Liebert 700VA, GXT3, 3000VA user manual See Table, Battery run time Recharge Time

Page 40

Specifications

Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230

 

Product model

 

Parameters

 

 

 

 

GXT3-1500RT230

GXT3-2000RT230

 

GXT3-3000RT230

 

 

 

 

 

Model Rating

1500VA/1350W

2000VA/1800W

 

3000VA/2700W

 

 

 

 

 

Dimensions, D x W x H, mm

(in)

 

 

 

Unit

497 × 430 × 85

 

 

602 × 430 × 85

(19.6 x 16.9 x 3.3)

 

 

(23.7 x 16.9 x 3.3)

 

 

 

Shipping

617 x 570 x 262

 

 

717 x 570 x 262

(24.3 x 22.4 x 10.3)

 

 

(28.2 x 22.4 x 10.3)

 

 

 

Weight, kg (lb)

 

 

 

 

Unit

23.2 (51.1)

25.5 (56.1)

 

32.4 (71.4)

Shipping

26 (57.3)

28 (61.7)

 

35 (77.2)

Input AC

 

 

 

 

Voltage Range (typical)

230VAC nominal; variable based on output load

 

 

 

 

 

 

90% ~ 100% loading

177VAC/280VAC

 

 

196VAC/280VAC

 

 

 

 

 

70% ~ 90% loading

168VAC/280VAC

 

 

184VAC/280VAC

30% ~ 70% loading

150VAC/280VAC

 

 

161VAC/280VAC

0 ~ 30% loading

115VAC/280VAC

 

 

115VAC/280VAC

 

 

 

 

Frequency

40Hz ~ 70Hz; Auto Sensing

 

 

 

 

 

 

Input Power Receptacle

C14

C20

 

 

 

 

 

Output AC

 

 

 

 

AC-AC Efficiency

> 88% AC-AC, minimum

 

Output Receptacles

C13 x 6

 

 

C13 x 6; C19 x 1

 

 

 

 

Voltage

220/230/240VAC (user configurable); ±3%

 

 

 

 

 

Frequency

50Hz or 60Hz

 

 

 

 

Waveform

Sine wave

 

Mains (AC) Mode Overload

200% for 2 seconds; 150% for 50 seconds

 

200% for 2 seconds;

 

 

150% for 55 seconds

 

 

 

 

Internal Battery Charger

 

 

 

 

Charger Current

1.88

2.71

 

2.5

Battery

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

 

 

 

Qty × V× Rating

4 × 12V × 7.2Ah

4 × 12V × 9.0Ah

 

6 × 12V × 9.0Ah

 

 

 

 

Battery Mfr/Part#

Panasonic/UP-RW1236

Panasonic/UP-RW1245

 

CSB/ GP 1272

CSB/ HR 1234W F2

Backup Time

See Table 15 -

Battery run time

 

Recharge Time

3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown

(Internal Batteries Only)

 

 

 

Environmental Requirements

 

 

 

 

Operating Temp

0ºC to 40ºC (32ºF to 104ºF); Table 14 - Operating temperature parameters

Storage Temp

-15ºC to +50ºC (5ºF to 122ºF)

 

 

 

 

Relative Humidity

0%RH to 95%RH, non-condensing

 

 

 

Operating Elevation

Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating

 

 

 

Storage Elevation

15000m (50,000 ft.) maximum

 

 

 

 

Audible Noise

< 45 dBA max. at 1 meter (3.2ft.) front and side

< 48 dBA max. at 1 meter (3.2ft.) front and side

 

< 46 dBA, at 1 meter (3.2ft.) rear

< 48 dBA, at 1 meter (3.2ft.) rear

Agency

 

 

 

 

Safety

IEC/EN/AS 62040-1:2008, GS mark

 

 

 

RFI/EMI

IEC/EN/AS 62040-2 2nd Ed. (Category C2) = CISPR22 Class A

 

 

 

Surge Immunity

IEC/EN 62040-2 2nd Ed. (IEC/EN 61000-4-5)

 

 

 

 

Transportation

ISTA Procedure 1A

 

Liebert® GXT3

34

Image 40
Contents Liebert GXT3 UPS 230V 700VA-3000VA Page Table of Contents Maintenance TroubleshootingOperation CommunicationFigures Page Important Safety Precautions UPS Safety NotesBattery Safety Information for the Protection of the EnvironmentGlossary of Symbols Features UPS models, power ratingsModel Nominal Power Rating Available ModelsRear Panel Features Appearance and ComponentsAppearance Ventilation Slots Operation and Display PanelOperating principle diagram Major ComponentsOperating Mode Manual Bypass Mode Battery ModeBattery Recharge Mode Frequency Converter ModePreparation for Installation InstallationUnpacking and Inspection What’s IncludedMechanical Installation Tower InstallationConnectors Spacers Support Bases Front Plastic Bezel CoverOperation and Display Panel Rotated Clockwise 90 Degrees Liebert GXT3 UPSRack Installation Pulling inner member from each bracket assemblyInstalling rear member of each bracket assembly Installing inner members Connecting to AC Mains and Loads Connecting Battery CablesSpecification of input circuit breaker Cable ConnectionConnecting Communication Cables Connecting USB Communication Cables1 On/Alarm Silence/Manual Battery Test button Control ButtonsOperation and Display Panel Standby/Manual Bypass buttonLevel Indicators Battery Level Indicators IndicatorsLoad Level Indicators UPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Manual Battery TestStarting the UPS Manual BypassDisconnecting Input Power from the Liebert GXT3 Shut Down the Liebert GXT3Communication Liebert IntelliSlot Communication CardsLiebert MultiLink USB Port Communication Configuration ProgramOutput voltage option, all models Any Mode Shutdown Terminal Block CommunicationOn Battery Battery Mode ShutdownLow Battery Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Replacement battery pack model numbersBattery Connector Battery ChargingInternal Battery Pack Handle Pull Out with Battery Handle Checking UPS Status PrecautionsChecking UPS Functions UPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionTroubleshooting table Condition AlarmEmerson representative or Emerson Channel Support Battery Cabinet Input Breaker External Battery ConnectorSpecifications Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSBattery run time Recharge Time See TableBattery cabinet specifications Operating temperature parametersBattery run times CabinetProduct Warranty Registration Ne t Is tTwor k Care