Toshiba 1000 user manual Power Range 6000 VA 208/240

Page 56

9.3Power Range 6000 VA (208/240 V)

 

1000 Series 6kVA Specification

 

 

Specification

Rackmount

US 208/240V

 

UT1G1G060C6RKB3 + UT1-BR-0607

General

Topology

 

True on-line, Double conversion, IGBT Power Factor Correction

 

Input

 

 

 

 

Certifications

 

CE

Input

Voltage (V)

 

Single Phase - 208/240Vin

 

Capacity (VA)

 

6kVA

 

Frequency

 

45-65 Hz auto sensing

 

Frequency Synchronization

 

± 3Hz

 

Power Factor

 

Greater than 0.97

 

Current THD

 

Less than 15%

 

Cold Start (0 to 100% load)

 

Default Output Frequency 60 Hz

 

Earth leakage (max.)

 

2mA (UPS only)

Bypass

Voltage (V)

 

+10/-15% of nominal (default)

 

 

 

+10/-10% of nominal

 

 

 

+15/-20% of nominal

 

 

 

Set by display panel

Output

Voltage

 

208V or 240V

 

Voltage Regulations

 

± 3%

 

Capacity (W)

 

4.2kW

 

Frequency

 

50 / 60 Hz auto sensing

 

Battery Mode/Free Run Mode

 

± 0.25 Hz

 

Wave Form

 

Sine wave, zero transfer time

 

Load Power Factor

 

0.7 PF

 

Efficiency AC/DC/AC

 

Greater than 89% at Nominal Voltage

 

High Efficiency Mode Efficiency

 

Greater than 92%

 

Rated Current (based on 240V)

 

25.0

 

Inverter Overload Capacity

 

125% for 1 min, 150% for 10 sec

 

Crest Factor

 

3.0 at full load

 

Voltage Transient Response

 

0%100%0%; ± 15 % max.

 

(battery mode with R type load)

 

20%100%20%; ± 9 % max.

 

Voltage Transient Recovery (R

 

Return to nominal voltage within 30 ms

 

type Load)

 

 

 

 

 

On-line Transfer Time – Inverter to

 

Less than 4m sec

 

Bypass and Bypass to Inverter

 

 

 

 

 

High Efficiency Transfer Time –

 

 

 

Inverter to Bypass and Bypass to

 

Less than 4m sec transfer time

 

Inverter

 

 

 

Short Circuit Protection

 

Electronic overload and short circuit.

 

Voltage Total Harmonic Distortion

 

Less than 3 % THD

 

(Full Linear Load)

 

 

 

 

 

Voltage Total Harmonic Distortion

 

Less than 5 % THD

 

(Full Non-Linear Load)

 

 

 

 

 

Steady State Output Voltage

 

No-load to Full-load +/- 2% at full battery.

 

Regulation

 

 

 

 

 

Common Mode Noise

 

less than 0.5Vrms

 

Leakage Current

 

.5mA

 

Surge Protection

 

MOV 260 Jules on Output

 

 

31

Image 56
Contents 1000 &1000+ Series Important Notice Uninterruptible Power System Table of Contents Limitations and Exclusions Manual’s Purpose and Scope Page VII ICES-003 EMC StatementsFCC Part Declaration of Conformity Request General Safety Instructions Safety Alert Symbol / Signal WordsPage Special Symbols Important Safety Instructions Qualified Personnel only Qualified Personnel shallPage XVI Instructions Importantes Concernant LA Sécurité Conserver CES InstructionsInspection/Storage/Disposal Storage Maintenance DisposalInstallation Precautions Conductor Routing and Grounding Operating Precautions Maintenance Note Xxiv Introduction System DescriptionGeneral Description Efficiency Optimizer Function Auto-Restart Free Run ModeDiagnostic Tests System Configuration Storage ShippingPage UPS Frequency Converter Option InstallationEnvironment Rear Panel Views 1000VA 1500VA Tower Rear Panel 2000VA 3000VA Tower Rear Panel2400VA Tower Rear Panel 2400VA Power Wiring Options X1-N or N-X3 120V Half Load1000 1500 VA Rack mount 2U Rear Panel 2000 3000 VA Rack mount 2U Rear PanelVA Rack mount UPS 3U, Battery Pack 3U Rear Panel Example of Installation of Plug & Play products 2400 VA6000 VA Front Panel Settings HE Mode SET ON/OFFOutlet GROUP1/GROUP2 Computer and Alarm Connections RS-232 Standard Interface PortDB9 Male Connector Outline Facing connector Dry Contact Interface optional cardEPO Port emergency power off USB PortNetwork Transient Protector Load SegmentsUser’s Guide to Operations UPS Startup and Shutdown Starting the UPSShutting Down the UPS Button OperationControl Panel Functions Control panels 1000/1500/2000/3000VA Normal DisplayLCD Message Description UPS ConfigurationsUPS Meters Display Page Audible Alarms Silencing an AlarmUPS Manual Test Interpreting UPS MessagesTroubleshooting Alarm Description What You Should DoMaintenance Battery ServicingTechnical Specifications Power Range 1000-3000 VA 120Power Range 2400 VA 208/240 Power Range 6000 VA 208/240 Rackmount US 208/240V UT1G1G060C6RKB3 + UT1-BR-0607 GeneralEnvironment Power Range 1000-3000 VA 230 RKB2Backup Time at Partial Loads Warranty Information Uninterruptible Power SystemLimitations and Exclusions Modifications
Related manuals