Toshiba user manual Power Range 1000-3000 VA 230, RKB2

Page 58

9.4Power Range 1000-3000 VA (230 V)

Tower

International

UT1E1E010C6

UT1E1E015C6

 

UT1E1E020C6

UT1E1E030C6

 

230V Model

 

 

 

 

 

Rack-

International

UT1E1E010C6

UT1E1E015C6

 

UT1E1E020C6

UT1E1E030C6RKB

mount (2U)

230V Model

RKB2

RKB2

 

RKB2

2

Input

Voltage

 

230 VAC

(161 – 276 V)

 

 

(International)

 

 

 

 

 

 

Voltage Range

 

+20% to -30%

 

 

(International)

 

 

 

 

 

 

Frequency

 

50 / 60 Hz auto sensing

 

 

Power Factor

 

Greater than 0.97

 

 

Topology

True on-line, Double conversion Input PF correction

Output

Voltage

 

 

230 VAC

 

 

(International)

 

 

 

 

 

 

Capacity (VA)

1000 VA

1500 VA

 

2000 VA

3000 VA

 

Capacity (W)

700 W

1050 W

 

1400 W

2100 W

 

Frequency

 

50 / 60 Hz auto

sensing*

 

 

Wave Form

 

Sine wave, zero transfer time

 

 

Load Power

 

 

0.7

 

 

Factor

 

 

 

 

 

 

Efficiency

 

Greater than 86%

Greater than 85%

 

AC/DC/AC

 

 

 

 

 

 

Rated Current

4.3 A

6.5 A

 

13 A

13 A

 

(International)

 

 

 

 

 

 

Overload

125%

for 1 min., 150% for

10 sec.

125% for 1 min.,

 

Capacity

 

 

 

 

130% for 10 sec.

 

Crest Factor

 

3.0 at full load

 

 

2.5 at full load

Battery

DC Voltage

36 V / 12 V

 

72V

/ 12 V

 

(Tower & 2U)

9 AH x 3

 

9 AH x 6

 

Backup Time

7 min

6 min

 

5 min

5 min

 

(Tower & 2U)

(full load)

(full load)

 

(full load)

(full load)

 

Interface

RS-232 and USB standard

RemotEye II® and

EMD option

Physical

Dimensions

16.5”L x 6.0”W x 9.4”H

 

16.7" L x 8.9" W

16.7" L x 8.9" W x

 

(Tower)

 

 

 

x 14.2" H

14.2" H

 

Dimensions

16.7”L x 16.9”W x 3.5”H

 

25.0"L x 16.9"W

25.0"L x 16.9"W x

 

(2U)

 

 

 

x 3.5"H"

3.5"H"

 

Weight

35.6 lbs /

37.4 lbs /

 

68.4 lbs /

72.6 lbs / 71.5 lbs

 

(Tower/2U)

37.6 lbs

37.6 lbs

 

69.5 lbs

 

 

Line Cord

 

 

IEC 320

 

 

(International)

 

 

 

 

 

 

Receptacles

IEC 320 (4 / 4)

IEC 320 (8 / 4)

IEC 320 (8 / 4)

 

(Tower/2U)

 

 

 

 

 

 

International

 

 

 

 

 

Environ-

Operating

 

32 – 104°F (0 – 40°C)

 

ment

Temperature

 

 

 

 

 

 

Altitude

 

11,500 ft (3500 m) above sea level

 

Warranty

 

Three years on electronics

 

 

 

 

 

Two years full replacement on battery (See Toshiba warranty policy for full details.)

 

 

 

 

 

 

 

Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user to select a fixed output frequency and simultaneously disables the bypass mode.

Standards - Safety: EN 62040-1, Emissions: EN 62040-2, Immunity: EN 62040-2 Category C1 (1000-2000VA), EN 62040-2 Category C2 (2000-3000VA

33

Image 58
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII FCC Part EMC StatementsICES-003 Declaration of Conformity Request General Safety Instructions Safety Alert Symbol / Signal WordsPage Special Symbols Important Safety Instructions Qualified Personnel only Qualified Personnel shallPage XVI Instructions Importantes Concernant LA Sécurité Conserver CES InstructionsInspection/Storage/Disposal Storage Maintenance DisposalInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv Introduction System DescriptionGeneral Description Efficiency Optimizer Function Diagnostic Tests Free Run ModeAuto-Restart System Configuration Storage ShippingPage Environment InstallationUPS Frequency Converter Option Rear Panel Views 1000VA 1500VA Tower Rear Panel 2000VA 3000VA Tower Rear Panel2400VA Tower Rear Panel 2400VA Power Wiring Options X1-N or N-X3 120V Half Load1000 1500 VA Rack mount 2U Rear Panel 2000 3000 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel Example of Installation of Plug & Play products 2400 VA6000 VA Front Panel Settings HE Mode SET ON/OFFOutlet GROUP1/GROUP2 Computer and Alarm Connections RS-232 Standard Interface PortDB9 Male Connector Outline Facing connector Dry Contact Interface optional cardNetwork Transient Protector EPO Port emergency power offUSB Port Load SegmentsShutting Down the UPS User’s Guide to OperationsUPS Startup and Shutdown Starting the UPS Button OperationControl Panel Functions Control panels 1000/1500/2000/3000VA Normal DisplayUPS Meters Display UPS ConfigurationsLCD Message Description Page UPS Manual Test Audible AlarmsSilencing an Alarm Interpreting UPS MessagesTroubleshooting Alarm Description What You Should DoMaintenance Battery ServicingTechnical Specifications Power Range 1000-3000 VA 120Power Range 2400 VA 208/240 Power Range 6000 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 GeneralEnvironment Power Range 1000-3000 VA 230 RKB2Backup Time at Partial Loads Warranty Information Uninterruptible Power SystemLimitations and Exclusions Modifications