Liebert 700VA Shut Down the Liebert GXT3, Disconnecting Input Power from the Liebert GXT3

Page 27

Operation

4.5Shut Down the Liebert GXT3

1.Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds.

If manual bypass is not available, disregard the first step.

2.Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds, to shut down the UPS. The UPS will shut down about 30 seconds after the button is pressed.

Power to the connected loads is now Off.

4.6Disconnecting Input Power from the Liebert GXT3

1.After the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert GXT3, disconnect the input cable plug.

2.Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

3.Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering Off the UPS, the UPS ceases output and the load is powered Off.

21

Liebert® GXT3

Image 27
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Communication MaintenanceTroubleshooting OperationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols Available Models FeaturesUPS models, power ratings Model Nominal Power RatingVentilation Slots Operation and Display Panel Rear Panel FeaturesAppearance and Components AppearanceMajor Components Operating principle diagramOperating Mode Frequency Converter Mode Manual Bypass ModeBattery Mode Battery Recharge ModeWhat’s Included Preparation for InstallationInstallation Unpacking and InspectionFront Plastic Bezel Cover Mechanical InstallationTower Installation Connectors Spacers Support BasesLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Cable Connection Connecting to AC Mains and LoadsConnecting Battery Cables Specification of input circuit breakerConnecting USB Communication Cables Connecting Communication CablesStandby/Manual Bypass button 1 On/Alarm Silence/Manual Battery Test buttonControl Buttons Operation and Display PanelIndicators Level Indicators Battery Level IndicatorsLoad Level Indicators UPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Manual Bypass Startup Checklist for the Liebert GXT3Manual Battery Test Starting the UPSShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert IntelliSlot Communication Cards CommunicationLiebert MultiLink Configuration Program USB Port CommunicationOutput voltage option, all models Terminal Block Communication Any Mode ShutdownBattery Mode Shutdown On BatteryLow Battery Replacement battery pack model numbers Replacing the Internal Battery PackMaintenance Battery Replacement ProceduresBattery Charging Battery ConnectorInternal Battery Pack Handle Pull Out with Battery Handle Precautions Checking UPS StatusChecking UPS Functions Indicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsCondition Alarm Audible AlarmAudible alarm description Troubleshooting tableEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Care Ne tIs t Twor k