9.3Power Range 6000 VA (208/240 V)
| 1000 Series 6kVA Specification | ||
|
| Specification | |
Rackmount | US 208/240V |
| UT1G1G060C6RKB3 + |
General | Topology |
| True |
| Input | ||
|
|
| |
| Certifications |
| CE |
Input | Voltage (V) |
| Single Phase - 208/240Vin |
| Capacity (VA) |
| 6kVA |
| Frequency |
| |
| Frequency Synchronization |
| ± 3Hz |
| Power Factor |
| Greater than 0.97 |
| Current THD |
| Less than 15% |
| Cold Start (0 to 100% load) |
| Default Output Frequency 60 Hz |
| Earth leakage (max.) |
| 2mA (UPS only) |
Bypass | Voltage (V) |
| |
|
|
| |
|
|
| |
|
|
| Set by display panel |
Output | Voltage |
| 208V or 240V |
| Voltage Regulations |
| ± 3% |
| Capacity (W) |
| 4.2kW |
| Frequency |
| 50 / 60 Hz auto sensing |
| Battery Mode/Free Run Mode |
| ± 0.25 Hz |
| Wave Form |
| Sine wave, zero transfer time |
| Load Power Factor |
| 0.7 PF |
| Efficiency AC/DC/AC |
| Greater than 89% at Nominal Voltage |
| High Efficiency Mode Efficiency |
| Greater than 92% |
| Rated Current (based on 240V) |
| 25.0 |
| Inverter Overload Capacity |
| 125% for 1 min, 150% for 10 sec |
| Crest Factor |
| 3.0 at full load |
| Voltage Transient Response |
| 0%100%0%; ± 15 % max. |
| (battery mode with R type load) |
| 20%100%20%; ± 9 % max. |
| Voltage Transient Recovery (R |
| Return to nominal voltage within 30 ms |
| type Load) |
| |
|
|
| |
|
| Less than 4m sec | |
| Bypass and Bypass to Inverter |
| |
|
|
| |
| High Efficiency Transfer Time – |
|
|
| Inverter to Bypass and Bypass to |
| Less than 4m sec transfer time |
| Inverter |
|
|
| Short Circuit Protection |
| Electronic overload and short circuit. |
| Voltage Total Harmonic Distortion |
| Less than 3 % THD |
| (Full Linear Load) |
| |
|
|
| |
| Voltage Total Harmonic Distortion |
| Less than 5 % THD |
| (Full |
| |
|
|
| |
| Steady State Output Voltage |
| |
| Regulation |
| |
|
|
| |
| Common Mode Noise |
| less than 0.5Vrms |
| Leakage Current |
| .5mA |
| Surge Protection |
| MOV 260 Jules on Output |
|
| 31 |