Toshiba 1000 user manual Installation, Environment, UPS Frequency Converter Option

Page 33

5. Installation

5.1Environment

To ensure safe and proper operation, ensure that the installation conforms to the following specifications.

NOTE: Remove the protective plastic adhesive shipping cover over the Off-On button before turning the UPS On.

Ensure that the installation location is consistent with the following:

Avoid extreme temperature and humidity. Maximal battery life can be attained with a recommended temperature range of 15 °C to 25 °C.

Protect the equipment from moisture.

Space and ventilation requirements must be met. Ensure there is at least 100mm (4 inch) behind and 50mm (2 inch) on the sides of the UPS for ventilation.

Ensure that the front of the UPS remains clear for user access.

The External Battery Cabinets must be installed next to or underneath the UPS.

5.2UPS Frequency Converter Option

The UPS has an optional software upgrade that allows it to serve as a frequency converter. Installing this software allows the user to set the UPS output to 50 or 60 Hz regardless of the input frequency.

This option can be downloaded from the Toshiba website, www.toshiba.com/ind. Follow the home page menu path to: UPS>> Options/Accessories>> 1000 series>> Software>> Frequency Conversion.

**Note: Installing the frequency converter software upgrade will disable the bypass function. (This insures that in the event of power loss you are not trying to, for example, run a 50 Hz load with 60 Hz commercial power.)

8

Image 33
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII EMC Statements FCC PartICES-003 Declaration of Conformity Request Safety Alert Symbol / Signal Words General Safety InstructionsPage Special Symbols Important Safety Instructions Qualified Personnel shall Qualified Personnel onlyPage XVI LA Sécurité Conserver CES Instructions Instructions Importantes ConcernantInspection/Storage/Disposal Disposal Storage MaintenanceInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv System Description IntroductionGeneral Description Efficiency Optimizer Function Free Run Mode Diagnostic TestsAuto-Restart System Configuration Shipping StoragePage Installation EnvironmentUPS Frequency Converter Option 2000VA 3000VA Tower Rear Panel Rear Panel Views 1000VA 1500VA Tower Rear Panel2400VA Tower Rear Panel X1-N or N-X3 120V Half Load 2400VA Power Wiring Options2000 3000 VA Rack mount 2U Rear Panel 1000 1500 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel 2400 VA Example of Installation of Plug & Play products6000 VA HE Mode SET ON/OFF Front Panel SettingsOutlet GROUP1/GROUP2 RS-232 Standard Interface Port Computer and Alarm ConnectionsDry Contact Interface optional card DB9 Male Connector Outline Facing connectorUSB Port EPO Port emergency power offNetwork Transient Protector Load SegmentsUPS Startup and Shutdown Starting the UPS User’s Guide to OperationsShutting Down the UPS Button OperationControl Panel Functions Normal Display Control panels 1000/1500/2000/3000VAUPS Configurations UPS Meters DisplayLCD Message Description Page Silencing an Alarm Audible AlarmsUPS Manual Test Interpreting UPS MessagesAlarm Description What You Should Do TroubleshootingBattery Servicing MaintenancePower Range 1000-3000 VA 120 Technical SpecificationsPower Range 2400 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 General Power Range 6000 VA 208/240Environment RKB2 Power Range 1000-3000 VA 230Backup Time at Partial Loads Uninterruptible Power System Warranty InformationLimitations and Exclusions Modifications