Liebert GXT3, 700VA, 3000VA user manual Battery Charging, Battery Connector

Page 33

Maintenance

Figure 22 Disconnecting the battery plug and battery connector (front view)

 

 

 

 

Battery Connector

Battery Connector

5.Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in Figure 23.

Figure 23 Pulling out the battery

Internal Battery Pack

Battery

Handle

Pull Out with Battery Handle

6.Unpack the new internal battery pack. Take care not to destroy the packing.

Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support.

7.Line up and slide in the new internal battery pack.

8.Reconnect the battery plug and battery receptacle

9.Gently push the battery wire and internal battery pack back into the UPS.

10.Reattach the front battery door with the six screws.

11.Reattach the front plastic bezel cover to the UPS.

NOTE

The internal battery pack is hot-swappable. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.

Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output power and will drop the connected load.

6.2Battery Charging

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains input power.

If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.

27

Liebert® GXT3

Image 33
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Troubleshooting MaintenanceOperation CommunicationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols UPS models, power ratings FeaturesModel Nominal Power Rating Available ModelsAppearance and Components Rear Panel FeaturesAppearance Ventilation Slots Operation and Display PanelMajor Components Operating principle diagramOperating Mode Battery Mode Manual Bypass ModeBattery Recharge Mode Frequency Converter ModeInstallation Preparation for InstallationUnpacking and Inspection What’s IncludedTower Installation Mechanical InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Connecting Battery Cables Connecting to AC Mains and LoadsSpecification of input circuit breaker Cable ConnectionConnecting USB Communication Cables Connecting Communication CablesControl Buttons 1 On/Alarm Silence/Manual Battery Test buttonOperation and Display Panel Standby/Manual Bypass buttonIndicators Level Indicators Battery Level IndicatorsLoad Level Indicators UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Manual Battery Test Startup Checklist for the Liebert GXT3Starting the UPS Manual BypassShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert IntelliSlot Communication Cards CommunicationLiebert MultiLink Configuration Program USB Port CommunicationOutput voltage option, all models Terminal Block Communication Any Mode ShutdownBattery Mode Shutdown On BatteryLow Battery Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Replacement battery pack model numbersBattery Charging Battery ConnectorInternal Battery Pack Handle Pull Out with Battery Handle Precautions Checking UPS StatusChecking UPS Functions Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Is t Ne tTwor k Care