Inspection/Storage/Disposal

CAUTION

Inspection

Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material.

Uncrating

Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping.

Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.

Storage

During periods of non-use, the following guidelines are recommended for storage.

Storage Preparation

1.Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.

2.Stop the unit.

3.Disable the COLD START function prior to storing the unit by following the instructions in section 4. Shipping, page 6.

4.Ensure the MCCB switch is in the Off position.

Storing Conditions

For best results, store the UPS in the original shipping container and place on a wood or metal pallet.

Storage temperature — -4 – 104 °F (-20 – 40 °C).

XVIII

Image 19
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII FCC Part EMC StatementsICES-003 Declaration of Conformity Request Safety Alert Symbol / Signal Words General Safety InstructionsPage Special Symbols Important Safety Instructions Qualified Personnel shall Qualified Personnel onlyPage XVI LA Sécurité Conserver CES Instructions Instructions Importantes ConcernantInspection/Storage/Disposal Disposal Storage MaintenanceInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv System Description IntroductionGeneral Description Efficiency Optimizer Function Diagnostic Tests Free Run ModeAuto-Restart System Configuration Shipping StoragePage Environment InstallationUPS Frequency Converter Option 2000VA 3000VA Tower Rear Panel Rear Panel Views 1000VA 1500VA Tower Rear Panel2400VA Tower Rear Panel X1-N or N-X3 120V Half Load 2400VA Power Wiring Options2000 3000 VA Rack mount 2U Rear Panel 1000 1500 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel 2400 VA Example of Installation of Plug & Play products6000 VA HE Mode SET ON/OFF Front Panel SettingsOutlet GROUP1/GROUP2 RS-232 Standard Interface Port Computer and Alarm ConnectionsDry Contact Interface optional card DB9 Male Connector Outline Facing connectorLoad Segments EPO Port emergency power offUSB Port Network Transient ProtectorButton Operation User’s Guide to OperationsUPS Startup and Shutdown Starting the UPS Shutting Down the UPSControl Panel Functions Normal Display Control panels 1000/1500/2000/3000VAUPS Meters Display UPS ConfigurationsLCD Message Description Page Interpreting UPS Messages Audible AlarmsSilencing an Alarm UPS Manual TestAlarm Description What You Should Do TroubleshootingBattery Servicing MaintenancePower Range 1000-3000 VA 120 Technical SpecificationsPower Range 2400 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 General Power Range 6000 VA 208/240Environment RKB2 Power Range 1000-3000 VA 230Backup Time at Partial Loads Uninterruptible Power System Warranty InformationLimitations and Exclusions Modifications