Liebert 700VA, GXT3, 3000VA user manual Operating Mode

Page 13

Product Description

Rectifier/Power Factor Correction (PFC) Circuit

In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current achieves two objectives:

Efficient power use by the UPS

Reduced reflected harmonics

This results in cleaner power being available to other devices in the building that are not protected by the UPS.

Inverter

In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC circuit to produce precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power.

Battery Charger

The battery charger utilizes energy from the mains power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is plugged in, even when the UPS is not turned On.

DC-to-DC Converter

The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, increasing reliability.

Battery

The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the Liebert GXT3 in an ambient temperature of 0°C to 25°C (32°F to 77°F).

Optional external battery cabinets are available to extend battery run times.

Dynamic Bypass

The Liebert GXT3 provides an alternate path for mains power to the connected loads in the unlikely event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected loads to bypass.

NOTE

The bypass power path does not protect the connected loads from disturbances on the mains.

1.5Operating Mode

The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery Recharge Mode and Frequency Converter Mode.

For the descriptions of operation mode indicators and control buttons, refer to 3.0 - Operation and Display Panel.

1.5.1Mains (AC) Mode

During Mains (AC) Mode, the mains provides energy to the Liebert GXT3. The filters, PFC circuit and inverter process this power to provide high-level power to connected loads. Meanwhile, the UPS maintains the batteries in a fully charged state.

7

Liebert® GXT3

Image 13
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Troubleshooting MaintenanceOperation CommunicationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols UPS models, power ratings FeaturesModel Nominal Power Rating Available ModelsAppearance and Components Rear Panel FeaturesAppearance Ventilation Slots Operation and Display PanelMajor Components Operating principle diagramOperating Mode Battery Mode Manual Bypass ModeBattery Recharge Mode Frequency Converter ModeInstallation Preparation for InstallationUnpacking and Inspection What’s IncludedTower Installation Mechanical InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Connecting Battery Cables Connecting to AC Mains and LoadsSpecification of input circuit breaker Cable ConnectionConnecting USB Communication Cables Connecting Communication CablesControl Buttons 1 On/Alarm Silence/Manual Battery Test buttonOperation and Display Panel Standby/Manual Bypass buttonLevel Indicators Battery Level Indicators IndicatorsLoad Level Indicators UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Manual Battery Test Startup Checklist for the Liebert GXT3Starting the UPS Manual BypassShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Communication Liebert IntelliSlot Communication CardsLiebert MultiLink USB Port Communication Configuration ProgramOutput voltage option, all models Terminal Block Communication Any Mode ShutdownOn Battery Battery Mode ShutdownLow Battery Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Replacement battery pack model numbersBattery Connector Battery ChargingInternal Battery Pack Handle Pull Out with Battery Handle Checking UPS Status PrecautionsChecking UPS Functions Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Is t Ne tTwor k Care