 and UL

 

Type 1 Standard

 

 

 

Paint System

Black Color

 

Front Panel

1000 Series Panel

 

Connectors/Options

EPO

 

 

Battery Connectors

 

 

Option card Slot (Network and Dry Contact)

 

Buzzer Volume

Mute/Unmute

Warranty

 

Three years on electronics

 

 

Two years full replacement on battery (See Toshiba warranty

 

 

policy for full details.)

Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user

to select a fixed output frequency and simultaneously disables the bypass mode. Standards – FCC Part 15 Class A (2-3kVA), UL 1778, ICES-0003

Safety – EN 62040-1, Emissions: EN 62040-2, Immunity: EN 62040-2 Category C2

32

Image 57
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII EMC Statements FCC PartICES-003 Declaration of Conformity Request Safety Alert Symbol / Signal Words General Safety InstructionsPage Special Symbols Important Safety Instructions Qualified Personnel shall Qualified Personnel onlyPage XVI LA Sécurité Conserver CES Instructions Instructions Importantes ConcernantInspection/Storage/Disposal Disposal Storage MaintenanceInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv System Description IntroductionGeneral Description Efficiency Optimizer Function Free Run Mode Diagnostic TestsAuto-Restart System Configuration Shipping StoragePage Installation EnvironmentUPS Frequency Converter Option 2000VA 3000VA Tower Rear Panel Rear Panel Views 1000VA 1500VA Tower Rear Panel2400VA Tower Rear Panel X1-N or N-X3 120V Half Load 2400VA Power Wiring Options2000 3000 VA Rack mount 2U Rear Panel 1000 1500 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel 2400 VA Example of Installation of Plug & Play products6000 VA HE Mode SET ON/OFF Front Panel SettingsOutlet GROUP1/GROUP2 RS-232 Standard Interface Port Computer and Alarm ConnectionsDry Contact Interface optional card DB9 Male Connector Outline Facing connectorUSB Port EPO Port emergency power offNetwork Transient Protector Load SegmentsUPS Startup and Shutdown Starting the UPS User’s Guide to OperationsShutting Down the UPS Button OperationControl Panel Functions Normal Display Control panels 1000/1500/2000/3000VAUPS Configurations UPS Meters DisplayLCD Message Description Page Silencing an Alarm Audible AlarmsUPS Manual Test Interpreting UPS MessagesAlarm Description What You Should Do TroubleshootingBattery Servicing MaintenancePower Range 1000-3000 VA 120 Technical SpecificationsPower Range 2400 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 General Power Range 6000 VA 208/240Environment RKB2 Power Range 1000-3000 VA 230Backup Time at Partial Loads Uninterruptible Power System Warranty InformationLimitations and Exclusions Modifications
Related manuals