12.The heat sink and other components may become extremely hot to the touch. Allow the unit to cool before coming in contact with these items.
13.Warning signs should be placed on or near the load as a notification that the load is being powered by the UPS.
14.Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel.
WARNING
While operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown power to the load.
CAUTION
After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been fully discharged. The UPS could be damaged if the unit is not fully discharged before the breaker is reset.
MAINTENANCE NOTE
The 1000 Series UPS is not designed for
XXIII