Liebert 700VA, 3000VA user manual Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS

Page 39

Specifications

9.0SPECIFICATIONS

The specifications of the Liebert GXT3 are listed in Table 11 and Table 12.

Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS

 

 

Product model

Parameters

 

 

 

GXT3-700RT230

 

GXT3-1000RT230

 

 

 

 

Model Rating

700VA/630W

 

1000VA/900W

 

 

 

 

Dimensions, D x W x H, mm (in)

 

 

Unit

497 x 430 x 85 (19.6 x 16.9 x 3.3)

 

 

Shipping

617 x 570 x 262 (24.3 x 22.4 x 10.3)

 

 

 

 

Weight, kg (lb)

 

 

 

Unit

 

16.8 (37)

 

 

 

Shipping

 

20 (44)

 

 

 

 

Input AC

 

 

 

Voltage Range (typical)

230VAC nominal; variable based on output load

 

 

 

90% ~ 100% loading

 

177VAC/280VAC

 

 

 

70% ~ 90% loading

 

168VAC/280VAC

 

 

 

30% ~ 70% loading

 

150VAC/280VAC

 

 

 

0 ~ 30% loading

 

115VAC/280VAC

 

 

Frequency

40Hz ~ 70Hz; Auto Sensing

 

 

 

Input Power Receptacle

 

C14

 

 

 

 

Output AC

 

 

 

AC-AC Efficiency

 

> 88% AC-AC, minimum

 

 

 

Output Receptacles

 

C13 × 6

 

 

Voltage

220/230/240VAC (user configurable); ±3%

 

 

 

Frequency

 

50Hz or 60Hz

 

 

 

Waveform

 

Sine wave

 

 

Mains (AC) Mode Overload

200% for 2 seconds; 150% for 1 minute with transfer to bypass

 

 

 

 

Internal Battery Charger

 

 

 

Charger Current

 

1.3

 

 

 

 

Battery

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

Qty × V× Rating

 

4 × 12V × 5.0Ah

 

 

Battery Mfr/Part#

YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245

 

 

Backup Time

See Table 15 - Battery run times

Recharge Time

3 hours to 90% capacity after full discharge with 100% load till UPS

auto-shutdown (Internal Batteries Only)

 

Environmental Requirements

 

 

 

Operating Temp

0ºC to +40ºC (+32ºF to +104ºF); Table 14 - Operating temperature parameters

Storage Temp

-15ºC to +50ºC (5ºF to 122ºF)

 

 

Relative Humidity

0%RH to 95%RH, non-condensing

 

 

Operating Elevation

Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating

 

 

Storage Elevation

15,240 (50,000 ft.) maximum

 

 

Audible Noise

< 46 dBA, at 1 meter (3.2ft) from the rear

< 43 dBA, at 1 meter (3.2ft) from the front or sides

 

Agency

 

 

 

Safety

IEC/EN/AS 62040-1:2008, GS mark

 

 

RFI/EMI

IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A

 

 

Surge Immunity

IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)

 

 

 

Transportation

 

ISTA Procedure 1A

33

Liebert® GXT3

Image 39
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Communication MaintenanceTroubleshooting OperationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols Available Models FeaturesUPS models, power ratings Model Nominal Power RatingVentilation Slots Operation and Display Panel Rear Panel FeaturesAppearance and Components AppearanceMajor Components Operating principle diagramOperating Mode Frequency Converter Mode Manual Bypass ModeBattery Mode Battery Recharge ModeWhat’s Included Preparation for InstallationInstallation Unpacking and InspectionFront Plastic Bezel Cover Mechanical InstallationTower Installation Connectors Spacers Support BasesLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Cable Connection Connecting to AC Mains and LoadsConnecting Battery Cables Specification of input circuit breakerConnecting USB Communication Cables Connecting Communication CablesStandby/Manual Bypass button 1 On/Alarm Silence/Manual Battery Test buttonControl Buttons Operation and Display PanelIndicators Level Indicators Battery Level IndicatorsLoad Level Indicators UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Manual Bypass Startup Checklist for the Liebert GXT3Manual Battery Test Starting the UPSShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert IntelliSlot Communication Cards CommunicationLiebert MultiLink Configuration Program USB Port CommunicationOutput voltage option, all models Terminal Block Communication Any Mode ShutdownBattery Mode Shutdown On BatteryLow Battery Replacement battery pack model numbers Replacing the Internal Battery PackMaintenance Battery Replacement ProceduresBattery Charging Battery ConnectorInternal Battery Pack Handle Pull Out with Battery Handle Precautions Checking UPS StatusChecking UPS Functions Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsCondition Alarm Audible AlarmAudible alarm description Troubleshooting tableEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Care Ne tIs t Twor k