Liebert 3000VA Startup Checklist for the Liebert GXT3, Starting the UPS, Manual Battery Test

Page 26

Operation

4.0OPERATION

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS.

NOTE

The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service.

4.1Startup Checklist for the Liebert GXT3

Before starting the UPS, perform these checks:

___ 1. Check that the input plugs and loads are connected properly and reliably.

___ 2. Check that the battery cable is connected properly.

___ 3. Check that the communication cables are connected properly.

4.2Starting the UPS

1.Turn On the input circuit breaker (see Figure 2 for its position).

2.Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three seconds.

After the button is pressed, the LEDs on the display will signal that the unit has initiated the startup process.

3.Once the inverter LED has been illuminated, turn On the connected loads.

4.Check the status indicators to determine whether the Liebert GXT3 is operating normally.

5.Check the load level indicators to verify that the connected load does not exceed the UPS’s rated capacity.

The UPS is now providing conditioned power to the loads.

4.3Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present.

If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.

Retest the batteries after 24 hours of charging.

After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson® representative or Emerson Network Power Channel Support.

If none of the five Battery LEDs illuminate during a manual battery test, check the battery connection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.

If none of the five Battery LEDs illuminate during the second manual battery test, replace batteries and contact your local Emerson representative or Emerson Channel Support.

4.4Manual Bypass

Press the Standby/Manual Bypass button once while the UPS is in Mains (AC) Mode and hold it for about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting.)

Liebert® GXT3

20

Image 26
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Operation MaintenanceTroubleshooting CommunicationFigures Page Important Safety Precautions UPS Safety NotesBattery Safety Information for the Protection of the EnvironmentGlossary of Symbols Model Nominal Power Rating FeaturesUPS models, power ratings Available ModelsAppearance Rear Panel FeaturesAppearance and Components Ventilation Slots Operation and Display PanelOperating principle diagram Major ComponentsOperating Mode Battery Recharge Mode Manual Bypass ModeBattery Mode Frequency Converter ModeUnpacking and Inspection Preparation for InstallationInstallation What’s IncludedConnectors Spacers Support Bases Mechanical InstallationTower Installation Front Plastic Bezel CoverOperation and Display Panel Rotated Clockwise 90 Degrees Liebert GXT3 UPSRack Installation Pulling inner member from each bracket assemblyInstalling rear member of each bracket assembly Installing inner members Specification of input circuit breaker Connecting to AC Mains and LoadsConnecting Battery Cables Cable ConnectionConnecting Communication Cables Connecting USB Communication CablesOperation and Display Panel 1 On/Alarm Silence/Manual Battery Test buttonControl Buttons Standby/Manual Bypass buttonLoad Level Indicators IndicatorsLevel Indicators Battery Level Indicators UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Starting the UPS Startup Checklist for the Liebert GXT3Manual Battery Test Manual BypassDisconnecting Input Power from the Liebert GXT3 Shut Down the Liebert GXT3Liebert MultiLink Liebert IntelliSlot Communication CardsCommunication Output voltage option, all models Configuration ProgramUSB Port Communication Any Mode Shutdown Terminal Block CommunicationLow Battery Battery Mode ShutdownOn Battery Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Replacement battery pack model numbersInternal Battery Pack Handle Pull Out with Battery Handle Battery ChargingBattery Connector Checking UPS Functions PrecautionsChecking UPS Status Indicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmTroubleshooting table Audible AlarmAudible alarm description Condition AlarmEmerson representative or Emerson Channel Support Battery Cabinet Input Breaker External Battery ConnectorSpecifications Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSBattery run time Recharge Time See TableBattery cabinet specifications Operating temperature parametersBattery run times CabinetProduct Warranty Registration Twor k Ne tIs t Care