Liebert 3000VA USB Port Communication, Configuration Program, Output voltage option, all models

Page 29

Communication

5.2USB Port Communication

The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink®. The configuration program can be completed through the communication port.

5.2.1Configuration Program

Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users, the factory default settings will be adequate. This section illustrates the features available for modification, as well as the factory default setting.

The USB configuration program allows these features of the Liebert GXT3 to be changed:

Enable/Disable Auto-Restart

Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled

Set the Low Battery Warning alarm time from 2 to 30 minutes

Enable/Disable the Auto-Battery test

Enable/Disable Auto-Restart after removing Remote shutdown

Set the wiring mode of Remote shutdown

Set the Auto-Enable output

Set the Auto-Battery test to 7, 14, 21 or 28 days

Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Emerson® software products

Select one of multiple output voltages to match various voltages (see Table 6).

Table 6 Output voltage option, all models

Factory Default Setting

Output Voltage Option

 

 

230VAC

220VAC, 230VAC and 240VAC

 

 

NOTICE

The output voltage settings cannot be changed while the UPS is On and powering connected loads.

NOTE

Programming the output voltage of a 230V model of the Liebert GXT3 to 220V automatically derates the UPS to 96% of both the VA and Watt ratings (refer to 9.0 - Specifications for VA and Watt ratings).

NOTE

• This program is compatible with UPS models beginning with ‘GXT3,’ as in ‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.

A computer running Windows 2000®, XP® or Vista® is required to set up and run the configuration program.

23

Liebert® GXT3

Image 29
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Troubleshooting MaintenanceOperation CommunicationFigures Page UPS Safety Notes Important Safety PrecautionsInformation for the Protection of the Environment Battery SafetyGlossary of Symbols UPS models, power ratings FeaturesModel Nominal Power Rating Available ModelsAppearance and Components Rear Panel FeaturesAppearance Ventilation Slots Operation and Display PanelMajor Components Operating principle diagramOperating Mode Battery Mode Manual Bypass ModeBattery Recharge Mode Frequency Converter ModeInstallation Preparation for InstallationUnpacking and Inspection What’s IncludedTower Installation Mechanical InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverLiebert GXT3 UPS Operation and Display Panel Rotated Clockwise 90 DegreesPulling inner member from each bracket assembly Rack InstallationInstalling rear member of each bracket assembly Installing inner members Connecting Battery Cables Connecting to AC Mains and LoadsSpecification of input circuit breaker Cable ConnectionConnecting USB Communication Cables Connecting Communication CablesControl Buttons 1 On/Alarm Silence/Manual Battery Test buttonOperation and Display Panel Standby/Manual Bypass buttonLoad Level Indicators IndicatorsLevel Indicators Battery Level Indicators UPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Manual Battery Test Startup Checklist for the Liebert GXT3Starting the UPS Manual BypassShut Down the Liebert GXT3 Disconnecting Input Power from the Liebert GXT3Liebert MultiLink Liebert IntelliSlot Communication CardsCommunication Output voltage option, all models Configuration ProgramUSB Port Communication Terminal Block Communication Any Mode ShutdownLow Battery Battery Mode ShutdownOn Battery Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Replacement battery pack model numbersInternal Battery Pack Handle Pull Out with Battery Handle Battery ChargingBattery Connector Checking UPS Functions PrecautionsChecking UPS Status Troubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Input Breaker External Battery Connector Battery CabinetSpecifications of GXT3-700RT230 and GXT3-1000RT230 UPS SpecificationsSee Table Battery run time Recharge TimeOperating temperature parameters Battery cabinet specificationsCabinet Battery run timesProduct Warranty Registration Is t Ne tTwor k Care
Related manuals
Manual 13 pages 59.68 Kb