Liebert GXT3, 700VA Cable Connection, Connecting to AC Mains and Loads, Connecting Battery Cables

Page 21

Installation

11.Through the rack-mount ears, use M5 screws provided in this kit to secure the front of the UPS to the rack’s vertical rails to prevent the UPS from sliding out of position.

12.If optional Liebert external battery cabinets will be connected to the UPS, they can be placed all on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as those for the UPS.

NOTE

Up to four external battery cabinets can be connected to the Liebert GXT3. Each cabinet will increase the battery recharge time.

2.5Cable Connection

The Liebert GXT3 rear panel has an input receptacle and output receptacles. Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet.

2.5.1Connecting to AC Mains and Loads

NOTE

Ensure that all the loads are turned Off.

Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded.

Emerson® recommends installing an upstream circuit breaker of the same series as the Liebert GXT3’s input circuit breaker. The upstream breaker should have a higher capacity than the UPS input circuit breaker.

The specification of input circuit breaker on the rear panel of the UPS is given in Table 2.

Table 2 Specification of input circuit breaker

 

Rated Circuit

Model

Breaker

 

 

GXT3-700RT230

10A

 

 

GXT3-1000RT230

10A

 

 

GXT3-1500RT230

10A

 

 

GXT3-2000RT230

16A

 

 

GXT3-3000RT230

16A

 

 

1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.

NOTE

1. Do not overload any one output receptacle.

2.Output cable length should not exceed 10m (32.8 ft).

3.Plug the input receptacle of the Liebert GXT3 into the input power connection.

2.5.2Connecting Battery Cables

1.Switch Off the input breaker of the battery cabinet.

2.Take out the battery cable included with the battery cabinet.

3.Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.

4.Switch On the battery breaker on the rear of the external battery cabinet.

5.Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.

15

Liebert® GXT3

Image 21
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Troubleshooting MaintenanceOperation CommunicationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols UPS models, power ratings FeaturesModel Nominal Power Rating Available ModelsAppearance and Components Rear Panel FeaturesAppearance Ventilation Slots Operation and Display PanelMajor Components Operating principle diagramOperating Mode Battery Mode Manual Bypass ModeBattery Recharge Mode Frequency Converter ModeInstallation Preparation for InstallationUnpacking and Inspection What’s IncludedTower Installation Mechanical InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Connecting Battery Cables Connecting to AC Mains and LoadsSpecification of input circuit breaker Cable ConnectionConnecting USB Communication Cables Connecting Communication CablesControl Buttons 1 On/Alarm Silence/Manual Battery Test buttonOperation and Display Panel Standby/Manual Bypass buttonIndicators Level Indicators Battery Level IndicatorsLoad Level Indicators UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Manual Battery Test Startup Checklist for the Liebert GXT3Starting the UPS Manual BypassShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert IntelliSlot Communication Cards CommunicationLiebert MultiLink Configuration Program USB Port CommunicationOutput voltage option, all models Terminal Block Communication Any Mode ShutdownBattery Mode Shutdown On BatteryLow Battery Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Replacement battery pack model numbersBattery Charging Battery ConnectorInternal Battery Pack Handle Pull Out with Battery Handle Precautions Checking UPS StatusChecking UPS Functions Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Is t Ne tTwor k Care