5.5Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
Settings | Options | Default | Remarks |
1) O/P VOLT SET | 100/110/115/120/127 | 120 V | 120 V (FOR LV series) |
(output voltage | 208/220/230/240 Vac | 230 V | 230 V (FOR HV series) |
set) |
|
|
|
|
|
|
|
2) I/P FREQ SET | +/- 2% | +/- 5% | Input Frequency range in |
(input frequency | +/- 5% |
| Free Run mode |
setting) | +/- 7% |
|
|
3) I/P BYPASS | +/- 10% | +10% | Input Voltage range when |
SET | +10% | Bypass mode is on | |
(input bypass | +15% |
|
|
setting) |
|
|
|
4) FREE RUN | ON/OFF | ON | If ON, enable UPS runs on |
SET |
|
| Asynchronous mode. |
|
|
| For example: |
|
|
| If input freq 55Hz |
|
|
| output freq stays at 60Hz. |
|
|
| If OFF, disable UPS runs on |
|
|
| synchronous mode. |
|
|
| For example: |
|
|
| If input freq 55Hz, |
|
|
| UPS will go to battery mode. |
5) HE MODE SET | ON/OFF | OFF | If ON, enable UPS runs in |
|
|
| High efficiency mode. The |
|
|
| unit will be in bypass mode |
|
|
| with 95% or higher |
|
|
| efficiency. |
|
|
| If OFF, the unit will be in the |
|
|
| online mode with 85% |
|
|
| efficiency. |
6) MANUAL | ON/OFF | OFF | If ON, enable UPS switch to |
BYPASS |
|
| Bypass mode immediately. |
|
|
|
|
16